NHTC / NHPC ELECTRODE STEAM HUMIDIFIER
Installation Manual

This document and the information disclosed herein are proprietary data of WALTER MEIER LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of WALTER MEIER LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the NORTEC name should be taken as referring to WALTER MEIER LTD.

WALTER MEIER LTD. does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by WALTER MEIER LTD.
Copyright 2008, WALTER MEIER LTD. All rights reserved.
The Specification Label for your NH Series Humidifier is located on the bottom of the unit. You will find it attached to the skirt that separates the electrical and plumbing compartments on the electrical compartment side.
RECORD OF REVISIONS For each revision, put the revised pages in your manual and discard the superseded pages. Write the revision number and revision date, date put in manual, and the incorporator’s initials in the applicable columns on the Record of Revisions.
Date Put In Manual By
Date Put In Manual By



E. HOW TO REMOVE THE STEAM CYLINDER 52 F. MANDATORY CLEANING OF THE DRAIN VALVE 53 G. HOW TO INSTALL THE REPLACEMENT CYLINDER 54
10-40 TROUBLESHOOTING 1. TROUBLESHOOTING NH ELECTRODE STEAM HUMIDIFIERS 56 A. PREPARATION 56 B. STARTING POINT 56 C. NHTC/NHPC 56 2. TROUBLESHOOTING DISTRIBUTORS 58 A. TROUBLESHOOTING ATMOSPHERIC DISTRIBUTORS 58 3. SAM-E TROUBLESHOOTING 58 A. PROCEDURE 58 4. BLOWER PACKS TROUBLESHOOTING 59 A. PROCEDURE 59 5. DIGITAL ON/OFF HUMIDISTAT SENSOR CALIBRATION 59 A. PROCEDURE 59 6. 0-10V DIGITAL HUMIDISTAT SENSOR CALIBRATION 66 A. PROCEDURE 66
10-50 TECHNICAL 1. WIRING AND TERMINALS 68 A. HUMIDIFIER CONTROL INFORMATION 68 B. NH WIRING 69 2. CHECK LISTS 71 A. PRE-NORTEC ONLINE START UP CHECKLIST WIRING 71 B. PRE-NORTEC LINKS START-UP CHECKLIST 71 C. HUMIDIFIER MANDATORY PRE-START UP CHECKLIST 72 D. HUMIDIFIER MANDATORY START-UP CHECKLIST AND QUICK REFERENCE 73 E. PERIODIC MAINTENANCE CHECKLIST AND QUICK REFERENCE 74 3. SPARE PARTS AND EXPLODED VIEWS 76 A. ASD, BSD, CSD DISTRIBUTOR 76 B. SAM-E SPARE PARTS 76 C. NH SERIES HUMIDIFIER SPARE PARTS 77
2008-08-28

10-00 INTRODUCTION Figure 1. NHTC 2 Figure 2. Humidifier Box 4 Figure 3. Distributor Box 4 Figure 4. SAM-e Distributor Box 4 Figure 5. Remote Mounted Blower Pack Box 4 Figure 6. Typical NHTC Installation 6-7
10-10 INSTALLATION PROCEDURES Figure 1. Clearances and Operating Conditions 12 Figure 2. Mounting with Keyholes 12 Figure 3. Mounting with Mounting Bracket 12 Figure 4. Drain Water and Supply Connection 13 Figure 5. Steam Run and Condensate Return Installation Guidelines 15 Figure 6. Steam Run and Condensate Return Installation Guidelines 16 Figure 7. Primary Voltage Supply Wiring 18 Figure 8. On-Off Control Guidelines and Low Voltage Terminal Strip 20 Figure 9. NORTEC Control Guidelines and Wiring (Optional) 21 Figure 10. Setpoint Versus Outdoor Temperature 22 Figure 11. NORTEC Humidity Transducer Guidelines and Wiring (Optional) 24 Figure 12. Networking NHTCs (Optional) 25 Figure 13. NORTEC OnLine Installation Guidelines (Optional) 26
10-20 OPERATION Figure 1. NHTC Components (Front View) 28 Figure 2. NHTC Components (Side View) 28 Figure 3. Humidifier Start-Up 31 Figure 4. Drain Rate Versus Water Conductivity 31 Figure 5. Capacity Setting and Cylinder Life 31 Figure 6. Basic Steam Production Method 32 Figure 7. Software Flow Chart 34 Figure 8. Steam Distributor Operation 44 Figure 9. SAM-e Operation 45 Figure 10. Blower Pack Operation and Adjustments 45 Figure 11. NORTEC Digital Controller 46 Figure 12. Difference from Setpoint in Relation to Demand Signal 47 Figure 13. Duct and Wall Mounted Transducer 47
10-30 MAINTENANCE PROCEDURES Figure 1. Cylinder Components 51 Figure 2. Cylinder Removal Procedure 52 Figure 3. Drain Valve Maintenance 53 Figure 4. Cylinder Replacement Procedure 54
10-50 TECHNICAL Figure 1. NHTC/NHPC Double Unit Wiring Diagram 69 Figure 2. NHTC/NHPC Wiring Diagram 70 Figure 3. Distributor Exploded View and Spare Parts 76 Figure 4. SAM-e Exploded View and Spare Parts 76 Figure 5. NHTC/NHPC Plumbing Compartment Exploded View and Spare Parts 77 Figure 6. NHTC/NHPC Electrical Compartment Exploded View and Spare Parts 80
Figure Page

10-10 INSTALLATION PROCEDURE Table 1. Maximum Recommended Length of Steam Runs 14 Table 2. Steam Line Material 14 Table 3. Recommended Material and Size for Steam Run 14 Table 4. Recommended Condensate Line at Distributor(s) 17 Table 5. Equivalent Length Elbow and T-Fittings 17 Table 6. Humidifier and Distributor Inlet/Outlet Sizes 17
10-20 OPERATION Table 1. NHTC / NHPC Components 29-30 Table 2. Self-Test Messages 32 Table 3. Signal Light Status 41 Table 4. Status Messages with LED State 42
10-40 TROUBLESHOOTING Table 1. Troubleshooting Symptoms 57 Table 2. Ensuring A Demand Signal 58 Table 3. NH System Messages 60 Table 4. Term Definitions 66
10-50 TECHNICAL Table 1. Controller and Sensor Specifications 68 Table 2. NHTC/NHPC Plumbing Part List 78 Table 3. NHTC/NHPC Electrical Parts List 81
Table Page







(1) Check packing slip to ensure ALL material has been delivered.
(2) All material shortages are to be reported to NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period.
(3) Inspect shipping boxes for damage and note damages on shipping waybill accordingly.
(4) After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
(5) All NORTEC products are shipped on an FOB factory basis. Any and all damage, breakage or loss claims are to be made directly to the shipping company.
(1) The equipment packaging is standardized in that each box in the shipment will always have the same contents. The following paragraphs identify the contents of each box.
(1) The typical equipment found in the humidifier and controls box is shown in Figure 2. The contents of the box are listed on the box. If controls are ordered they will be listed and small accessories that fit into the box will also be listed on the box.
(1) Depending on the equipment ordered any of the following distributor box configurations may be received:
a. For equipment received if an ASD, BSD, CSD distributor(s) is ordered refer to Figure 3.
b. For equipment received if a SAM-e distributor is ordered refer to Figure 4.
c. For equipment received if a RMBP is ordered refer to Figure 5.
(1) Additional accessories such as DWC, DWSP, Filter, and Fill cup extension kits are shipped in a separate box. Smaller accessories that would fit in the humidifier box are put in the humidifier box and the box is identified as containing such.


BAG WITH MANUAL, CLAMPS, HOSE SECTION


STEAM HOSE SECTION (NOT SUPPLIED IF BUILT ON BLOWER PACK ORDERED)



Figure 3. Distributor Box
Figure 2. Humidifier Box






Figure 5. Remote Mounted Blower Pack Box

(1) Ensure that available voltage and phase corresponds with humidifier voltage and phase as indicated on humidifier’s specification label.
(2) Ensure that the dedicated external fuse disconnect is of sufficient size to handle the rated amps as indicated on the specification label. Refer to local codes.
(3) Report any discrepancy immediately to the site engineer.
(4) Location and mounting is described in Chapter 10-10.
(5) Typical installation (See Figure 6.) shows the references to the appropriate chapter of the manual.













































(1) The NORTEC NHTC series humidifier is designed to mount on a suitable wall or vertical surface. Do not sit the unit on the floor due to clearances required for plumbing and electrical connections. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance on the humidifier. Local and national codes should be consulted before final location and installation of the humidifier. NORTEC cannot accept responsibility for installation code violations. See Figure 1 Clearances and Operating Conditions.
(2) The location of the humidifier should be below the steam distributor. DO NOT locate the humidifier any further then absolutely necessary from the steam distributor location as net output will be reduced as a result of heat loss through the steam line.
(3) When possible, mount the NHTC humidifier at a height convenient for servicing.
(1) The NHTC series humidifier is wall mounted using keyholes located on the back of the unit’s cabinetry. The keyholes are spaced 16 inches apart center to center for large units and 10.7 inches apart for small as per UL certification standard stud spacing dictates.
(2) Use #12 x 3 in. screws. 2 screws are needed for a single unit (NHTC 010 to 100 lbs/hour). 3 screws are needed for a double unit (NHTC 150 to 200 lbs/hour). Insert the screw 16 in. apart. Be sure the screws are level to each other. Proceed to insert the screws into the studs until there is 1/4 in. of screw exposed. Ensure the screws are properly anchored to the wall.
(3) Raise the unit. Align the keyholes on the back of the unit with the screws. Place the screws through the keyholes. Make sure the unit is level then tighten the screws to secure the unit in place.
(4) Once the unit is securely fixed to the wall, install the “L” shaped brackets into the same studs the unit is attached to. Place the brackets on top of the unit, inline with the studs. Using the appropriate sized wood screw fasten the “L” brackets to the studs securing the unit from any upward motion. See Figure 2 Mounting with keyhole.
(1) For NHTC units that mount using a Wall mounting bracket 3 x #12 3.0 inch wood screws are to be used.
(2) Wall mounting bracket provided should be securely attached horizontally with open edge upwards, using field-supplied fasteners. Be sure the bracket is mounted level See Figure 3.
(3) If humidifiers are mounted on a roof, a thermostatically ventilated weather proof cabinet should be used. Consult factory.

