NH Seriesp.1TMp.1NHTC / NHPC ELECTRODE STEAM HUMIDIFIERp.1Engineering Manualp.12538144-Bp.1PROPRIETARY NOTICEp.2LIABILITY NOTICEp.2COPYRIGHT NOTICEp.2SPECIFICATION LABEL LOCATIONp.22008-10-01p.2Subject Pagep.4WARRANTYp.4LIST OF FIGURESp.5Figure Pagep.510-00 ELECTRODE STEAM ENGINEERINGp.510-10 HUMIDITY, STEAM ABSORPTION AND DISTRIBUTIONp.510-30 SUBMITTALSp.6LIST OF TABLESp.7Table Pagep.710-00 INTRODUCTIONp.9Figure 1. NHTCp.101. INTRODUCTIONp.11A. PROPORTIONAL + INTEGRAL AUTO-ADAPTIVE CONTROL SYSTEM FOR THEp.11NHTC/ NHPCp.11Figure 2. Optimum Boiling Timep.13B. NH CAPACITY ADJUSTMENTp.14C. DRAIN CYCLE AND CYLINDER LIFEp.14(2) Water Conditions vs Cylinder Lifep.14(3) Output vs Cylinder Lifep.14Figure 4. Typical Auto-Adaptive Operationp.153. PRE-INSTALLATION EQUIPMENT VERIFICATIONp.17A. GENERALp.17Figure 6. Typical NHRS Installation (Sheet 1 of 2)p.18Figure 7. Typical NHRS Installation (Sheet 2 of 2)p.19HUMIDITY, STEAM ABSORPTIONp.20AND DISTRIBUTIONp.20HUMIDITY, STEAM ABSORPTION AND DISTRIBUTIONp.211. HUMIDITYp.21A. ESTIMATING THE HUMIDIFICATION LOADp.21B. LOAD CALCULATION SUMMARYp.21C. TEMPERATURE AND HUMIDITY REQUIREDp.21D. TEMPERATURE AND HUMIDITY AVAILABLEp.21Table 1. Outdoor/Indoor Relative Humidity Conversion Chartp.22Table 2. Load Calculation Summary Sheetp.22E. INCOMING AIR VOLUMEp.23Table 4. Design Outdoor Conditionsp.24(% RH)p.247:30 P.M. °Cp.24°Fp.24Table 4. Design Outdoor Conditions (cont)p.25Figure 1. Schematic of a Typical Print Shop HVAC Systemp.27Table 5. Inside Relative Humidities At Which Moisture Will Condense On Windowsp.29Table 6. Regain of Hygroscopic Materialsp.30Table 7. Design Indoor Conditions For Various Places, Products and Processesp.31Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)p.32%RHp.32°F °Cp.32Figure 2. Psychrometric Chartp.352. STEAM ABSORPTION AND DISTRIBUTIONp.36A. VARIABLES THAT AFFECT ABSORPTION DISTANCESp.36Table 8. Variables That Affect Absorption Distancesp.36Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifierp.37FPM °F °C % RH FT CMp.37Figure 3. Steam Distributor Locationp.37B. CALCULATING THE DOWN STREAM HUMIDITY LEVELp.38Table 10. Water (lbs/hr) Contained in 1000 CFM of Airp.38NOTEp.39C. CONTROL OF DUCT OR PLENUM SATURATIONp.39Figure 4. Condensate Drain Panp.393. STEAM RUNS AND CONDENSATE RETURNSp.40A. STEAM RUNSp.40Figure 5. Proper Slopep.40Figure 6. Drain Teep.40Table 11. Steam Line Materialp.41Table 12. Recommended Material and Size for Steam Runp.41OD)p.41Table 13. Recommended Condensate Line at Distributor(s)p.41Table 14. Maximum Recommended Length of Steam Runsp.42B. CONDENSATE RETURNp.42Figure 8. Condensate Tee At Any Low Pointp.43
Page 1 of the Nortec NHTC user manual — 2538144-B
Seite 1 · Zum Vergrößern klicken
Seite 1
Nortec NHTC — NH Series diagram (page 1)
Abb. 1 · NH Series
Nortec NHTC — NH Series diagram (page 1)
Abb. 2 · NH Series

NH Series

Nortec NHTC — NH Series diagram (page 1)
Abb. 3 · NH Series

TM

NHTC / NHPC ELECTRODE STEAM HUMIDIFIER

Engineering Manual

2538144-B

Page 2 of the Nortec NHTC user manual — 2008-10-01
Seite 2 · Zum Vergrößern klicken
Seite 2

PROPRIETARY NOTICE

This document and the information disclosed herein are proprietary data of WALTER MEIER LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of WALTER MEIER LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the NORTEC name should be taken as referring to WALTER MEIER LTD.

Nortec NHTC — PROPRIETARY NOTICE diagram (page 2)
Abb. 4

LIABILITY NOTICE

NORTEC does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by NORTEC.

COPYRIGHT NOTICE

Copyright 2008, WALTER MEIER LTD. All rights reserved.

SPECIFICATION LABEL LOCATION

The Specification Label for your NH Series humidifier is located on the bottom of the unit. You will find it attached to the skirt that separates the electrical and plumbing compartments on the electrical compartment side.

RECORD OF REVISIONS For each revision, put the revised pages in your manual and discard the superseded pages. Write the revision number and revision date, date put in manual, and the incorporator’s initials in the applicable columns on the Record of Revisions.

Date Put In Manual By

Date Put In Manual By

2008-10-01

Show 8 more labels / short text on this page
Revision · Revision · Revision · Revision · Number · Date · Number · Date
Page 3 of the Nortec NHTC user manual — PROPRIETARY NOTICE
Seite 3 · Zum Vergrößern klicken
Seite 3
Page 3 of the Nortec NHTC user manual — PROPRIETARY NOTICE
Page 4 of the Nortec NHTC user manual — 2008-10-01
Seite 4 · Zum Vergrößern klicken
Seite 4

Subject Page

7. CONTROLS 53 A. GENERAL 53 B. ON/OFF CONTROLS 53 C. MODULATING CONTROLS 53 D. OUTDOOR TEMPERATURE SETBACK 54 E. TRANSDUCER SENSORS 54 F. POSITIONING CONTROLS AND SENSORS 55 G. NORTEC ONLINE 55 H. NORTEC LINKS 57 I. TYPICAL INSTALLATION LAYOUT FOR NHTC/NHPC 58 J. NORTEC CONTROLLER DIMENSIONS 58

10-20 SPECIFICATIONS 1. HUMIDIFIERS 64 A. GENERAL 64 B. PRODUCTS 64 C. EXECUTION 70

10-30 SUBMITTALS 1. SUBMITTAL DESCRIPTIONS 74 A. INTRODUCTION 74 B. NH UNIT 74 C. DISTRIBUTORS 74 D. SAM-e 74 E. BLOWER PACK 74 F. CONTROLS 75

WARRANTY

2008-10-01

Page 5 of the Nortec NHTC user manual — 2008-10-01
Seite 5 · Zum Vergrößern klicken
Seite 5

LIST OF FIGURES

Figure Page

10-00 ELECTRODE STEAM ENGINEERING

Figure 1. NHTC 2 Figure 2. Optimum Boiling Time 5 Figure 3. Conductivity 5 Figure 4. Typical Auto-Adaptive Operation 7 Figure 5. Capacity Setting & Cylinder Life 8 Figure 6. Output vs Service Life 8 Figure 7. Typical NHRS Installation 10

10-10 HUMIDITY, STEAM ABSORPTION AND DISTRIBUTION

Figure 1. Schematic of a Typical Print Shop HVAC System 19 Figure 2. Psychrometric Chart 27 Figure 3. Steam Distributor Location 29 Figure 4. Condensate Drain Pan 31 Figure 5. Proper Slope 32 Figure 6. Drain Tee 32 Figure 7. Steam Line Connection 35 Figure 8. Condensate Tee At Any Low Point In Steam Line 35 Figure 9. Trap To Prevent Steam In Condensate Line 35 Figure 10. Levelling the Distributor 37 Figure 11. Single Steam Distributor Installation – Minimum Clearance 38 Figure 12. Cutting Duct For Mounting 39 Figure 13. Humidification Distance Nomogram 39 Figure 14. Best Location for Multiple Steam Distributors 40 Figure 15. Roof Top Units 2-20 Tons – Typical Location 41 Figure 16. Small Units On Residential Furnaces 41 Figure 17. SAM-e Tubes 42 Figure 18. Cross-Section of Distributor Pipe 42 Figure 19. Absorption Distance – 3" Centers 45 Figure 20. Absorption Distance – 6" Centers 45 Figure 21. Absorption Distance – 9" Centers 45 Figure 22. Absorption Distance – 12" Centers 45 Figure 23. SAM-e Header 23 Figure 24. SAM-e Tubes 23 Figure 25. Steam Inlet 47 Figure 26. Typical SAM-e Installation for Atmospheric Steam Applications 50 Figure 27. NH Series Humidifier With Built-On Blower Pack 51 Figure 28. NH Series Remote Mounted Blower Pack 51 Figure 29. Set Point Versus Outdoor Temperature 54 Figure 30. NORTEC OnLine Monitoring 56 Figure 31. NORTEC Online Configuration Form 59 Figure 32. NORTEC Links Form 60

2008-10-01

Page 6 of the Nortec NHTC user manual — 2008-10-01
Seite 6 · Zum Vergrößern klicken
Seite 6

Figure Page

Figure 33. Humidifier Controlled by Air Proving, On/Off Duct Mounted High Limit and Modulating Wall Mounted Space Controller 61 Figure 34. Humidifier Controlled by Air Proving, Modulating Duct Mounted High Limit and Modulating Wall Mounted Space Controller 61 Figure 35. Humidifier Controlled by Air Proving, Modulating Duct Mounted High Limit and Modulating Wall Mounted Return Air Sensor with Wall Mounted Controller 62 Figure 36. Humidifier Controlled by Air Proving, Duct Mounted High Limit Sensor and Modulating Duct Mounted Return Air Sensor with Networking Option 62

10-30 SUBMITTALS

Figure 1. Low Voltage Control Terminal Strip 77 Figure 2. Primary (Line) Voltage Wiring to Unit 78 Figure 3. Physical Data - NHTC/NHPC 005-030 79 Figure 4. Physical Data - NHTC/NHPC 050-100 80 Figure 5. Physical Data - NHTC/NHPC 150-200 81 Figure 6. Distributor Dimensions (3 Sheets) 82 Figure 7. SAM-e General Dimensions 85 Figure 8. General Mini SAM-e Dimensions 86 Figure 9. In-Duct/AHU Installation Without Mounting Frame Installation 87 Figure 10. In-Duct/AHU Installation With Mounting Frame Installation 88 Figure 11. Outside Duct Installation Without Mounting Frame Installation 89 Figure 12. Outside Duct Installation With Mounting Frame Installation 90 Figure 13. Vertical Duct Installation 91 Figure 14. Outside Duct Mounting Cover Plates 91 Figure 15. Atmospheric SAM-e Adapter Dimensions 92 Figure 16. Atmospheric Steam Header and Adapter Configuration 93 Figure 17. Physical Data for Remote Mounted Blower Pack 94 Figure 18. Physical Data Units With Optional Built-On Blower Packs 95 Figure 19. Wall Digital Humidistat 97 Figure 20. Duct Sensor 98

2008-10-01

Page 7 of the Nortec NHTC user manual — 2008-10-01
Seite 7 · Zum Vergrößern klicken
Seite 7

LIST OF TABLES

Table Page

10-00 ELECTRODE STEAM ENGINEERING

Table 1. Features Comparison 7 Table 2. NHTC/NHPC Characteristics 9

10-10 HUMIDITY, STEAM ABSORPTION AND DISTRIBUTION

Table 1. Outdoor/Indoor Relative Humidity Conversion Chart 14 Table 2. Load Calculation Summary Sheet 14 Table 3. Grains of Water Per Cubic Foot – Saturated Air (100% rh) 15 Table 4. Design Outdoor Conditions 16 Table 5. Inside Relative Humidities At Which Moisture Will Condense On Windows . . 21 Table 6. Regain of Hygroscopic Materials 22 Table 7. Design Indoor Conditions For Various Places, Products and Processes 23 Table 8. Variables That Affect Absorption Distances 28 Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifier 29 Table 10. Water (lbs/hr) Contained in 1000 CFM of Air 30 Table 11. Steam Line Material 33 Table 12. Recommended Material and Size for Steam Run 33 Table 13. Recommended Condensate Line at Distributor(s) 33 Table 14. Maximum Recommended Length of Steam Runs 34 Table 15. Air Pressure Loss in AHU/Duct 44 Table 16. Condensate Loss 46 Table 17. SAM-e Tube Matrix 48 Table 18. Mini SAM-e Headers – 3" 49 Table 19. Mini SAM-e Headers – 6" 49 Table 20. Mini SAM-e Tubes 49 Table 21. Mini Inlet Configurations – For Atmospheric Steam Unit 49 Table 22. Ceiling and Frontal Clearances for Blower Packs 52

10-30 SUBMITTALS

Table 1. NH Series Unit Options 99 Table 2. Common Accessories Universal 100 Table 3. Steam Distributors 100 Table 4. Steam Distributor Accessories 101 Table 5. SAM-e Header 103 Table 6. Adjustable Mounting Frame for SAM-e 106 Table 7. SAM-e Tube Matrix 106 Table 8. SAM-e Inlet and Adapter Configurations 110 Table 9. Remote Blower Pack 111 Table 10. Built-On Blower Pack 111 Table 11. Controls – ON/OFF 112 Table 12. Modulating Control By NORTEC 112

2008-10-01

Page 8 of the Nortec NHTC user manual — 2008-10-01
Seite 8 · Zum Vergrößern klicken
Seite 8

Table Page

Table 13. Modulating Demand Signal By Others Single Channel 113 Table 14. Modulating Demand Signal By Others Dual Channel 113 Table 15. Modulating By Other Transducer Signal 113 Table 16. NORTEC OnLine Options 114 Table 17. NORTEC Links Options 114 Table 18. NH Series Fusing Options 114

2008-10-01

Page 9 of the Nortec NHTC user manual — 10-00 INTRODUCTION
Seite 9 · Zum Vergrößern klicken
Seite 9
Nortec NHTC — 10-00 INTRODUCTION diagram (page 9)
Abb. 5

10-00 INTRODUCTION

Page 10 of the Nortec NHTC user manual — Figure 1. NHTC
Seite 10 · Zum Vergrößern klicken
Seite 10
Nortec NHTC — Figure 1. NHTC diagram (page 10)
Abb. 6 · Figure 1. NHTC

Figure 1. NHTC

Page 11 of the Nortec NHTC user manual — A. PROPORTIONAL + INTEGRAL AUTO-ADAPTIVE CONTROL SYSTEM FOR THE
Seite 11 · Zum Vergrößern klicken
Seite 11

1. INTRODUCTION

The NHTC humidifier is controlled by Nortec’s Patented Auto adaptive Water Management Control System. This system allows the humidifiers to adapt to basically any potable incoming water and changes that occur to the water supply. This eliminates the need to readjust drain timers, changes complete cylinders or time consuming adjustment of electrode spacing’s. The system also adjusts the drain rate of the humidifier to reduce the amount of drain water exiting the humidifier as water conditions change. This reduces energy loss due to excessive draining of hot water and extends cylinder life since less water and minerals enter the humidifier.

The following is a brief description of how the Auto-Adaptive water Management System works.

The electrode steam system produces pure uncontaminated steam with variable output through electronic power control of the electrodes. Water borne minerals remain in the cylinder and are periodically flushed out through the automatic cylinder drain. On NHTC and NHPC models the drain automatically empties the steam cylinder if it is not operated for three days. Solid mineral scale sinks to the bottom of the cylinder which, when filled with residue, is easily removed and replaced.

A. PROPORTIONAL + INTEGRAL AUTO-ADAPTIVE CONTROL SYSTEM FOR THE

NHTC/ NHPC

(1) NORTEC’s patented P+I Auto-Adaptive control system allows the unit to operate at an optimal low water level using the same fixed electrode spacing regardless of the incoming water conditions. Boiling of the water allows the minerals in the water to remain behind in the cylinder. This raises the contained water conductivity to a value higher than the incoming water. The P+I Auto-Adaptive control system monitors and adjusts the contained water conductivity as these changes occur.