(4) All water supply and drain line connections should be installed in accordance with local plumbing codes.
(5) For installation details see Figure 5 & 6.
CAUTION
DRAIN WATER FROM HUMIDIFIER CAN BE VERY HOT.
(1) The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons.
(2) For installation details see Figure 4.
(1) Tables 1 through 6 indicate what material and recommended length to use when installing atmospheric steam lines. The lengths mentioned are equivalent feet and therefore the full length of tubing with the addition of equivalent feet of elbows and tees.
(2) Figure 5 illustrates the guidelines for installation, routing and trapping of steam runs and condensate returns.
(3) Table 6 indicates steam outlet size of humidifier and steam inlet size of distributors.










Figure 1. Clearances and Operating Conditions





Figure 3. Mounting with Mounting Bracket



Table 1. Maximum Recommended Length of Steam Line Unit Size Steam Output Distance Possible Loss Steam Line Size NH-005 5 lbs/hr 8 feet 1.0 lbs/hr 3/4 NH-010 10 lbs/hr 15 feet 1.5 lbs/hr 3/4 NH-020 20 lbs/hr 20 feet * 2.0 lbs/hr 3/4 NH-030 30 lbs/hr 25 feet * 2.5 lbs/hr 3/4 NH-050 50 lbs/hr 40 feet ** 4.0 lbs/hr 1 ½” NH-075 75 lbs/hr 50 feet ** 5.0 to 10.0 lbs/hr 1 ½” NH-100 100 lbs/hr 50 feet ** 5.0 to 10.0 lbs/hr 1 ½” NH-150 150 lbs/hr 50ft/cylinder ** 5.0 to 10.0 lbs/hr 1 ½” cyl NH-200 200 lbs/hr 50ft/cylinder ** 5.0 to 10.0 lbs/hr 1 ½” cyl * Use one inch copper steam line for longer runs. ** Use two inch copper steam line for longer runs.

(RO or DI) Short Run < 10 feet (3m) yes yes yes Long Run > 10 feet (3m) no yes yes
Table 3. Recommended Materials and Sizes for Steam Runs Unit Size Steam Run Steam Line Material Steam Line Description
lbs/hr kg/hr ft m
0-30 0-13 0-10 0-3 Copper Tube 0.750 in MED-L Tubing (0.875 inch OD)
0-30 0-13 30+ 3+ Copper Tube 1.0 inch MED-L Tubing (1.125 inch OD)
0-30 0-13 0-10 0-3 Stainless Steel Tube 0.875 inch Tube x 0.049 inch thick
0-30 0-13 30+ 3+ Stainless Steel Tube 1.125 inch Tube x 0.049 inch thick
50-100 22-45 0-20 0-6 Copper Tube 1.500 in MED-L Tubing (1.625 inch OD)
50-100 22-45 20+ 6+ Copper Tube 2.0 inch MED-L Tubing (2.125 inch OD)
50-100 22-45 0-20 0-6 Stainless Steel Tube 1.750 inch Tube x 0.065 inch thick
50-100 22-45 20+ 6+ Stainless Steel Tube 2 inch Tube x 0.065 inch thick


















Figure 5. Steam Run and Condensate Return Installation Guidelines (Sheet 1 of 2)




















Figure 6. Steam Run and Condensate Return Installation Guidelines (Sheet 1 of 2)


0.250 inch. MED-L Tubing (0.375 inch OD) 0.375 Tube 0.049 inch thick
0.500 inch. MED-L Tubing (0.875 inch OD) 0.650 Tube 0.049 inch thick

0.750 / 0.875 in. 2 ft. 1 ft. 4 ft.
1.500 / 1.750 in. 3 ft. 6 in. 1ft. 9 in. 7 ft.
2.000 / 2.500 in. 4 ft. 6 in. 2 ft. 3 in. 10 ft.

NH 5-30 0.875 in. OD ASD, BSD 0.875 inch OD
NH 50-100 1.75 in. OD CSD 1.75 inch OD
NH 150-200 Two 1.75 in. OD Blower Pack 0.875 inch OD or 1.75 inch OD
** mini SAM-e inlet is determined on order and may have two 1.75 in. OD inlets.



















(1) Primary Voltage Supply Wiring to Humidifier
(a) Local electrical codes should always be followed when installing a NORTEC Humidifier. Direct wiring to the high voltage terminal is shown in Figure 7.
(1) Controls are available from NORTEC as accessories. If controls were not ordered with humidifier, they must be purchased or supplied by others. The following information is relevant to all controls, factory supplied or otherwise.
REGARDLESS OF SELECTING ON/OFF OR MODULATING CONTROL METHOD, NORTEC HUMIDIFIERS MUST HAVE A CLOSED CIRCUIT ACROSS ITS ON/OFF SECURITY LOOP CONTROL TERMINAL TO OPERATE. NORTEC HIGHLY RECOMMENDS THE USE OF A HIGH LIMIT HUMIDISTAT AND AN AIR PROVING SWITCH IN SERIES FOR THIS FUNCTION.
The method and guidelines for installing on/off controls are displayed in Figure 8. It can be combined with all control methods.
(b) Demand Signal Controls Installation
Figure 9 uses the Nortec optional Controllers to demonstrate the typical demand signal installation.
(a) On-Off Controls






(1) Each humidistat and controller is equipped with an integrated reset function that will limit the setpoint during cold weather operation. This will prevent condensation on windows and building structures. Figure 10 illustrates how the setpoint reset feature operates.
(2) This feature is enabled by removing the jumper from terminals 8 and 1 on the humidistat and wiring the outdoor temperature sensor to these terminals.
(3) When the outdoor temperature setback feature is in effect, the humidistat will normally display the calculated setpoint limit based on the outdoor air temperature. A snowflake will also be displayed to indicate cold weather operation. When any key on the controller is pressed, the LCD screen will display the customer specified setpoint for a short duration.

Figure 10. Setpoint Versus Outdoor Temperature

(1) Figure 11 displays the NORTEC optional humidity transducer installation.
(1) The wiring of master/slave networks are explained in Figure 12. It allows operation of multiple NHTCs with one control signal.
(1) An abbreviated recommended installation of NORTEC OnLine and its components are shown in Figure 13.






























































(1) Refer to Figures 1 and 2 when reading Table 1.
(1) Figure 3 describes the method for powering up a humidifier and the cautions to take.
(1) Figure 6 describes the method the NH Series humidifier uses to produce pure clean
steam. The NORTEC NH electrode steam humidifier uses NORTEC’s patented Auto- Adaptive cycle to calculate drains to maintain optimal performance. Figure 4 Drain Rate vs Water Conductivity depicts an indication of drain amounts.
(1) The output of all NH Series humidifiers is pure, clean steam; minerals originally in the
incoming water are left behind. These minerals will eventually coat the cylinder electrodes. Therefore, the mineral content of the incoming water, the unit running time and output capacity setting ultimately determine cylinder life. NORTEC’s cylinder life is up to 2,000 hours of operation. Water chemistry and capacity can affect cylinder life. (See Figure 5.) See Table 4 to identify the message which indicates when the cylinder is at the end of its life.