(2) The humidifiers are designed to produce full steam output at the lowest possible electrode coverage to obtain maximum cylinder life.

(3) The units operate between A and D of the main steam output demand. Accordingly, the current flow between the electrodes in the cylinder is maintained between these pre-established limits programmed into the P+I Auto-Adaptive control system.

(4) As the water boils away and the electrode coverage is reduced, the steam output is also reduced slightly. A pre-determined design parameter of every NORTEC cylinder is the known time (To) (time optimum) that it takes to boil down from A to D of output (also referenced to as amp trigger points) at a pre-designed contained water conductivity. (See Figure 2.)

(5) Whenever the conductivity in the cylinder water is lower than the designed conductivity, the (Ta) (time actual) to boil down from A to D will be longer than the To. (See Figure 3.)

Page 12 of the Nortec NHTC user manual — 1. INTRODUCTION
Seite 12 · Zum Vergrößern klicken
Seite 12

(6) As the water is boiled away, the minerals left behind increase the conductivity of the water in the cylinder. As soon as the conductivity is greater than design, the Ta to boil from A to D will be shorter than To and a drain cycle is initiated.

(7) The fill valve always opens during timer drains, adding cold water to mix with the hot water from the cylinder during automatic drain cycles. This tempering process is required to meet plumbing codes.

(8) As can be seen from a typical sequence depicted in Figure 4, the P+I Auto- Adaptive system allows the unit to be self-regulating. It drains only when necessary and only the amount of water to maintain optimum operating conditions.

(9) Relying on the proportional (P) feedback only to decide how much to drain is like guessing what is happening based on a ‘snapshot’ only. By taking into consideration a series of “snapshots”: (one from each of the past ten cycles for example), the control system has more data on which to base its decision to drain. The integral (I) part of the P+I Auto-Adaptive system provides this added feedback.

(10) The proportional (P) and integral (I) factors have been weighted as to the relative

influence each will have when the NHTC/NHPC calculates a drain. The preprogrammed weighing was derived through extensive field and laboratory tests. When supply water conductivity is extremely high (requiring substantially more drains), the NHTC/NHPC will see the pattern developing in cycles stored in memory. It will then initiate additional drains to adjust the contained water conductivity.

(11) If low conductive water conditions occur, the P+I control will reduce the drains

necessary to maintain optimum operating conditions within the cylinder. If extreme water conditions are encountered, the NHTC/NHPC can be reprogrammed with factory instructions to compensate.

(12) NORTEC’s P+I Auto-Adaptive control system has been designed to benefit users

who demand very tight control of the relative humidity. It maintains steam output above the B level, even during auto drains. (See Figure 4.)

(13) The P+I Auto-Adaptive control system allows the humidifier to maintain tighter

humidity control without the problem of rh depression during drain cycles that occur with other humidifiers. This results in more consistent space rh levels, even with a simple on/off control system.

Page 13 of the Nortec NHTC user manual — Figure 2. Optimum Boiling Time
Seite 13 · Zum Vergrößern klicken
Seite 13
Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 7 · Figure 2. Optimum Boiling Time
Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 8 · Figure 2. Optimum Boiling Time
Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 9 · Figure 2. Optimum Boiling Time

Figure 2. Optimum Boiling Time

Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 10 · Figure 2. Optimum Boiling Time
Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 11 · Figure 2. Optimum Boiling Time
Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 12 · Figure 2. Optimum Boiling Time
Nortec NHTC — Figure 2. Optimum Boiling Time diagram (page 13)
Abb. 13 · Figure 2. Optimum Boiling Time

Figure 3. Conductivity

Page 14 of the Nortec NHTC user manual — (3) Output vs Cylinder Life
Seite 14 · Zum Vergrößern klicken
Seite 14

B. NH CAPACITY ADJUSTMENT

(1) Each NORTEC NH Series humidifier is rated at its maximum output capacity. By means of the alphanumeric display and keypad on the NHTC/NHPC, the humidifiers can be adjusted to obtain an output between 20% and 100% of its rated capacity.

C. DRAIN CYCLE AND CYLINDER LIFE

(1) Water Type Used (Potable or Softened)

(a) The electrode steam product line is one of the most efficient humidifier systems since it uses the minerals in the water to conduct electricity. If no minerals are present no current can pass from one electrode to another, thus no steam production can occur.

(b) Although the electrode steam humidifier is ideal for potable water, it should not be used with pure reverse osmosis or deionized water since the conductivity is too low.

(2) Water Conditions vs Cylinder Life

(a) The NH Series is designed to adapt to most potable or softened water supplies. Since the output of all NH Series humidifiers is pure, clean steam, minerals originally in the incoming water are left behind in the steam cylinder. Many of these minerals will be removed during short flush cycles within the cylinder. Therefore, the water chemistry, the unit running time, and output capacity setting ultimately determines the cylinder life. (See Figure .)

(3) Output vs Cylinder Life

(a) As minerals build-up on the electrodes in the cylinder of the NORTEC NH Series humidifier, the patented P+I Auto-Adaptive control system automatically raises the water level slightly in the cylinder. This exposes fresh electrode surface to the water and maintains peak output and efficiency from the humidifier. Once the

(b) electrode surface is completely encrusted by the minerals, the user is alerted to change the cylinder. Other humidifiers’ performance degrades gradually as the minerals build-up. The NH Series maintains maximum efficiency then the cylinder is replaced. (See Figure .)

(4) Water Conditions vs Drain Rate

(a) The P+I Auto-Adaptive control system automatically adjusts the drain rate to maintain the design water conductivity required for proper operation. This ensures regular flushing of minerals which become concentrated in the water, and minimizing wastage of hot water. The humidifier automatically adjusts it’s drain rate with changes in incoming water conductivity through the Auto- adaptive water management system.

Page 15 of the Nortec NHTC user manual — Figure 4. Typical Auto-Adaptive Operation
Seite 15 · Zum Vergrößern klicken
Seite 15
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 15)
Abb. 14 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 15)
Abb. 15 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 15)
Abb. 16 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 15)
Abb. 17 · Figure 4. Typical Auto-Adaptive Operation

0. Store previous cycle’s drain decision in integral (l) memory. 1. Fill to A trigger (use all places below 1-10). 2. Boil to C trigger without timing to allow previous fill water to mix thoroughly during boiling. 3. Boil from C to D while monitoring time (T actual). 4. Decide how long (how much) to drain, then fill to B. 5. Drain according to the P+I calculated drain time, fill on to control outlet temperature. 6. At D, stop draining and postpone remaining drain, fill to B. 7. Continue remaining drain. 8. With drain finished, fill to A. 9. Boil to D, timing from C to D. 10. Decide how long to drain (in this case zero) based on present and past cycles.

Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 15)
Abb. 18 · Figure 4. Typical Auto-Adaptive Operation

Figure 4. Typical Auto-Adaptive Operation

Page 16 of the Nortec NHTC user manual — Figure 4. Typical Auto-Adaptive Operation
Seite 16 · Zum Vergrößern klicken
Seite 16

It is important to note that the drain rate shown includes the make-up water, mixed with the drain water, which tempers the drain water to 140°F (60°C) or less.

Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 19 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 20 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 21 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 22 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 23 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 24 · Figure 4. Typical Auto-Adaptive Operation
Nortec NHTC — Figure 4. Typical Auto-Adaptive Operation diagram (page 16)
Abb. 25 · Figure 4. Typical Auto-Adaptive Operation

Figure 6. Output vs Service Life

Figure 5. Capacity Setting & Cylinder Life

Page 17 of the Nortec NHTC user manual — A. GENERAL
Seite 17 · Zum Vergrößern klicken
Seite 17

3. PRE-INSTALLATION EQUIPMENT VERIFICATION

A. GENERAL

(1) Ensure the available voltage and phase correspond with humidifier voltage and

phase as indicated on the humidifier’s specification label.

(2) Ensure that the external fuse disconnect is sufficient size to handle the rated

amperage as indicated on the humidifier’s specifications label. Refer to local building codes.

(3) Report any discrepancy immediately to the site engineer.

(4) Location and mounting is described in Chapter 10-10.

(5) For typical installation see Figures 6 & 7.

Page 18 of the Nortec NHTC user manual — Figure 6. Typical NHRS Installation (Sheet 1 of 2)
Seite 18 · Zum Vergrößern klicken
Seite 18
Nortec NHTC — Figure 6. Typical NHRS Installation (Sheet 1 of 2) diagram (page 18)
Abb. 26 · Figure 6. Typical NHRS Installation (Sheet 1 of 2)

Figure 6. Typical NHRS Installation (Sheet 1 of 2)

Page 19 of the Nortec NHTC user manual — Figure 7. Typical NHRS Installation (Sheet 2 of 2)
Seite 19 · Zum Vergrößern klicken
Seite 19
Nortec NHTC — Figure 7. Typical NHRS Installation (Sheet 2 of 2) diagram (page 19)
Abb. 27 · Figure 7. Typical NHRS Installation (Sheet 2 of 2)

Figure 7. Typical NHRS Installation (Sheet 2 of 2)

Page 20 of the Nortec NHTC user manual — HUMIDITY, STEAM ABSORPTION
Seite 20 · Zum Vergrößern klicken
Seite 20

HUMIDITY, STEAM ABSORPTION

AND DISTRIBUTION

Page 21 of the Nortec NHTC user manual — D. TEMPERATURE AND HUMIDITY AVAILABLE
Seite 21 · Zum Vergrößern klicken
Seite 21

HUMIDITY, STEAM ABSORPTION AND DISTRIBUTION

1. HUMIDITY

A. ESTIMATING THE HUMIDIFICATION LOAD

(1) Relative humidity is the percentage of moisture in the volume of air at a given

temperature, compared to the maximum amount of moisture that the volume of air can hold at the same temperature and atmospheric pressure. As air becomes warmer, it can absorb more moisture per unit volume. Therefore a quantity of air containing a specific amount of moisture will have different values of relative humidity as the temperature changes.

(2) It is this process that causes dry air in building. As cold incoming air is heated, its

relative humidity value drops. Therefore moisture must be added to attain an acceptable level of humidity within the building. Determining how much moisture must be added is the object of this brochure. Table 2 simplifies the calculations which are described here in detail.

B. LOAD CALCULATION SUMMARY

(1) In order to determine the humidification load three basic values need to be known:

(a) The design conditions of the humidified space, i.e., the temperature and humidity

required.

(b) The conditions of the incoming air, i.e., the temperature and humidity available.

(c) Incoming air volume and secondary conditions that can affect the humidification load.

(2) Data and calculations required to estimate humidification load are described in

Tables 1, 2 and 3.

C. TEMPERATURE AND HUMIDITY REQUIRED

(1) The design temperature and humidity of a space depends mostly upon the job being

performed. Once the design temperature and humidity have been established, the required moisture can be found in gr/ft3 from Table 3. Remember always to take the worst case (highest temperature, highest humidity).

For example: The press room of a printing plant should be kept at 76 - 80°F with 43% - 47% rh

Therefore, the worst case is 80°F, 47% rh. From Table 3 the required moisture is 11.04 gr/ft3 x 47% = 5.19 gr/ft3

D. TEMPERATURE AND HUMIDITY AVAILABLE

(1) The outdoor conditions tell us the moisture available in the incoming air. Approximate

values can be obtained from Table 4 and combined with Table 3 to find moisture available. Once again we must take the worst case (here, it is lowest temperature, lowest humidity). As can be seen, the contribution of moisture from the outside air is almost zero.

(2) Formula 1

Page 22 of the Nortec NHTC user manual — Table 2. Load Calculation Summary Sheet
Seite 22 · Zum Vergrößern klicken
Seite 22

Table 1. Outdoor/Indoor Relative Humidity Conversion Chart

100% 2 4 5 6 7 9 12 17 19 23 29 36 43 52

95% 2 3 4 6 7 9 12 16 17 22 28 34 41 50

90% 2 3 4 5 6 8 11 15 16 21 26 31 39 48

85% 2 3 4 5 6 8 11 14 15 20 24 29 37 45

80% 2 3 4 5 6 7 10 13 15 19 23 27 35 42

75% 2 3 4 4 5 7 10 12 14 18 22 26 33 39

70% 1 2 3 4 5 6 9 11 13 17 20 24 31 36

65% 1 2 3 4 4 5 8 10 12 15 19 23 29 34

60% 1 2 3 3 4 5 7 9 11 14 17 21 26 31

55% 1 1 3 3 4 4 7 8 10 13 16 19 24 29

50% 1 1 2 3 3 4 6 8 9 12 14 18 22 26

45% 1 1 2 3 3 4 6 7 8 11 13 16 20 24

40% 1 1 2 2 3 4 5 7 7 10 12 14 18 21

35% 1 1 2 2 2 4 5 6 6 9 10 12 15 18

30% 0 1 2 2 2 3 4 5 6 7 9 11 13 15

25% 0 1 1 1 2 3 3 4 5 5 7 9 11 13

20% 0 1 1 1 2 2 3 3 4 5 5 7 9 10

15% 0 0 1 2 3 3 4 4 5 6 8

10% 0 0 0 1 1 1 2 2 2 3 3 3 4 6

5% 0 1 1 1 2 2 2 3 3

0% 0

-20° -10° -5° 0° +5° +10° +15° +20° +25° +30° +35° +40° +45° +50°

Outdoor temperature Chart shows what the residual indoor RH would be at 70°F under varying outdoor conditions if a proper humidification system were not installed in the building. Studies indicate that the recommended RH should be between 40% and 60% for optimum benefits to the occupants.

Table 2. Load Calculation Summary Sheet

Determine the moisture required in the space (Table 3)

Grains from Table 3 at space temp x Indoor RH = A gr/ft3

Determine the moisture level of incoming air (Table 4)

Grains from Table 4 at space temp x Outdoor RH = B gr/ft3

Therefore: moisture to be added: (moisture) M - A - B gr/ft3 →M gr/ft3

Determine the volume of air to be humidified. Choose the largest value.

1. Natural ventilation: Volume x number of air changes ft 3 /hr
2. Exhaust air: CFM x 60 min/hr ft 3 /hr
3. Make-up air: CFM x 60 min/hr ft 3 /hr → C ft 3 /hr

Therefore: Gross humidification load = L (load) = MxC = lbs/hr →L lbs/hr 7,000

Outdoor relative humidity

Page 23 of the Nortec NHTC user manual — E. INCOMING AIR VOLUME
Seite 23 · Zum Vergrößern klicken
Seite 23

Table 3. Grains of Water Per Cubic Foot – Saturated Air (100% rh)

°C °F Grains °C °F Grains °C °F Grains °C °F Grains °C °F Grains °C °F Grains

-23 -10 .29 4 40 2.86 58 5.41 76 9.75 35 95 17.28 114 29.34

-5 .35 41 2.97 59 5.60 77 10.06 96 17.80 115 30.13

-18 0 .48 42 3.08 16 60 5.80 78 10.40 97 18.31 49 120 34.38

8 .61 43 3.20 61 6.00 79 10.80 98 18.85 125 39.13

-12 10 .78 44 3.32 62 6.20 27 80 11.04 99 19.39 54 130 44.41

-9 15 .99 7 45 3.44 63 6.41 81 11.40 38 100 19.95 135 50.30

-7 20 1.24 46 3.56 64 6.62 82 11.75 101 20.52 60 140 56.81

-4 25 1.56 47 3.69 18 65 6.85 83 12.11 102 21.11 145 64.04

-1 30 1.95 48 3.83 66 7.07 84 12.49 103 21.71 66 150 72.00

31 2.04 49 3.97 67 7.31 29 85 12.87 104 22.32 155 80.77

32 2.13 10 50 4.11 68 7.57 86 13.27 41 105 22.95 71 160 90.43

33 2.21 51 4.26 69 7.80 87 13.67 106 23.60 165 101.00

34 2.29 52 4.41 21 70 8.10 88 14.08 107 24.26 77 170 112.60

2 35 2.38 53 4.56 71 8.32 89 14.51 108 24.93 175 125.40

36 2.47 54 4.72 72 8.59 32 90 14.94 109 25.62 82 180 139.20

37 2.56 13 55 4.89 73 8.87 91 15.39 43 110 26.34 185 154.30

38 2.66 56 5.06 74 9.15 92 15.84 111 27.07 88 190 170.70

39 2.76 57 5.23 24 75 9.45 93 16.31 112 27.81 195 188.60

94 16.79 113 28.57

Assume our printing plant is located in Denver, Colorado. From Table 4, the worst case is -10°F with 37% rh

From Table 30.29 gr/ft 3 x 37% rh - 0.11 gr/ft 3

Combining this result with that of Moisture Required (A) we see that we will need 5.19 - 0.11 = 5.08 grains of moisture for every cubic foot of outside air brought in.