Figure 2. NHTC Components (Side View)

Item Number Component Name Description
1 Steam Connector Used to allow easy replacement of cylinders without disconnecting the steam line.
2 Condensate Return This inlet is to return condensate to the unit.
3 Fill Cup The fill cup allows isolation from the fill line by supplying an air gap. It will also overflow any water that cannot enter the cylinder to drain.
4 Float Chamber (Optional) Detection OPTION – Used with the advanced foam detection setting.
5 Manual Drain Button By pushing this button, manual drain is initiated with software support. Software support supplies drain cooling if enabled and will disable manual drain after 10 minutes.
6 Door Interlock The door interlock prevents the unit from running when the front door is off. For startup and troubleshooting, pulling this interlock will overide this safety feature.
7 Back-up Drain Back-up drain switch allows the draining of the cylinder without electronic support.
8 Fill Valve The fill valve allows water to flow up to the fill cup. In units with Drain Water Cooling to 120 degrees option, this valve is a dual valve. The second valve is wired in parrallel with the drain valve to quench the water with fresh cold water everytime the drain is activated.
9 Drain Canal The drain canal allows all drainable water to accumulate into one location to then be drained away.
10 Drain Valve Drain valve when energized will allow water to flow down to the drain canal. When not energized, water flowing from the fill cup will flow up into the cylinder.
11 Transformer The transformer converts the primary supply voltage to the required 24 VAC to the unit electronics. It is protected by a fuse to ensure that the 24 VAC electronics are protected from surges or shorts.
12 On/Off Switch Turns the unit power on and off. Be aware that high voltage will still enter the unit even though the 24VAC electronic are disabled. The contactor will not be energized. Main shut-off should be open before any servicing is performed.
13 Graphical Display and Menu Buttons
The graphical display and buttons are used to navigate through the software. Use software flowchart as a reference.
14 Remote Relay Board (Optional) The remote relay board is a set of 4 dry contacts, rated for 24 VAC 1A, which activate in conjunction with humidifier on, steam production, service and error conditions.
15 NORTEC Cylinder The NORTEC disposable cylinder contains electrodes that become energized when the contactor is closed. This allows current to pass through the water from one electrode to another, generating heat within the water. The water then boils and the output is clean pure steam.

Item Number Component Name Description
17 Cylinder Plug Cylinder plugs are press fit on cylinder electrode pins. These color coded connections should fit snuggly, on same color pins. Replace if loose or frayed.
18 Low Voltage Terminal Strip The low voltage terminal strip is the location at which all controls are connected. See Installation for details.
19 Driver Board The driver board(s) is the housing of all fuses and relays. It is connected to the total controller, and monitor and activate all humidifier states.
20 Contactor The contactor(s) when energized allow main power to energize the cylinder electrodes, allowing current to pass, boiling the water.
21 NORTEC OnLine Module (Optional)
NORTEC ONLINE OPTION NHTC ONLY. This module allows the NHTC to be connected to the internet and communicate information to NORTEC via the internet. See NORTEC OnLine operation for details. NHTC only
22 Links Module (Optional)
NORTEC LINKS OPTION NHTC ONLY This module allows the NHTC to communicate with a BMS system using the communication protocol requested at order. See NORTEC Links operation for details. NHTC only
23 Network Terminal Strip The network terminal strip allows up to 13 NHTC units to be connected on one Links module and eight OnLine modules. See Installation of NORTEC Links and OnLine for details on wiring humidifier networks.
24 Fuse Holder OPTIONAL FUSE PACKAGE provides protection of individual high voltage lines in the humidifier and does not replace fuse and external disconnect.
25 High Voltage Terminal Strip Connection point of main power lines to the humidifier from the underside of the strip. It is accompanied by a ground terminal which grounds the cabinet.
26 Total Controller The total controller board (hidden in this view) is part of the graphical display. It is the microcomputer that sends and collects information from the driver boards, network modules and any other humidifier connected to it.




Figure 5. Capacity Setting and Cylinder Life
Conductivity



Table 2. Self-Test Messages
Graphic Display Explanation/Comments (What You Read)
The unit is beginning its bootup routine, along with powering up the EEPROM on the SMART Cylinder
The unit reads the type of cylinder to provide maximum control of operation. If it unable to do so it will skip the rest of the self-test and fault out.
SELF TEST CYLINDER Inlet Valve ESC
Unit energizes the fill valve for 1 second.
SELF TEST CYLINDER Drain Valve ESC
Unit energizes the drain valve for 2 seconds.
SELF TEST CYLINDER Heat Cont. ESC
Unit closes the contactor for 2 seconds.
SELF TEST CYLINDER Pump ESC
Unit activates the pump (if present) for 2 seconds.
SELF TEST CYLINDER Bleed Valve ESC
Unit activates the bleed valve (if present) for 2 seconds.
SELF TEST REMOTE Steam Relay ESC
Unit activates the steam relay for remote fault indication package and green light.
SELF TEST REMOTE Service Relay ESC
Unit activates the service relay for remote fault indication package and yellow light.
SELF TEST REMOTE Error Relay ESC
Unit activates the error relay for remote fault indication package and red light.
SELF TEST REMOTE Oper. Relay ESC
Unit activates the unit on relay.
(1) The flow chart in Figure 7 depicts the software logic and definitions.
(1) The microcomputer applies corrective actions whenever its self-diagnostics identifies a
problem that it is able to correct by itself. If the corrective action is not successful then it displays a system message. If the corrective action requires a service person, then the microcomputer’s only resort is to stop the unit and display a system message. The unit never stops unless it has to.
(2) After three days of no call from either the on/off controls or the modulating controls,
when active, the three-day drain active feature is automatically activated long enough to drain all water from the steam cylinder. This NORTEC feature will prolong the life of the cylinder. (User selectable, default is ON.)















(1) Table 3 describes general signal light status meanings.
OFF OFF OFF Unit is on standby or humidifier has just been energized but has not sensed production of steam yet.
OFF ON OFF Humidifier senses production of steam.
ON OFF OFF An attention state exists that should not prevent the unit from producing steam when the controls call for it. Check the message on the screen to try to correct it.
ON ON OFF Prepare to replace cylinder or normal startup operation. May also indicate an attention during operation. Check the message on the screen to try to correct it.
BLINK OFF OFF Manual Drain On with software drain switch.
OFF BLINK OFF Unit sees a demand, but safeties are open.
OFF OFF ON Operation fault (unit will not run).
(2) Table 4 describes common status messages and the lights displayed for each and their
meaning. For a list of warnings and faults, see Chapter 10-40 Troubleshooting.
(1) The unit will report only one cylinder at a time if the unit was ordered without coupled
circuits. You will notice on the screen the indication of which cylinder you are monitoring and in the lower right the option to monitor the alternate cylinder.
Yellow Green Red

NHTC Display Message LED state System Action
Idle None Unit is made idle.
Humidifying GRN (after steam production starts)
The unit has closed the contactor and is sending current to the cylinder to humidify.
MANUAL DRAIN: ON YEL (blink) The drain valve is activated.
SAFETY LOOP; OPEN GRN (blink)
Steam production stopped.
LEVEL SENSOR; ON None Deactivates the fill valve to prevent overfilling.
KEEP WARM ACTIVATED None Keep Warm feature activated, it has closed the contactor to warm the water.
W19: Cylinder spent YEL, GRN The electronics allow the cylinder to be reset up to four times before locking out the humidifier.
E19: Cylinder spent YEL, RED Humidifier interrupts operation and the fault relay is activated.
FOAM: FULL TANK FLUSHING None The unit will initiate a flush of the cylinder and resume operation.

Symptom Diagnosed Probable Cause Corrective Action
Unit is awaiting a demand or control signal.
This is normal when there is no need for humidity. If you believe there is a need for humidity, and the unit should not be idle, refer to troubleshooting
The unit is now boiling water in the cylinder and filling as necessary.
This is normal when there is a need for humidity. If you believe there is no need for humidity, and the unit should idle, refer to troubleshooting
This is not a fault or warning. It is an indication that the manual drain switch has been activated.
Manual drain switch has been activated. Press Manual Drain button again to stop the drain action.
Safety loop circuit (terminal 1 and 2) is open.
One or more of the safety devices is open as the result of a device failure, improper installation or an unsafe condition has been detected.
Determine which device is preventing continuity of the safety loop circuit, and verify that it is functioning properly and is properly installed and calibrated.
Water has reached the top of the cylinder and has activated the high water sensor. This is not an error or fault, but is normal on start-up and at the end of a cylinder life span.
If foaming is determined to be the cause of the high water indication, consult your local representative about possible adjustment and/or a foam detection kit. If not foaming, consider it normal operation unless water level is not at the top of the cylinder.
Keep Warm feature is enabled and proceeding to a Keep Warm Cycle.
Unit is entering the Keep Warm cycle. The unit has been inactive for a given period and is keeping the water warm.
Normal for unit with Keep Warm setting activated.
Electronics have determined cylinder is spent. Within the next 72 hours the humidifier will stop.
The cylinder must be replaced with the same type and model.
When ordering a new cylinder, quote the model number presently installed in the humidifier.
Electronics have determined that the cylinder is spent.
The cylinder must be replaced with the same type and model.
When ordering a new cylinder, quote the model number presently installed in the humidifier.
The electronics has detected foaming within the cylinder (only for units with the optional Foam Detection Package).
The unit has detected a foaming condition within the cylinder.
The unit will initiate corrective action on its own.
Normal Operation · Normal Operation

(1) Figure 8 describes the method by which the steam distributor releases pure clean
steam into the duct while collecting condensate and removing it by the condensate return.
(1) Figure 9 describes the method by which the Short Absorption Manifold releases pure
clean steam into the duct while collecting condensate, removing it by condensate return and ensuring short absorption distance.
WARNING
DURING AND FOLLOWING OPERATION OF THE HUMIDIFIER, THE STEAM AND COMPONENTS IN CONTACT WITH THE STEAM ON THE BLOWER PACK CAN BECOME HOT AND CAN BURN IF TOUCHED.
(1) Figure 10 describes the method by which the blower pack distributes the pure clean
steam directly into the space required. It also describes the adjustments that can be made to conform to the specific situation.





(1) Figure 11 shows the components of the NORTEC Controller and how to adjust the
setpoint.
(2) In the case of a modulating NORTEC Controller, Figure 12 shows the relation between
the difference from setpoint to %rh in the room and the 0-10 V DC demand signal sent out. From this basis the NORTEC Controller uses its PI algorithm to adjust its demand signal in accordance with the history of the environment. This type of control allows for tighter and more precise control.
(1) The NORTEC digital transducers, shown in Figure 13, are designed to sense humidity
in duct or in room respectively, and report it back to a controller or the NHTC directly. Required humidifier output is determined by controller or humidifier.
CAUTION
NORTEC DOES NOT RECOMMEND USING THE DRY RELAY CONTACTS WITH ANYTHING MORE THAN 24 VAC, 1 AMP.
(1) The NHTC reports the signal light status, in Table 3, by closing the supplied dry contact
relays which can be wired back to a BMS or monitoring station. This method of monitoring is not as informative as the actual display, but alerts you to the general status of the unit.


(1) NORTEC LINKS 2 is an option that can be integrated with the NHTC. This allows a
BMS to monitor and in the right configuration, control the humidifier. For additional information about NORTEC Links and its operation and configuration, go to www.humidity.com and look up the NORTEC LINKS 2 manual.
(2) Table 5 contains a list of NORTEC LINKS 2 variable definitions. For a complete list,
contact the factory.
(1) NORTEC OnLine is an option that can be integrated with the NHTC. This allows a user
to log onto the internet, go to www.norteconline.com and log in to allow them to monitor their unit from any computer with an internet connection. (See Figure 14)
(2) After initially logging into the NORTEC OnLine server the user will be presented with a
list of humidifiers currently registered with the Server program. Each humidifier will be listed with a unit type identifier, a serial number and an address descriptor.
(3) By clicking on the humidifier name, the user will then be brought to a status screen with
an image of the selected humidifier.
(4) Figure 14 shows a typical NORTEC OnLine Monitoring Screen. Use this manual in
combination with NORTEC OnLine to be able to monitor and understand the settings possible through the NORTEC OnLine Interface.


Figure 13. Duct and Wall Mounted
Relation to Demand Signal
Transducer


PROCEDURES

Typical tools required for any maintenance procedure: - Slotted Screwdriver - Small Slotted Screwdriver - Phillips Screwdriver - Needle-Nose Pliers - Wrench
WARNING
DISCONNECT MAIN POWER BEFORE ANY SERVICING.
THE PLUMBING AND ELECTRICAL COMPARTMENTS CONTAIN HIGH VOLTAGE COMPONENTS AND WIRING. ACCESS SHOULD BE LIMITED TO AUTHORIZED PERSONNEL ONLY.
(1) The NHTC and its components are a very low maintenance system. The only
maintenance normally required is to change the cylinder, clean out the drain valve assembly, clean out the inlet valve screen and know the procedure for extended shut- down and start-up.
(1) The steam cylinder is disposable and must be replaced at end of cylinder life. Cylinder
life is dependent on water supply conditions and humidifier usage. Failure to replace the cylinder at the end of cylinder life will cause the unit to lock out. NORTEC is not responsible for any damages resulting from, or attributed to, the failure to replace a spent cylinder (see Manufacturer’s Warranty). There are many indications, each of which signifies the end of cylinder life. See 10-20 Operation, Table 4, for details on how the unit functions and determines end of cylinder life.
(1) As long as the NHTC is powered, it will automatically drain the cylinder when there has
not been a call for humidity for an extended period of time. This feature will reduce or prevent the possibility of corrosion of the electrodes and the accumulation of algae and bacteria growing in the cylinder. The cylinder will remain empty until there is a call for humidity at which time the fill valve will open and refill the cylinder. The unit will go through its normal process for optimum operation.
(2) Should it be required to disconnect power to the humidifier for a period of extended
shut-down, always drain the cylinder first. Leave the switch in the OFF position and ‘open’ the main external fused disconnect to stop power to the humidifier. Close the shut-off valve in the water supply line feeding the humidifier.

(1) Consult Figure 1 for NORTEC cylinder components.


(1) Consult Figure 2 for removal of the steam cylinder.


(1) Always clean the drain valve before installing a new cylinder since the valve port may
be as dirty as the used cylinder. Figure 3 describes the process of removing and cleaning the drain valve. Perform paragraph E. before proceeding.


(1) Consult Figure 4 to install the replacement cylinder.



(1) Ensure the installation detail conform to installation requirements.
(2) Understanding the Principle of Operation and the software menus is an asset when
troubleshooting. This information is found in chapter 10-20 Operation and can be elaborated on by your local representative.
(3) When contacting your local representative or NORTEC for troubleshooting assistance,
please ensure the serial number has been obtained for reference purposes.
(4) Whenever the troubleshooting steps indicate a problem with the main pc-board, first
check all connections at the main PCB (including the ribbon cable connections at the center of the main PCB) before ordering replacements.
(1) Table 1 checkpoints will allow for faster troubleshooting. Ensuring that all these steps
are taken is good practice when beginning to troubleshoot the NH series humidifier. Check your symptom and verify all points before ordering any replacement parts or contacting your local representative. Use the wiring diagram when necessary for clarification.
Wiring diagrams on unit supersedes diagrams in this manual.
BE AWARE, WHEN TROUBLESHOOTING, THAT THE HUMIDIFIER IS POWERED BY HIGH VOLTAGE AND FAMILIARITY WITH BOTH GOOD PRACTICES AND WIRING OF THE HUMIDIFIER IS RECOMMENDED. ANY TROUBLESHOOTING THAT REQUIRES OPENING THE CABINET SHOULD BE DONE BY QUALIFIED PERSONNEL.
(1) The self-diagnostic system built into the NHTC is continually checking the status of the
electrical circuits to the fill valve, drain valve, primary voltage contactor, high water sensor and steam cylinder. The modulating signals from external humidistat and reduced manual capacity settings are taken into consideration. When problem symptoms are found, the NHTC/NHPC will take self-corrective actions, if applicable. It will, if necessary, respond by shutting itself down. Table 3 describes some of the conditions the NH unit can detect and warn or protect itself against. Table 4 contains a definition of the terms used in this section.

System What to Check Why
Nothing is happening when the on/off switch is turned on
Main power is on and matches the specified voltage on the specification label.
No, or improper voltage can cause the electronics or components not to respond.
24 VAC output from the step-down transformer. Check high and low voltage.
24 VAC is required to power nearly all the components of the humidifier, including the electronics.
Ensure that fuses in the humidifier and on the electronic boards are good. Ensure that 24 VAC is getting to the main board.
The fuses are in place to prevent damage to the electronics. If there was a surge the fuse may have blown to prevent damage to the unit.
Door interlock open. The door interlock has malfunctioned.
The unit will not fill or fills very slowly (less then 1” per minute)
Water supply is on and water pressure is between 30 to 80 psig
The proper water volume and pressure must be available as the valves in the NH unit rely on its pressure to control volume and operation. NORTEC recommends 55 to 60 PSIG.
Unit is getting a demand signal or the unit is producing the required steam capacity. See ensuring demand Table 2.
The unit will not activate the fill valve without a demand for humidity. It will also only fill as necessary once there is a demand. Once it reaches the requested demand, it will stop filling.
No leak at drain valve or around cylinder. Check for water coming out of the drain. Check the fill valve inlet. Check fill valve strainer. Check optional inline filter.
The cylinder is held in by gravity and sealed by an O-ring. If not properly seated, it could leak and prevent the unit from filling.
Pressure in the steam line could also prevent filling causing the water in the fill cup to overflow to drain.
Strainer is clogged.
Fill valve may also be restricted after capturing debris in its filter.
Unit will not humidify or is not reaching requested capacity.
Unit is getting a demand signal. Refer to Table 2.
Unit will not send power to the cylinder without a demand and safeties met.
Capacity is manually limited. The unit will not surpass the capacity dictated by the user in the software.
Cylinder is full. The unit will not fill further than a full cylinder. Operation requires it to try to concentrate the conductivity, which may take several hours, before it reaches full capacity.
Unit has faulted or has a warning
Check Table 3, Faults and Warning Codes Each code is identified and each has individual causes and solutions.
Drain stuck open