E. INCOMING AIR VOLUME

(1) The following outlines the steps necessary to determine the amount of outside air being

brought into the humidified space and the corresponding amount of moisture required. There are three basic means by which outside air is introduced into the humidified space. These are:

(a) Through natural ventilation, for example, opening and closing doors and windows,

and by infiltration through cracks and openings in the building construction.

(b) Through mechanical ventilation, for example, the introduction of make-up air, or

the exhausting of stale air by the building HVAC system.

(c) Through the economizer section of the HVAC system - if this feature is included in the system.

(2) For maximum accuracy, all three should be estimated and the largest chosen.

(2) Formula 2

Page 24 of the Nortec NHTC user manual — 7:30 P.M. °C
Seite 24 · Zum Vergrößern klicken
Seite 24

Table 4. Design Outdoor Conditions

(% RH)

(% RH)

7:30 A.M.

1:30 P.M.

7:30 P.M.

7:30 A.M.

1:30 P.M.

7:30 P.M. °C

°F

°F

56 64 68 78 35 35 Arizona Flagstaff Phoenix Yuma

10 10 81 --

95 95 84 90

32 41 44 Arkansas Little Rock -15 5 80 67 68 95 85 55 59 35

California Eureka Fresno Los Angeles Sacramento San Diego San Francisco

32 41 32 38 29 29 Colorado Denver Grand Junction Pueblo

30 25 35 30 35 35

87 93 63 90 76 84

-- 80 46 82 58 68

77 66 51 70 60 70

90 105 90 100 85 85

92 61 85 76 86 92

-- 36 50 46 68 75

80 20 54 28 65 78

35 35 35 Connecticut New Haven -18 0 75 65 69 95 77 64 74 35 Delaware Wilmington -18 0 77 62 70 95 80 52 69 35 District of Columbia

Washington -18 0 73 56 64 95 78 52 64 35

2 25 35 89 87 56 59 75 75 95 91 85 83 57 64 76 76 35 33 Georgia Atlanta Augusta Savannah

35 37 35 Idaho Boise Lewiston

82 79 75 73 74 71 95 95 54 64 34 37 23 25 35 35 Illinois Cairo Chicago Peoria

37 35 35 Indiana Fort Wayne Indianapolis Terre Haute

35 35 35 Iowa Davenport Sioux City

-- 78 -- 67 -- 72 95 95 -- 86 -- 55 -- 54 35 35 Kansas Dodge City Topeka

78 78 57 64 61 67 95 100 77 85 45 54 52 54 35 38 Kentucky Louisville -18 0 78 68 69 95 77 52 57 35 Louisiana New Orleans Shreveport

20 20 85 83 67 67 73 66 95 100 84 86 64 56 72 62 35 38 Maine Portland -21 -5 81 65 74 90 78 58 76 32 Maryland Baltimore -18 0 72 68 56 95 71 52 65 35

Massachusetts Boston -18 0 72 59 67 92 72 55 70 33 Michigan Detroit Grand Rapids

82 85 71 78 77 80 95 95 74 76 50 51 56 54 35 35 Minnesota Duluth Minneapolis

78 82 74 72 74 75 93 95 87 82 61 54 66 54 33 35 Mississippi Vicksburg -12 10 82 65 67 95 87 61 70 35

0 78 77 64 65 66 68 100 95 76 73 48 50 47 55 38 35 Montana Billings Butte

Kansas City St. Louis

67 76 73 70 60 71 90 95 65 82 40 36 33 33 32 35 Nebraska North Platte Omaha

80 82 62 68 66 73 85 95 84 80 50 51 46 51 29 35 Nevada Reno -21 -5 82 67 54 95 72 25 20 35 New Hampshire Concord -26 -15 78 60 69 90 80 49 69 32

Show 66 more labels / short text on this page
JANUARY Relative Humidity · JULY Relative Humidity · Dry Bulb · Dry Bulb · State City °C · Alabama Birmingham Mobile · -12 -12 · 83 75 56 · 58 47 37 · -- 39 27 · 90 105 110 · 77 53 51 · 36 31 31 · -- 23 23 · -23 -26 -29 · -10 -15 -20 · 54 77 67 · 37 64 44 · 41 64 48 · 95 95 95 · 55 48 73 · 27 27 34 · 30 22 35 · Florida Jacksonville Miami · -12 -12 · 10 10 20 · 80 84 83 · 64 59 58 · 69 69 72 · 95 98 95 · 83 83 85 · 57 55 61 · 68 69 80 · -23 -20 · -18 -23 -23 · 0 -10 -10 · 81 81 83 · 69 70 72 · -- 75 77 · 98 95 96 · 83 78 81 · 57 51 53 · -- 55 58 · -23 -23 -18 · -10 -10 · 84 83 82 · 75 72 70 · 81 78 76 · 95 95 95 · 84 84 77 · 53 54 50 · 58 60 56 · -26 -29 · -15 -20 · -23 -23 · -10 -10 · -23 -23 · -10 -10 · -32 -29 · -25 -20 · -23 -18 · Missouri · -32 -29 · -25 -20 · -29 -23 · -20 -10
Page 25 of the Nortec NHTC user manual — 7:30 P.M. °C
Seite 25 · Zum Vergrößern klicken
Seite 25

Table 4. Design Outdoor Conditions (cont)

(% RH)

(% RH)

7:30 A.M.

1:30 P.M.

7:30 P.M.

7:30 A.M.

1:30 P.M.

7:30 P.M. °C

°F

°F

New Jersey Atlantic City Newark Trenton

35 35 35 New Mexico Albuquerque -18 0 68 51 46 95 59 33 28 35 New York Albany Buffalo New York Rochester

34 34 35 35 North Carolina Asheville Raleigh

-23 -21 -18 -21

75 79 72 81

63 72 61 73

71 78 66 79

93 93 95 95

79 78 75 80

52 53 58 50

64 63 68 60

0 10 82 82 59 57 69 69 93 95 88 86 56 55 73 72 34 35 North Dakota Bismarck -34 -30 77 71 75 95 85 52 49 35 Ohio Cincinnati Cleveland Columbus Toledo

35 Oklahoma Oklahoma City -18 0 79 62 65 101 80 49 51 38 Oregon Baker Portland

-18 -18 -23 -23

0 0 -10 -10

82 81 83 79

70 72 71 72

74 79 76 75

95

84 79 78 76

52

60 58 60 59

12 -5 10 83 87 81 82 78 78 90 90 69 86 68 63 36 48 32 32 Pennsylvania Harrisburg Philadelphia Pittsburgh Scranton

35 Rhode Island Providence -18 0 73 60 67 93 79 57 73 34 South Carolina Charleston Columbia

-18 -18 -18 -21

0 0 0 -5

72 74 77 80

49 65 67 67

65 68 63 --

95

78 78 80 77

51 52 52 50

62 64 63 --

15 10 87 81 55 57 76 65 95 95 88 83 64 56 82 68 35 35 South Dakota Huron Rapid City

79 71 72 69 76 67 95 95 86 71 52 42 49 40 35 35 Tennessee Knoxville Memphis

0 0 83 82 65 67 69 73 95 95 83 85 55 55 66 59 35 35 Texas Amarillo Corpus Christi Dallas El Paso Houston San Antonio

38 35 38 38 35 38 Utah Salt Lake City -23 -10 80 71 72 95 56 27 23 35 Vermont Burlington -23 -10 81 69 78 90 76 54 67 32 Virginia Richmond -9 15 84 60 68 95 81 57 72 35 Washington Seattle Walla Walla

71 88 81 63 85 82

51 66 62 45 66 60

52 75 62 39 73 59

100 95 100 100 95 100

77 93 79 60 90 88

43 58 50 37 58 49

42 68 47 30 66 45

20 10 10 20 20

86 80 80 74 74 78 85 95 86 50 63 33 47 22 29 35 West Virginia Charleston Parkersburg