Check Why and How
Safety Loop (terminal 1 and 2) is closed
The safety loop is checked to ensure that it is safe to operate. Checking to see 24 VAC from terminal 1 to ground, and terminal 2 to ground should indicate whether is closed.
If found to be open, isolate which component in the safety loop is open to solve the issue. If suspect, confirm that it is connected and operating properly.
Channel 1 has a signal. Whether for on/off or modulating, a voltage potential signal must be present between terminal 3 and 4 for the humidifier temperature.
If on/off there should be 5 VDC.
If VDC modulating, at least 25% of total possible signal must be present.
If mA controlled, at least 25% of total possible signal must be present.
If Transducer signals, the unit setpoint must be higher then the sensed room RH signal.
Channel 2 has a signal Only applicable if configured to accept dual channel input.
If VDC modulating, at least 25% of total possible signal must be present.
If mA controlled, at least 25% of total possible signal must be present.
If Transducer signals, the high limit setpoint must be higher than the sensed RH signal.
KEEP IN MIND WHEN TROUBLESHOOTING DISTRIBUTORS THAT THEY ARE BEING USED WITH STEAM AND THEREFORE, ARE AND CAN REMAIN VERY HOT DURING THE TROUBLESHOOTING PROCESS.
(1) If the distributor is spitting out water, ensure that the distributor is installed level and
check the condensate return for proper slope, check head above the trap, and check the trap that it is clear of obstructions.
(2) If the distributor is condensing inside the duct, make sure the installation clearances
are as indicated in Chapter 10-10 Installation, and make sure that the design conditions have not changed. If over humidification of the duct results, check controls and safeties (ensure safeties are properly installed and functioning). 3. SAM-e TROUBLESHOOTING
(1) If the SAM-e is spitting out water, ensure that the distributor is installed per instructions
in Chapter 10-10 Installation and check the condensate return for proper slope and trap and that it is clear of obstructions. The condensate return must be the lowest point of the SAM-e header.

(2) If the SAM-e is condensing inside the duct, make sure that the design conditions have
not changed.
(3) If grommets leak, make sure the tubes are firmly inserted, if cracks or damage are
(1) An optional blower pack (BP), ensure power supplied to blower pack either from
humidifier or other source, if present, gets its primary voltage from inside the humidifier. This way, only one external power source has to be connected to the equipment. Confirm this power source before troubleshooting the blower pack.
(2) Ensure blower pack is installed per Chapter 10-10 Installation.
(3) If fans are not functioning, confirm safety is not open. Fans are only ON when steam is
(1) The humidity sensor is factory calibrated, however, it can be field recalibrated.
(a) The calibration routine can be accessed by pressing and holding down the option
button for five seconds. A new screen will appear with the calibration adjustments.
(b) Press the up or down buttons until the text calH appears on the LCD screen.
(c) To adjust the calibration press the Option button. The screen should load to display the current calibration trim. The calibration trim can be adjusted by pressing the up or down buttons to the desired level and then pressing the option button to confirm the settings.
(d) Press the Power button to return to the normal display.
A properly calibrated hygrometer should be used in conjunction with any calibration procedure.

NHTC Display Message LED state System Action Symptom Diagnosed
RED Humidifier is in standby until problem corrected.
On power up, the controller cannot detect the driver board for cylinder B.
E6: Extendet Missing RED Humidifier activates its fault relay and interrupts its operation until communication is fixed.
The slave unit is not in communication with the master unit. Master unit powered?
E7: CPU CRC fault RED Humidifier activates its fault relay and interrupts operation.
Problem with the processor hardware or software.
W11: Safety Loop Open GRN Humidifier goes on standby. ON/OFF controls wired between terminal 1 and 2 are open.
W12: Cylinder Max Level NONE Fill valve interrupted. Water at top of cylinder.
RED Humidifier activates its fault relay and interrupts its operation.
The high water sensor is activated but no current is measured in cylinder.
The humidifier will attempt to clear any debris by pulsing the drain valve.
The fill valve has been activated for an extended period of time but water has not reached the sensor.
E13: Fill: Timeout RED The fill valve has been activated for an extended period of time but has not reached the sensor.
Humidifier stops operation and the fault relay is activated.
W15: Over current YEL The drain is activated to decrease the water level in the cylinder.
Measured current in the cylinder has exceeded 115% of rated output.
E15: Over Current RED Humidifier interrupts operation and the fault relay is activated.
Measured current in the cylinder has exceeded 115% of rated output.
W16: Excess Current YEL Humidifier interrupts operation and the fault relay is activated.
Measured current in the cylinder has exceeded 115% of rated output.
E16: Excess Current RED Humidifier interrupts operation and the fault relay is activated.
Measured current in the cylinder has exceeded 130% of rated output.

Probable Cause Corrective Action
The electronics of the main PCB have diagnosed the main PCB (itself) as defective.
Reset humidifier and monitor display. If Error reoccurs within one minute of resetting the unit, the problem is with the main PCB. If the Error is not repeated, the primary power to the unit is suspect.

NHTC Display Message LED state System Action Symptom Diagnosed
E17: Req off current RED Humidifier interrupts operation and the fault relay is activated.
With no system demand, current is detected in the cylinder.
System has detected foaming and will attempt to self correct if foam mode is active.
System has detected foaming and will attempt to self correct if foam mode is active.
W19: Cylinder spent YEL The electronics allow the cylinder to be reset up to four times before locking out the humidifier.
Electronics have determined cylinder is spent. Within the next 72 hours the humidifier will stop.
E19: Cylinder spent YEL, RED Humidifier interrupts operation and the fault relay is activated.
Electronics have determined that the cylinder is spent.
W20: Conductivity too low YEL Humidifier will continue to operate on this water supply.
Water conductivity is determined to be less than optimum.
W23: Control sensor broken YEL Humidifier put on standby. After a timeout period, this warning becomes a fault.
Electronics cannot detect the control RH sensor connected to the humidifier.
E23: Control sensor broken RED Humidifier interrupts operation and the fault relay is activated.
Electronics cannot detect the control RH sensor connected to the humidifier.
W24: Limit sensor broken YEL Humidifier put on standby. After a timeout period, this warning becomes a fault.
Electronics cannot detect the limit RH sensor connected to the humidifier.
E24: Limit sensor broken RED Humidifier interrupts operation and the fault relay is activated.
Electronics cannot detect the limit RH sensor connected to the humidifier.
YEL The humidifier drains the cylinder after three days of inactivity.
This safety feature drains standing water.
YEL The humidifier drains the cylinder after three days of operation.
This customer selected feature drains the cylinder to remove minerals.

Probable Cause Corrective Action
The cylinder must be replaced with the same type and model.
When ordering a new cylinder, quote the model number of cylinder presently installed in the humidifier or serial number of humidifier.
The cylinder must be replaced with the same type and model.
When ordering a new cylinder, quote the model number presently installed in the humidifier.
--- To disable this feature, consult the programming manual shipped with the humidifier.
--- To disable this feature, consult the programming manual shipped with the humidifier.

NHTC Display Message LED state System Action Symptom Diagnosed
W27: Safety loop instability YEL The safety loop is interrupting humidifier operation.
A security control is causing the safety loop to switch on and off too rapidly.
W28: demand signal instability YEL The demand signal is swinging from low demand to high demand too quickly.
The demand signal is unstable.
W29: limit signal instability YEL The limit signal is swinging from low demand to high demand too quickly and the humidifier cannot respond.
The limit signal is unstable.
W30: Modbus remote disable YEL The humidifier is being controlled via the network, not locally.
The humidifier has been disabled by a network message.
W43: Keep warm active YEL This is a customer selectable feature to keep the cylinder water warm.
The humidifier is in standby mode. The cylinder may energize at any time.
YEL The cylinder automatically reduces the humidifier output to stabilize operation.
The demand signal is cycling on and off too frequently.
W45: safety loop short cycling YEL The cylinder automatically reduces the humidifier output to stabilize operation.
The demand signal is cycling on and off too frequently.
W46: RH high warning YEL An alarm indication is generated.
RH levels higher than the limit set have been detected. The humidifier should not be operational with this warning activated.
W47: RH low warning YEL The humidifier is operating and an alarm indication is generated.
RH levels lower than the limit set have been detected. The humidifier should be operational with this warning activated.
W49: wrong cylinder installed YEL An alarm indication is generated.
The cylinder installed is not the recognized type for the humidifier.
E50: Modbus Timeout RED Systems shuts down. Time window for Modbus has elapsed.

Probable Cause Corrective Action
--- Contact the system administrator to override the remote command.
--- To disable this feature, consult the programming manual shipped with the humidifier.
--- Verify that the replacement cylinder is the same as the old cylinder.

RATED AMPS Refers to amps listed on the humidifier specification label.
SHORT CYCLING When the ‘on time’ of the humidifier is less than ten minutes upon a call for humidity. To correct short cycling, all humidifiers have a capacity adjustment which allows the output of the humidifier to be reduced as low as 20% of rated output, thus extending the ‘on time’ required to maintain output.
FOAMING This phenomenon can occur in water when the impurities, already in the water, reach an excess concentration as result of boiling away pure water, and the continued boiling action agitating the contained water. The humidifier electronics are designed to prevent this occurrence, although in extreme cases water will foam with little concentration making it necessary to have the drain time of the water, contained in the cylinder, increased. Foaming is normally caused by short cycling, a restricted drain, or back pressure. The foam generated in these instances, is conductive and may lead to a false full cylinder indication if the level of the foam approaches the top of the cylinder.
BACK PRESSURE This can be caused by restriction of steam flow caused by long steam runs; improperly sloped steam lines; elbows changing the direction of the steam flow from horizontal to vertical without a drain leg, any plumbing detail allowing the accumulation of condensate; undersized steam line; improper steam distributor; downward air flow onto the distributor creating excess static pressure at the steam outlets; or high static pressure ducts (not probable). To overcome excess static pressure in the duct, a fill cup extension kit should be used. In downflow applications, a downflow distributor should be used but in some cases the fill cup extension will also be required.
To reset the humidifier, the ON/OFF switch at the front of the humidifier should be switched to the OFF position for a minimum of five seconds and then switched back to the ON position.
MONITORED LEG Refers to the primary wire to the cylinder which loops through the current sensing device on the driver PCB. This wire is terminated at the red cylinder plug at the cylinder. Units with six primary wires to the cylinder will monitor only one of the two wires, terminating with red plugs.
CONDENSATE Refers to steam that has condensed to a liquid.
(1) The humidity sensor is factory calibrated, however, it can be field recalibrated. The
calibration routine can be accessed by pressing and holding down the option button for five seconds. A new screen will appear with the calibration adjustments.
(a) Press the up or down buttons until calH appears on the LCD screen.
(b) To adjust the calibration press the Option button. The screen should load to display the current calibration trim.
(c) The calibration trim can be adjusted by pressing the up or down buttons to the desired level and then pressing the option button to confirm the settings.
(d) Press the Power button to return to the normal display.
Term Definition


(1) See Figure 7 and Figure 9 in Chapter 10-10 for Controller and Transducer terminal
definitions. See Figure 6 in Chapter 10-10 for low voltage terminal strip terminal definitions.
Power Supply Operating Voltage 24 VAC ± 10% 50/60 Hz
Power Consumption Max. 3 VA
Internal Rectification Half-wave rectified
Signal Inputs Analog Input Input Signal Resolution Accuracy
AI1 2-10 VDC 39 mV, 0.078 mA ± 2%
External Thermistor -40° to 140°C (-40° to 284°F)
0 to 100 %RH ± 3.0% at 25°C (77°F) ± 0.5%
Signal Outputs Digital Outputs Maximum Load
DO1 24 VAC 2A max.
Environment Operation Temperature Humidity
0° to 50°C(32° to 122°F)
Housing Materials Cover, back Mounting Plate
Fire proof ABS plastic Galvanized Steel
Temperature Input Range

(1) See Figure 1and 2 for the NHTC/NHPC Single and Double Unit Wiring diagrams.




(4) Start-Up Procedure:
Connection:
Ensure power is being supplied to the humidifier and Nortec Online Module.
Each individual Humidifier linked to lead Unit.
Connection can be direct or daisy-chained to other units.
Verify power to NetBiter (Power LED should be lit).
After power-up, verify network communication.
Lead Unit wired to Local Network (Ethernet, GPRS, Dial-up).
Verify variable operation after mapping is complete.
Network activity verified.
Perform regular humidifier start-up check.
Directly to humidifiers.
(4) Start-Up Procedure:
Connection:
Verify power to NORTEC Links
module.
Each individual Humidifier linked to lead Unit.
Verify power to I/O-Controller.
Connection can be direct or daisy-chained to other units.
Adjust Network address dials to
desired address (BACnet/IP address is preset at factory).
Lead Unit wired to Local BMS.
After power-up, verify network
communication.
Network activity verified.
Map desired network variables to
BMS.
Directly to humidifiers.
Verify variable operation after
mapping is complete.
Perform regular humidifier start-
up check.

Unit Serial #: No. of humidifiers: Tag: Unit type: Voltage: V/___ph Steam output: lbs/hr Customer/Job: Address: Inspected by: Date of inspection: / /
Well water ___ City water ___ Softened water ___ RO / DI water ___ Conductivity: mhmos Hardness: gr.
Clearances around the unit Acceptable Obstruction – Front (door opens freely?) 3 ft min – Top (steam lines) 2 ft min – Bottom (fill, drain, controls) 2 ft min – Right (main pwr) 2 ft min
CONDENSATE LINES:
– Slope up 2 in. per 12 in – Slope down 0.500 in. per 12 in – Traps ___ – Insulated ___ – Length/Size /
– Sloped back to drain ___ – Trapped 2 in. more than static
duct pressure ___ – Size – Stainless steel ___ or plastic ___ – % Vertical % Horizontal
– 90 degree elbows ___ qty: – 45 degree Elbows ___ qty: – Can condensate be trapped anywhere in the steam line? yes ___ no ___
– 0.050 in. at max 4ft from the unit ___– 3/8 in. connection at fill G – Water pressure: 30-80 psig ___ – PVC ___ – Stainless steel ___
– Air gap located within 3 ft of the unit ___ – Sloped to drain ___ – Size:
– Cylinder properly installed and sitting upright
– No loose wires around the unit or on the PC board? yes ___ no ___
Installed Location / Wiring /Setting Installed Location / Wiring /Setting – High limit: – Air proving: – Mod controller: – Other:
– Voltage, amperage rating and fuse correspond to Spec Label: ___ – Disconnect switch located close to humidifier: ___

Unit Serial #: No. of humidifiers: Tag: Unit type: Voltage: V/___ph Steam output: lbs/hr Customer/Job: Address: Inspected by: Date of inspection: / /
If no, return to Pre-Start-up Checklist before going on with start-up procedure.
– check that main breaker is on and power is at the unit. – check that main water shut-off valve is open. – on/off/drain switch must be switched on. – control circuit 1-2 must be made. – modulation humidistat, if present, must be calling. – door interlock switch must be made (interlock switch can be pulled out to operate unit).
The unit will undergo a self-test to ensure integrity of all the components:
– NHTC Start-Up Unit Cylinder – Reading Cylinder Data – Inlet Valve – Drain Valve – Heat Controller – Pump – Bleed Valve – Steam Relay – Service Relay – Error Relay – Operation Relay
It will then start filling the cylinder and begins normal operation. Most water does not contain enough conductivity for full boil on initial start-up. Units will need to concentrate the water over a time period (hours to days).

Unit Serial #: No. of humidifiers: Tag: Unit type: Voltage: V/___ph Steam output: lbs/hr Customer/Job: Address: Inspected by: Date of inspection: / /
NHTC/NHPC light indication and LCD display: 1. Yellow and Green light with W19: Cylinder Spent indicates the cylinder must be replaced in the next 72 hours. 2. Red and Yellow light with E19: Cylinder Spent indicates the cylinder is at the end of its life and must be replaced. CYLINDER REPLACEMENT PROCEDURE: 1. Turn off water supply to unit. 2. Activate drain to completely empty water content (less than 10 minutes) 3. When drained, stop drain and turn off unit. 4. Also open the main electrical disconnect switch and open plumbing. 5. Remove the cylinder plugs by pulling vertically. The plugs are press-fitted over the electrode pins protruding from the top of the cylinder. 6. Using a slotted screwdriver, loosen the steam line clamp(s) and pull steam line off the cylinder vertically. 7. Using a small slotted screwdriver, depress tab on the re-usable cable tie, if present, around the middle of the cylinder. This will loosen the cable tie to come apart for re- use later on. 8. The cylinder is now ready to be removed from the unit. CAUTION: Cylinder and any remaining water might still be HOT. 9. Always clean the drain valve before installing a new cylinder. (see further below) 10. Remove the used cylinder and replace by a new one. Do not re-use cylinder.
1. Note that ring terminal for drain valve green ground wire is sandwiched between drain valve body and drain pan. 2. Remove two screws securing drain valve body to drain pan. Disconnect the two slip-on terminals from the two tabs on the (24 VAC) drain valve coil. 3. Remove hose clip and hose connection from drain valve body. 4. Drain valve assembly is now free to be taken to a sink for disassembly and cleaning. Important: Tapered end of spring must be installed toward the solenoid. 5. Clean out the end of the hose, and then reconnect it to the drain valve body with the clamp. 6. Fit mounting screws through drain valve body, one through ring terminal on green ground wire. WARNING: To prevent the possibility of electrical shock the green ground wire must be
reinstalled before power is restored. Push the two slip-on terminals back onto the two tabs on the coil. The terminals, although not identical, are reversible.

Unit Serial #: No. of humidifiers: Tag: Unit type: Voltage: V/___ph Steam output: lbs/hr Customer/Job: Address: Inspected by: Date of inspection: / /
1. Reverse procedure should be followed to install new cylinder. Main disconnect is to be left open until cylinder is completely installed and reconnected. 2. Ensure that the re-usable cable tie and mounting brackets, within the unit, secure the cylinder properly. 3. The cylinder plug wires are colour-coded in accordance with coloured dots beside the electrode pins on top of the cylinder. 4. This colour coding must be adhered to when replacing cylinder plugs on pins. 5. With cylinders having six primary voltage cylinder plugs, it should be noted that there are two of each colour. 6. Care must be taken so that cylinder leads of the same color are always directly opposite each other as indicated by the dot formation on the top of the cylinder. 7. The white cylinder plug on all units is for the high water sensor electrode, which always goes on the single pin surrounded by a plastic shoulder. 8. Ensure that cylinder plugs fit snugly on the pins. 9. If cylinder plugs become loose, it is best to obtain a new replacement plug. Consult factory.
ACCESS SHOULD BE LIMITED TO AUTHORIZED PERSONNEL ONLY.
4. NHTC 3 day drain: As long as the NHTC is powered, it will automatically drain the cylinder when there has not been a call for humidity for an extended period of time. 5. The cylinder will remain empty until there is a call for humidity at which time the fill valve will open and refill the cylinder. This feature will reduce the possibility of corrosion of the electrodes and the possible accumulation of algae and bacteria growing in the cylinder.