79 82 64 66 70 74 95 95 88 80 53 52 67 65 35 35 Wisconsin Green Bay Milwaukee

75 76 68 70 73 73 95 95 85 81 58 58 64 64 35 35 Wyoming Cheyenne -26 -15 59 48 55 95 73 36 40 35 Province City Alberta Calgary Edmonton Grande Prairie Lethbridge Medicine Hat

31 30 29 33 36 British Columbia Estevan Point Fort Nelson Penticton Prince George Prince Rupert Vancouver

-34 -34 -42 -36 -34

-29 -29 -43 -32 -30

71 75 80 66 73

87 86 84 91 96

34 42 38 30 31

-8 -40 -18 -38 -12

84 79 81 82 87 87

87 94 85 73 80 80

32 32 44 53 54 41

31 34 29 23 27 27

Show 21 more labels / short text on this page
JANUARY Relative Humidity · JULY Relative Humidity · Dry Bulb · Dry Bulb · State City °C · -15 -18 -18 · 79 72 73 · 68 79 62 · 74 65 68 · 95 95 95 · 81 75 77 · 72 51 55 · 82 65 68 · -18 -12 · -29 -29 · -20 -20 · -18 -18 · -7 -12 -12 · -18 -23 · -26 -26 · -15 -15
Page 26 of the Nortec NHTC user manual — 7:30 P.M. °C
Seite 26 · Zum Vergrößern klicken
Seite 26

Table 4. Design Outdoor Conditions (cont)

(% RH)

(% RH)

7:30 A.M.

1:30 P.M.

7:30 P.M.

7:30 A.M.

1:30 P.M.

7:30 P.M. °C

°F

°F

Manitoba Brandon Churchill The Pas Winnipeg

32 26 29 32 New Brunswick Campbellton Fredericton Moncton Saint John

-34 -40 -37 -34

-29 -40 -35 -29

73 76 77 78

90 79 85 90

50 57 54 50

31 32 31 27 Newfoundland Corner Brook Gander Goose Bay St. John’s

-28 -27 -24 -24

-18 -16 -12 -12

77 72 82 82

87 89 88 81

54 47 52 62

29 29 30 26 N.W.T. Frobisher Resolute Yellowknife

-23 -21 -32 -17

84 85 86 79

47 45 42 60

17 12 26 Nova Scotia Halifax Sydney Yarmouth

28 29 24 Ontario Thunder Bay Hamilton Kaspuskasing Kingston Kitchener London North Bay Ottawa Peterborough Sioux Lookout Sudbury Timmins Toronto Windsor Sault St. Marie

30 33 31 29 31 32 31 32 32 18 32 32 32 31 29 P.E.I. Charlottetown -21 -6 86 84 57 29 Quebec Knob Lake Mont Joli Montreal Port Harrison Quebec City Sept-Iles Sherbrooke Trois Rivieres

-33 -18 -34 -24 -19 -18 -29 -27 -25 -36 -29 -36 -19 -16 -29

86 91 87 85 88 90 87 90 90 65 89 90 90 92 88

52 52 52 69 58 53 46 50 53 69 44 45 56 51 48

0 -20 -17 -13 -33 -20 -33

77 78 81 79 82

-40 -24 -27 -39 -28 -33 -28 -28

-11 -16 -39 -19 -27 -18 -18

30 27 31 31 Saskatchewan Prince Albert Regina Saskatoon Swift Current

86 80 87 88

60 47 58 58

31 33 32 34 Yukon Territory Dawson Whitehorse

-41 -37 -37 -34

-41 -34 -34 -29

77 81 76 79

88 92 90 93

76 80 57 78 60 40 14 26

Show 23 more labels / short text on this page
JANUARY Relative Humidity · JULY Relative Humidity · Dry Bulb · Dry Bulb · Province City °C · 84 76 85 · -43 -45 -45 · -45 -49 -49 · 77 71 82 · 63 54 78 · 67 81 50 · -18 -17 -15 · 83 84 83 · 83 84 76 · 50 56 70 · 80 75 79 · 84 80 77 · -3 -3 -20 · 55 62 88 · 70 71 58 · 13 17 31 · -49 -43 · -56 -45
Page 27 of the Nortec NHTC user manual — Figure 1. Schematic of a Typical Print Shop HVAC System
Seite 27 · Zum Vergrößern klicken
Seite 27

(3) Using the natural ventilation method requires knowing the volume of the humidified

space and the type of construction. A tightly constructed building will have a least one air change per hour. A loosely constructed building will have at least one and one half changes per hour, and this same building with a large a amount of incoming or exiting traffic will have at least two air changes per hour.

Assume our print shop has a floor area of 100' x 100' with a 20' ceiling with a large amount of traffic. This requires

100' x 100' x 20' x 2 = 400,000 ft3/hr.

Using our example, the moisture required is

400,000 x 5.08 = 290 lbs/hr 7000 grains/lb

(4) Using make-up air:

Assume our print shop has a 15,000 CFM HVAC system and uses 10% make-up air during winter. The amount of outside make-up air entering the HVAC system will, therefore, be 10% of 15,000 CFM = 1,500 CFM. The moisture required will be

1,500 x 5.08 x 60 min/hr = 65 lbs/hr 7,000 grains/lb

(Refer to Figure 1.)

Nortec NHTC — Figure 1. Schematic of a Typical Print Shop HVAC System diagram (page 27)
Abb. 28 · Figure 1. Schematic of a Typical Print Shop HVAC Sys…

Figure 1. Schematic of a Typical Print Shop HVAC System

(a) Formula 3 · (a) Formula 4

Page 28 of the Nortec NHTC user manual — Figure 1. Schematic of a Typical Print Shop HVAC System
Seite 28 · Zum Vergrößern klicken
Seite 28

(5) Using an exhaust air fan:

Assume the print shop has a 1,000 CFM fan to exhaust a drying room. The moisture required to humidify the drying room only is

1,000 x 5.08 x 60 min/hr = 44 lbs/hr 7,000 grains/lb

(Refer to Figure 1.)

(6) Using an economizer cycle:

(a) Care should be taken in sizing humidification load when an economizer cycle is

incorporated into a building HVAC system. The purpose of an economizer cycle is to provide building cooling using outside air, rather then the building refrigeration system when outside air conditions permit.

(b) The economizer cycle senses and compares outdoor air temperature and return

air temperature during the cooling season.

(c) When the HVAC system calls for cooling and the outdoor air temperature is low enough – typically 55°F or lower – the outside air and exhaust air dampers are positioned to provide the required supply air temperature to maintain cooling, and the recirculated air damper is positioned to maintain the required supply air volume. When the outdoor air temperature is higher than the supply air temperature required to maintain cooling but is lower than the return air temperature, the make-up air and exhaust air dampers are 100% open. The recirculation air damper closes, and the building refrigeration system provides the portion of cooling load that cannot be provided by outside air intake.

(d) From this it can be seen that it is possible to introduce 100% outside air into a

building during the cooling season.

For example, if out print shop were using 100% outdoor air at 55°F and 40% rh, then the moisture required is

5.19 - (4.89 x 40% rh) = 3.23 gr/ft3

Therefore, on a 15,000 CFM system, the humidification load will be

15,000 x 3.23 x 60 min/hr = 415 lbs/hr 7,000 grains/lb

(f) In the above examples, the largest humidification load was due to the economizer cycle at 415 lbs/hr.

(7) Using cooling or refrigeration loads:

(a) As air is cooled, it loses it’s ability to hold moisture. If it is cooled enough, some of

the moisture will condense out. This is known as cooling load. Cooling load calculations can be important for process applications or refrigeration applications to product dehydration.

(a) Formula 5 · (e) Formula 6

Page 29 of the Nortec NHTC user manual — Table 5. Inside Relative Humidities At Which Moisture Will Condense On Windows
Seite 29 · Zum Vergrößern klicken
Seite 29

Assume that during the summer the HVAC system is in the cooling mode. The air leaving the cooling coil is at 55°F and 90% rh. In order to maintain the desired 47% rh in the space, moisture must be added using the following formula:

Desired space 80°F 47% rh= 5.19 gr/ft3

55°F 90% = 4.89 x 0.90 = 4.40 gr/ft3 Grains to add = 0.79 gr/ft3

15,000 x 0.79 x 60 min/hr = 101.57 lbs/hr 7,000 grains/lb

(8) In considering Process and Environment, in Tables 5 through 7 you will find conditions

and processes that may affect your calculation and should be addressed.