(1) See Figure 3 for the ASD, BSD, CSD Distributor exploded view and spare parts.

B. SAM-e SPARE PARTS
(1) See Figure 4 for the SAM-e exploded view and spare parts.


(1) See Figure 5 for the NHTC/NHPC plumbing compartment exploded view and spare
parts and Table 2 for the parts list. See Figure 6 for the NHTC/NHPC electrical compartment exploded view and spare parts and Table 3 for the parts list.


CYLINDER 607 X 150-9741 1 2 2 2
2 STEAM OUTLET, LARGE, NHTC ONLY 150-9465 1 2
CLAMP FOR LARGE STEAM LINE 132-5009 2 4
4 DRAIN CHANNEL 111-6857 1 2
5 DRAIN CHANNEL GASKET 163-1026 1 2
6 VALVE DRAIN 93BEIGE + 24V COIL 145-6000 1 2
7 CYLINDER BRACKET 150-9593 1 2
FILL CUP ASSEMBLY LARGE 252-2407 1 2
LARGE STEAM LINE 1.500 IN. ID 7.000 IN. 132-8820 1 2
MODEL 005 010 020 020 030 050 075 100 150 200
CYLINDER 603 X 150-9739 1 1 1 2 2
CYLINDER 621 X 150-9744 1 2
Table 2. NHTC/NHPC Plumbing Part List
CYLINDER 411 X 150-9737 1 1
STEAM OUTLET, SMALL, NHTC ONLY 150-9466 1
3 CLAMP FOR SMALL STEAM LINE 132-5007 2
8 FILL CUP ASSEMBLY SMALL 252-2406 1
SMALL STEAM LINE 0.875 IN. ID 4.500 IN. 132-8820 1
CYLINDER 421 X 150-9738 1 1
CYLINDER 311 X 150-9731 1 1 1
SMALL STEAM LINE 0.875 IN. ID 5.000 IN. 132-8810 1
CYLINDER 309 X 150-9730 1 1
CYLINDER 305 X 150-9729 1
CYLINDER 321 X 150-9732 1 1 1
CYLINDER 204 X 150-9727 1 1
SMALL STEAM LINE 0.875 IN. ID 9.000 IN. 132-8810 1
CYLINDER 202 X 150-9725 1 1 1 1
VOLTS/PH
NO. DESCRIPTION NORTEC
CYLINDER 201 X 150-9724
CYLINDER 331 X 150-9733
CYLINDER 333 X 150-9734
CYLINDER 609 X 150-9742
CYLINDER 617 X 150-9743
CYLINDER 631 X 150-9745
CYLINDER 636 X 150-9746
ITEM

VALVE, SINGLE FILL, 3.3L/min 135-3037 1 2
11 GASKET FOR FILL THRU CAB 145-5000 1 2
-1/2"NPT 150-6288 1 2
CABLE TIE REUSABLE 5-600 CYL SZ 151-3005 1 2
CYL PLUG WITH BLACK MARKER 151-0046 1 2 2 2 1 1 2 2 2 1 1 2 2 1 4 4 4 2 2 4 4 2
CYL PLUG WITH YELLOW MARKER 151-0049 1 2 2 2 1 1 2 2 2 1 1 2 2 1 4 4 4 2 2 4 4 2
CYL PLUG WITH RED MARKER 151-0047 1 2 2 2 1 1 2 2 2 1 1 2 2 1 4 4 4 2 2 4 4 2
MODIFIED 150-4150 1 2
WALL BRACKET 150-200 LBS 145-7023 1
FLOAT ASSEMBLY, FOAM DETECTION 252-3334 1 2
FILLCUP EXTENSION KIT NHTC/NHPC 252-2160 1 2
VALVE, DUAL FILL, 3.3 L/min, 3.3L/min 1 2
MODEL 005 010 020 020 030 050 075 100 150 200
MARKER 132-4265 2 2 4 4
MARKER 132-4266 2 2 4 4
VALVE, SINGLE FILL, 2.0 L/min 135-3032 1 2
VALVE, DUAL FILL, 3.3 L/min, 2.0 L/min 1 2
WALL BRACKET 50-100 LBS 145-7022 1
Table 2. NHTC/NHPC Plumbing Part List (cont)
VALVE, SINGLE FILL, 1.2 L/min 135-3017 1
13 CABLE TIE REUSABLE 1-400 CYL SZ 151-3003 1
WALL BRACKET 5-30 LBS 145-7020 1
VALVE, DUAL FILL, 3.3 L/min, 1.2 L/min 1
VALVE, DUAL FILL, 3.3 L/min, 0.5 L/min 150-9698 1
VALVE, SINGLE FILL, 0.5 L/min 131-3244 1
NO. DESCRIPTION NORTEC
FOAM DETECTION OPTION
SUPER PLUG /W WIRE WITH YELLOW
FILL CUP EXTENSION KIT
DRAIN WATER COOLING
SUPER PLUG /W WIRE WITH BLACK
OPTIONAL COMPONENTS
12 FITTING BRASS 3/4 BSP / WASHER
CYLINDER PLUG 5MM 15A (HWS)
SUPER PLUG W/ WIRE WITH RED
ITEM



CONTACTOR 40 AMP 3PH 132-3014 1 2 2 1 2 1 4 4 2 4 2
TERMINAL BLOCK 3 POLE 95 AMP 132-3027 1
3 GROUND CLAMP 132-3020 1
6 PCB PROCESSOR NHPC (NOT SHOWN) 252-1274 1
PCB PROCESSOR NHTC 252-1277 1
ELECTRICITY CONVERTER 252-1278 1 2
8 SWITCH, ROCKER, DPST 252-2489 1
9 SWITCH SPST 208-240V 147-3010 1
10 SWITCH INTERLOCK IDM 423 132-3091 1
CABLE RIBBON 40 PIN NHTC/NHPC 252-2061 1 2
CABLE RIBBON 10 PIN NHTC FAULT 252-2062 1 2
CABLE EPROM LARGE 252-2037 1
CABLE EPROM DOUBLE 252-2060 1
CONTACTOR 30 AMP 3PH 132-3013 1 2 2 2 1 1 2 1 2 4 2 4
TERMINAL BLOCK 3 POLE 150 AMP 132-3028 1
MODEL 005 010 020 020 030 050 075 100 150 200
CONTACTOR 62 AMP 3PH 132-3015 2 2 1 4 4
TERM. BLOCK 3 POLE 310 AMPU 132-3030 1 1 1
TX 24VAC 150VA, PRIMARY 208 252-2318 1 1
TRANSFORMER 600/24 VAC 75 VA 132-3575 1
TRANSFORMER 480/24 VAC 75 VA 132-3460 1
TRANSFORMER 380/24V 75VA 132-3380 1
TRANSFORMER 240/24 VAC 75 VA 132-3230 1
TRANSFORMER 208 24V 75VA 132-3208 1
Table 3. NHTC/NHPC Electrical Parts List
CABLE EPROM SMALL 252-2033 1
CONTACTOR 30 AMP 1PH 145-3013 1
2 TERMINAL BLOCK 2 POLE 95A 132-3001 1
4 TRANSFORMER 120/24 VAC 75 VA 142-3110 1
VOLTS/PH
PCB DRIVER FOR NHTC 005 120V Only Use for NHTC 005
5 PCB FAULT REMOTE (OPTION) 252-1279
PCB DRIVER NHPC, NHTC INCL.
7 PCB DRIVER NHPC, NHTC INCL.
ITEM
NOT SHOWN

(OPTIONAL) 150-9694 6
MODEL 005 010 020 020 030 050 075 100 150 200
(OPTIONAL) 142-3176 6 6 12 12
(OPTIONAL) 142-3173 6 12
(OPTIONAL) 150-9692 6 12
PART NO. SINGLE PHASE THREE PHASE
Table 3. NHTC/NHPC Electrical Parts List (cont)
VOLTS/PH
NO. DESCRIPTION NORTEC
OPTIONAL COMPONENTS
PRIMARY FUSE JJN60(JLLN60)
PRIMARY FUSE JJN50(JLLN50)
PRIMARY FUSE JJN40 JLLN40
PRIMARY FUSE JJS40 (JLLS40)
PRIMARY FUSE JJS50 (JLLS50)
PRIMARY FUSE JJS60 (JLLS60)
ITEM


(1) Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE
COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
(2) THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing
replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
(3) The warranties set forth herein are in lieu of all other warranties expressed or implied
by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
(4) THE COMPANY’s limited warranty on accessories, not of the companies manufacture,
such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
(5) THE COMPANY makes no warranty and assumes no liability unless the equipment is
installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
(6) THE COMPANY makes no warranty and assumes no liability whatsoever for
consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
(7) THE COMPANY makes no warranty and assumes no liability whatsoever for damage
resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.
(8) THE COMPANY makes no warranty and assumes no liability whatsoever for
equipment that has failed due to ambient conditions when installed in locations having climates below 14°F (-10°C) during January or above 104°F (40°C) during July. (See Table 1: Weather Design Data above).
(9) THE COMPANY retains the right to change the design, specification and performance
criteria of its products without notice or obligation.

MODEL #
SERIAL #
CYLINDER #

Cylinder Replacement Date (MM/DD/YYYY)



Authorized Agent:
U.S.A. Walter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: northamerica.climate@waltermeier.com WEBSITE: www.humidity.com
CANADA Walter Meier (Climate Canada) Ltd. 2740 Fenton Road Ottawa, ON K1T 3T7 TEL: 1-866-NORTEC-1 FAX: (613) 822-7964
In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.
Was die auf dem Display angezeigten Fehlercodes bedeuten und wie man sie behebt.
| Code | Bedeutung | Lösung | |
|---|---|---|---|
| E5 | Cylinder B Controller | p.67 | |
| E6 | Extendet Missing | p.67 | |
| E7 | CPU CRC fault | p.67 | |
| W11 | Safety Loop Open | p.67 | |
| W12 | Cylinder Max Level | p.67 | |
| E12 | Cylinder max Level no | p.67 | |
| W13 | Fill Timeout | p.67 | |
| E13 | Fill: Timeout | p.67 | |
| W15 | Over current | p.67 | |
| E15 | Over Current | p.67 | |
| W16 | Excess Current | p.67 | |
| E16 | Excess Current | p.67 | |
| E17 | Req off current | p.69 | |
| W19 | Cylinder spent | p.69 | |
| E19 | Cylinder spent | p.69 | |
| W20 | Conductivity too low | p.69 | |
| W23 | Control sensor broken | p.69 | |
| E23 | Control sensor broken | p.69 | |
| W24 | Limit sensor broken | p.69 | |
| E24 | Limit sensor broken | p.69 | |
| W25 | 3-day idle drain | p.69 | |
| W26 | 3-day forced drain | p.69 | |
| W27 | Safety loop instability | p.71 | |
| W28 | demand signal instability | p.71 | |
| W29 | limit signal instability | p.71 | |
| W30 | Modbus remote disable | p.71 | |
| W43 | Keep warm active | p.71 | |
| W44 | Demand signal short | p.71 | |
| W45 | safety loop short cycling | p.71 | |
| W46 | RH high warning | p.71 | |
| W47 | RH low warning | p.71 | |
| W49 | wrong cylinder installed | p.71 | |
| E50 | Modbus Timeout | p.71 |
Häufige Probleme, wahrscheinliche Ursachen und Lösungen.
| Problem | Mögliche Ursache | Abhilfe | |
|---|---|---|---|
| Unit is awaiting a demand or control signal. | This is normal when there is no need for humidity. If you believe there is a need for humidity, and the unit should not be idle, refer to troubleshooting | Normal Operation | p.50 |
| The unit is now boiling water in the cylinder and filling as necessary. | This is normal when there is a need for humidity. If you believe there is no need for humidity, and the unit should idle, refer to troubleshooting | Normal Operation | p.50 |
| This is not a fault or warning. It is an indication that the manual drain switch has been activated. | Manual drain switch has been activated. | Press Manual Drain button again to stop the drain action. | p.50 |
| Safety loop circuit (terminal 1 and 2) is open. | One or more of the safety devices is open as the result of a device failure, improper installation or an unsafe condition has been detected. | Determine which device is preventing continuity of the safety loop circuit, and verify that it is functioning properly and is properly installed and calibrated. | p.50 |
| Water has reached the top of the cylinder and has activated the high water sensor. This is not an error or fault, but is normal on start-up and at the end of a cylinder life span. | 1. Normal on start-up with a new cylinder or a cylinder that has been completely drained because of an extended off period. This condition can last several hours until the water in the cylinder has concentrated or the electrodes can no longer provide rated capacity or adjusted capacity. Water level automatically rises to meet the demand. 2. Foaming can also cause an invalid high water indication. | If foaming is determined to be the cause of the high water indication, consult your local representative about possible adjustment and/or a foam detection kit. If not foaming, consider it normal operation unless water level is not at the top of the cylinder. | p.50 |
| Keep Warm feature is enabled and proceeding to a Keep Warm Cycle. | Unit is entering the Keep Warm cycle. The unit has been inactive for a given period and is keeping the water warm. | Normal for unit with Keep Warm setting activated. | p.50 |
| Electronics have determined cylinder is spent. Within the next 72 hours the humidifier will stop. | The cylinder must be replaced with the same type and model. | When ordering a new cylinder, quote the model number presently installed in the humidifier. | p.50 |
| Electronics have determined that the cylinder is spent. | The cylinder must be replaced with the same type and model. | When ordering a new cylinder, quote the model number presently installed in the humidifier. | p.50 |
| The electronics has detected foaming within the cylinder (only for units with the optional Foam Detection Package). | The unit has detected a foaming condition within the cylinder. | The unit will initiate corrective action on its own. | p.50 |
| On power up, the controller cannot detect the driver board for cylinder B. | Humidifier is in standby until problem corrected. | p.67 | |
| The slave unit is not in communication with the master unit. Master unit powered? | Humidifier activates its fault relay and interrupts its operation until communication is fixed. | p.67 | |
| Problem with the processor hardware or software. | Humidifier activates its fault relay and interrupts operation. | p.67 | |
| ON/OFF controls wired between terminal 1 and 2 are open. | Humidifier goes on standby. | p.67 | |
| Water at top of cylinder. | Fill valve interrupted. | p.67 | |
| The high water sensor is activated but no current is measured in cylinder. | Humidifier activates its fault relay and interrupts its operation. | p.67 | |
| The fill valve has been activated for an extended period of time but water has not reached the sensor. | The humidifier will attempt to clear any debris by pulsing the drain valve. | p.67 | |
| Humidifier stops operation and the fault relay is activated. | The fill valve has been activated for an extended period of time but has not reached the sensor. | p.67 | |
| Measured current in the cylinder has exceeded 115% of rated output. | The drain is activated to decrease the water level in the cylinder. | p.67 | |
| Measured current in the cylinder has exceeded 115% of rated output. | Humidifier interrupts operation and the fault relay is activated. | p.67 | |
| With no system demand, current is detected in the cylinder. | Humidifier interrupts operation and the fault relay is activated. | p.69 | |
| System has detected foaming and will attempt to self correct if foam mode is active. | System will activate selected foam algorithm. (See Figure 7.) | p.69 | |
| Electronics have determined cylinder is spent. Within the next 72 hours the humidifier will stop. | The electronics allow the cylinder to be reset up to four times before locking out the humidifier. | p.69 | |
| Electronics have determined that the cylinder is spent. | Humidifier interrupts operation and the fault relay is activated. | p.69 | |
| Water conductivity is determined to be less than optimum. | Humidifier will continue to operate on this water supply. | p.69 | |
| Electronics cannot detect the control RH sensor connected to the humidifier. | Humidifier put on standby. After a timeout period, this warning becomes a fault. | p.69 | |
| Electronics cannot detect the control RH sensor connected to the humidifier. | Humidifier interrupts operation and the fault relay is activated. | p.69 | |
| Electronics cannot detect the limit RH sensor connected to the humidifier. | Humidifier put on standby. After a timeout period, this warning becomes a fault. | p.69 | |
| Electronics cannot detect the limit RH sensor connected to the humidifier. | Humidifier interrupts operation and the fault relay is activated. | p.69 | |
| This safety feature drains standing water. | The humidifier drains the cylinder after three days of inactivity. | p.69 | |
| This customer selected feature drains the cylinder to remove minerals. | The humidifier drains the cylinder after three days of operation. | p.69 | |
| A security control is causing the safety loop to switch on and off too rapidly. | The safety loop is interrupting humidifier operation. | p.71 | |
| The demand signal is unstable. | The demand signal is swinging from low demand to high demand too quickly. | p.71 | |
| The limit signal is unstable. | The limit signal is swinging from low demand to high demand too quickly and the humidifier cannot respond. | p.71 | |
| The humidifier has been disabled by a network message. | The humidifier is being controlled via the network, not locally. | p.71 | |
| The humidifier is in standby mode. The cylinder may energize at any time. | This is a customer selectable feature to keep the cylinder water warm. | p.71 | |
| The demand signal is cycling on and off too frequently. | The cylinder automatically reduces the humidifier output to stabilize operation. | p.71 | |
| RH levels higher than the limit set have been detected. The humidifier should not be operational with this warning activated. | An alarm indication is generated. | p.71 | |
| RH levels lower than the limit set have been detected. The humidifier should be operational with this warning activated. | The humidifier is operating and an alarm indication is generated. | p.71 | |
| The cylinder installed is not the recognized type for the humidifier. | An alarm indication is generated. | p.71 | |
| Time window for Modbus has elapsed. | Systems shuts down. | p.71 |