(a) Table 5 shows the outdoor temperature at which the rh would cause condensation

on the windows to the outside. Should your outdoor conditions make this a possibility, an outdoor setback sensor may be a solution.

(b) Table 6 describes the moisture gain of various material and if your process or

environment includes a great amount of these materials that are constantly introduced to the area, its affects must be considered.

(c) Table 7 identifies many recommended indoor conditions for various locations and processes, these can be of use when deciding what conditions would be most beneficial in your application.

(d) In Figure 2, you will find the ASHRAE physchrometric chart describing the

enthalpy of dry air and the effects to and from rh in the air.

Table 5. Inside Relative Humidities At Which Moisture Will Condense On Windows

Outside Temperature Inside Temperature (°F/°C) Outside Temperature Inside Temperature (°F/°C)

°F °C 60/ 15.5 65/ 18.3 70/ 21 75/ 23.8 80/ 26.6 °F °C 60/ 15.5 65/ 18.3 70/ 21 75/ 23.8 80/ 26.6

Single Windows, Still Air Single Windows, Wind

-50 -45 9 9 9 8 8 -50 -45 4 3 3 3 2

-40 -40 12 12 11 10 10 -40 -40 5 4 4 4 3

-30 -34 16 14 14 13 13 -30 -34 7 6 6 6 5

-20 -29 20 18 18 17 16 -20 -29 10 9 9 8 7

-10 -23 25 23 22 21 20 -10 -23 14 13 12 11 10

0 -18 32 29 27 25 24 0 -18 20 18 16 15 13

10 -12 39 36 33 31 29 10 -12 28 24 22 20 18

20 -7 47 43 40 37 35 20 -7 36 32 30 26 24

30 -1 57 52 50 45 42 30 -1 48 41 38 34 30

40 4 70 63 60 53 50 40 4 62 54 49 43 40

(b) Formula 7 · (Formula 1)

Page 30 of the Nortec NHTC user manual — Table 6. Regain of Hygroscopic Materials
Seite 30 · Zum Vergrößern klicken
Seite 30

Table 5. Inside Relative Humidities At Which Moisture Will Condense On Windows (cont)

Outside Temperature Inside Temperature (°F/°C) Outside Temperature Inside Temperature (°F/°C)

°F °C 60/ 15.5 65/ 18.3 70/ 21 75/ 23.8 80/ 26.6 °F °C 60/ 15.5 65/ 18.3 70/ 21 75/ 23.8 80/ 26.6

Double Windows, Still Air Double Windows, Wind

-50 -45 34 34 34 33 32 -50 -45 23 26 26 26 25

-40 -40 38 38 36 36 35 -40 -40 32 30 30 29 28

-30 -34 42 42 41 40 38 -30 -34 36 34 34 32 31

-20 -29 47 46 46 44 42 -20 -29 41 39 38 35 35

-10 -23 52 50 49 48 46 -10 -23 46 45 42 42 39

0 -18 57 55 55 52 50 0 -18 52 49 47 46 44

10 -12 62 60 59 57 54 10 -12 58 56 53 52 49

20 -7 69 66 63 62 59 20 -7 65 63 59 58 54

30 -1 76 73 71 68 65 30 -1 72 70 66 64 60

40 4 84 80 79 74 71 40 4 80 78 73 70 67

Table 6. Regain of Hygroscopic Materials

Industry Materials Relative Humidity - %

10 20 30 40 50 60 70 80 90

Baking Crackers Flour White Bread

2.1 2.6 0.5

2.8 4.1 1.7

3.3 5.3 3.1

3.9 6.5 4.5

5.0 8.0 6.2

6.5 9.9 8.5

8.3 12.4 11.1

10.9 15.4 14.5

14.9 19.1 19.0

Leather Sole Oak, Tanned 5.0 8.5 11.2 13.6 16.0 18.3 20.6 24.0 29.2

Printing Paper – Comm. Ledger – 75% Rag

1% Ash Paper M.F. Newsprint – 24% Ash Paper White Bond Rag – 1% Ash Paper Writing – 3% Ash

2.1 2.4 3.0

3.2 3.7 4.2

4.0 4.7 5.2

4.7 5.5 6.2

6.1 6.5 7.2

7.2 7.5 8.3

8.7 8.8 9.9

10.6 10.8 11.9

13.2 14.2

Textile Cotton – Absorbent Cotton – American-cloth Cotton – Sea Isle-roving Hemp – Manila and Sisal Jute – Average Grade Linen – Dried Spun – Yarn Rayon – Celulose – Acetate – Fibre Rayon – Cupramonium – Average

4.8 2.6 2.5 2.7 3.1 3.6 0.8 4.0

9.0 3.7 3.7 4.7 5.2 5.4 1.1 5.7

12.5 4.4 4.6 6.0 6.9 6.5 1.4 6.8

15.7 5.2 5.6 7.2 8.5 7.3 1.9 7.9

18.5 5.9 6.6 8.5 10.2 8.1 2.4 9.2

20.8 6.8 7.9 9.9 12.2 8.9 3.0 10.8

22.8 8.1 9.5 11.6 14.4 9.8 3.6 12.4

24.3 10.0 11.5 13.6 17.1 11.2 4.3 14.2

25.8 14.3 14.1 15.7 20.2 13.8 5.3 10.0

Skein Rayon – Viscose Nitrocel Silk – Raw Chevennes-Skein Wool – Australian-Marino-Skein

4.0 3.2 4.7

5.7 5.5 7.0

6.8 6.9 8.9

7.9 8.0 10.8

9.2 8.9 12.8

10.8 10.2 14.9

12.4 11.9 17.2

14.2 14.3 19.9

16.0 18.8 23.4

Tobacco Cigarette 5.4 8.6 11.0 13.3 16.0 19.5 25.0 33.5 50.0

Wood Timber – Average Glue – Hide

3.0 3.4 4.4 4.8 5.9 5.8 7.6 6.6 9.3 7.6 11.3 9.0 14.0 10.7 17.5 11.8 22.0 12.5

Miscellaneous Charcoal-Steam Activated Gelatin Silica Gel Soap Starch

7.1 0.7 5.7 1.9 2.2

14.3 1.6 9.8 3.8 3.8

22.8 2.8 12.7 5.7 5.2

26.2 3.8 15.2 7.6 6.4

28.3 4.9 17.2 10.0 7.4

29.2 6.1 18.6 12.9 8.3

30.0 7.6 20.2 16.1 9.2

31.1 9.3 21.5 19.8 10.6

32.7 11.4 22.6 23.8 12.7

Page 31 of the Nortec NHTC user manual — Table 7. Design Indoor Conditions For Various Places, Products and Processes
Seite 31 · Zum Vergrößern klicken
Seite 31

Table 7. Design Indoor Conditions For Various Places, Products and Processes

Product and/or Process Temperature

%RH °F °C Abrasives Manufacturing 78 25 50 Bowling Alleys 73 – 75 23 – 24 50 – 55 Billiard Rooms 73 – 75 23 – 24 40 – 50 Bread Flour and Powdered Product Storage Fermentation (Bread Dough) Retarding of Doughs Final Proof Counterflow Cooling

60 75 85 85 – 90 80 – 85 Brewing Hop Storage Yeast Culture Room

70. 80 80 32 – 40 95 – 120 75
21. 27 27 0 – 4 35 – 49 24

50 – 60 80 Candy Chocolate Pan Supply Air Enrober Room Chocolate Cooling Tunnel Supply Air Hand Dippers Moulded Goods Cooling Chocolate Packing Room and Finished Stock Storage Centers Tempering Room Marshmallow Setting Room Grained Marshmallow (deposited in starch) Drying Gum (deposited in starch) Drying Sanded Gum Drying Gum Finished Stock Storage Sugar Pan Supply Air (engrossing) Polishing Pan Supply Air Pan Rooms Nonpareil Pan Supply Air Hard Candy Cooling Tunnel Supply Air Hard Candy Packing Hand Candy Storage Caramel Rooms

29. 32 --
2. 0 --
45. 55 25 – 30 70 – 85 45 70 – 85 50 30 – 35 40 – 45 40 15 – 25 25 – 40 65 20 – 30 40 – 50 30 – 35 20 40 – 55 35 – 40 40 40 Raw Material Storage Nuts (insect) Nuts (rancidity) Eggs Chocolate (flats) Butter Dates, Figs, etc. Corn Syrup Liquid Sugar Comfort Air Conditioners
55. 62 80 – 85 40 – 45 62 40 – 45 65 75 – 80 75 – 78 110 125 – 150 100 50 – 65 85 – 105 70 – 80 75 – 80 100 – 120 60 – 70 70 – 75 50 – 70 70 – 80
13. 17 27 – 29 4 – 7 17 4 – 7 18 24 – 27 24 – 26 43 52 – 66 38 10 – 18 29 – 41 21 – 27 24 – 27 38 – 49 16 – 21 21 – 24 10 – 21 21 – 27
65. 75 65 – 75 85 – 90 50 65 – 75 – 30 – 40 50 – 60 Ceramics Refractory Molding Room Clay Storage Decalcomania Production and Decorating room Cereal Packaging

45 34 – 38 30 65 20 40 – 45 90 – 100 75 – 80 75 – 80

7 1 – 3 -1 18 -7 4 – 7 32 – 38 24 – 27 24 – 27

50. 90 60 – 70 35 – 65 48 45 – 50 Cheese Curing Cheddar Swiss Blue Brick Limburger Camembert
110. 150 80 60 – 80 75 – 80 75 – 80
43. 66 27 16 – 27 24 – 27 24 – 27
45. 55 60 48 – 50 60 – 65 60 – 65 53 – 59
7. 13 16 9 – 10 16 – 18 16 – 18 12 – 15
85. 90 80 – 85 95 90 95 90

Relative Humidity

Page 32 of the Nortec NHTC user manual — Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)
Seite 32 · Zum Vergrößern klicken
Seite 32

Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)

%RH

°F °C

Clean Rooms – Computer Rooms Computer Room Clean Room – General Clean Room – Critical

70. 80 70 – 74 71.5 – 72.5
21. 27 21 – 23 22 – 22.5
40. 60 40 – 60 43 – 47

Distilling Grain Storage General Manufacturing Aging

60 0 – 75 65 – 72

16 16 – 24 18 – 22

35. 40 45 – 60 50 – 60

Electrical Products Coil and Transformer Winding X-ray Tube Assembly Instruments Manufacture and Laboratory Thermostat and Humidistat Assembly and Calibration Close Tolerance Assembly Meter Assembly and Test Fuse and Cutout Assembly, Capacitor Winding and Paper Storage Conductor Wrapping with Yarn Lightning Arrestor Assembly Thermal Circuit Breaker Assembly and Test Water Wheel Generators Thrust Runner Hopping Processing Selenium and Copper Oxide Plates

72 68 70 76 72 76 73 75 68 76

22 20 21 24 22 24 23 24 20 24

15 40 50 – 55 50 – 55 40 – 45 60 – 63 50 65 – 70 20 – 40 30 – 60

30. 50 30 – 40

Fruit Storage Apples Apricots Grapefruits (California) Grapefruits (Florida) Grapes (Eastern) Grapes (Western) Lemons Oranges (California) Oranges (Florida) Peaches and Nectarines Plums Specialty Citrus Fruit

30. 40 31 – 32 58 – 60 50 31 – 32 30 – 31 58 – 60 40 – 44 32 – 34 31 30 – 32 38 – 40

-1– 4 -1 – 0 14 – 16 10 -1 – 0

90 90 – 95 85 – 90 85 – 90 85 90 – 95 86 – 88 85 – 90 85 – 90 90 90 – 95 90 – 95

-1 14 – 16 4 – 7 0 – 1 -1 -1 – 0

Fur Storage 40 – 50 4 – 10 55 – 65

Gum Manufacture Rolling Stripping Breaking Wrapping

77 68 72 74 74

25 20 22 23 23

33 63 53 47 58

Hospitals Operating, Cystoscopic and Fracture Rooms Patient Rooms Intensive Care Unit Administrative and Service Areas

68. 76 75 75 70 – 80
20. 24 24 24 21 – 27

50 40 – 50 40 30 – 50

Leather Drying Storage, Winter Room Temperature

70. 120 50 – 60 21 – 49 10 – 16 75 40 – 60

Lenses (Optical) Fusing Grinding

75 80 27 27 45 80

Relative Humidity · Temperature · Product and/or Process

Page 33 of the Nortec NHTC user manual — %RH
Seite 33 · Zum Vergrößern klicken
Seite 33

Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)

Product and/or Process Temperature

%RH

°F °C

Libraries and Museums Normal Reading and Viewing Rooms Rare Manuscript Storage Vaults Art Storage Areas

70. 74 70 – 72 65 – 72
21. 23 21 – 22 17 – 22
40. 50 45 50

Matches Manufacture Drying Storage

72. 74 70 – 75 60 – 62
22. 23 21 – 24 16 – 17

Meat and Fish Beef (Fresh) Beef, Fish, Lamb and Pork (Frozen) Fish (Fresh) Lamb and Pork (Fresh)

32 –34 -10 – 0 33 – 35 32 – 34

0. 1 -23 – -18
88. 92 90 – 95 90 – 95 85 – 90
1. 3 0 – 1

Mushrooms Sweating-out Period Spawn Added Growing Period Storage

120. 140 60 – 75 48 – 60 32 – 35
49. 60 16 – 24 9 – 16 0 – 2

– Nearly Sat.

80 80 – 85

Oil PaintsPaint Spraying 60 – 90 16 – 32 80

Pharmaceuticals Manufactured Powder Storage and Packaging Area Milling Room, Table Compressing and Coating Effervescent Tablets and Powders Hypodermic Tablets Colloids Cough Drops Glandular Products Ampoule Manufacturing Gelatin Capsules and Storage Microanalysis Biological Manufacturing and Liver Extracts Serums Animal Rooms

75 70 80 76 75 76 75 – 80

24 21 27 24 – 27

35 35 20 30 30 – 50 40 5 – 10 35 – 50 35 50 35 50 50

Plastics Manufacturing Areas Thermosetting Molding Compounds Cellophane Wrapping

80 75 – 80 27 24 – 27 35 – 30 45 – 65

Plywood Hot Pressing (Resin) Cold Pressing

90 90 32 32 60 15 – 25

Printing Platemaking Lithographic Press Room Letterpress and Web Offset Press Rooms and Paper Storage Paper Storage (Multicolor Sheet Feed Lithography)

75. 80 76 – 80 76 – 80 76 – 80
24. 27 24 – 27 24 – 27 24 – 27

45 Max 43 – 47 50 5 – 8 Higher than Press Room

Rubber Dipped Goods Cementing Dipping Surgical Articles Storage Prior to Manufacture Laboratory (ASTM Standard)

80 75 – 90 60 – 75 73.4

27 24 – 32 16 – 24 23

25. 30 25 – 30 40 – 50 50

Tea Packaging 65 18 65

Relative Humidity · 50 60 50

Page 34 of the Nortec NHTC user manual — Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)
Seite 34 · Zum Vergrößern klicken
Seite 34
Page 34 of the Nortec NHTC user manual — Table 7. Design Indoor Conditions For Various Places, Products and Processes (cont)
Page 35 of the Nortec NHTC user manual — Figure 2. Psychrometric Chart
Seite 35 · Zum Vergrößern klicken
Seite 35
Nortec NHTC — Figure 2. Psychrometric Chart diagram (page 35)
Abb. 29 · Figure 2. Psychrometric Chart

Figure 2. Psychrometric Chart

Page 36 of the Nortec NHTC user manual — Table 8. Variables That Affect Absorption Distances
Seite 36 · Zum Vergrößern klicken
Seite 36

2. STEAM ABSORPTION AND DISTRIBUTION

A. VARIABLES THAT AFFECT ABSORPTION DISTANCES

(1) This manual will help in the design of a steam distribution system to provide the

optimum performance from the humidifier and absorption of steam within the duct system.

(2) Experience has shown that absorption of steam is affected primarily by the

psychrometric conditions of the air based on how much residual capacity at a given air volume and temperature exist to hold the moisture being introduced.

(3) To properly introduce steam into an air stream, five variables must be known:

(a) Temperature (°F or °C). If the air temperature varies, pick the lowest temperature.

(b) Highest humidity level before the distributor (%rh).

(c) The amount of moisture being added resulting in a change of rh in the duct or plenum (Δ %rh).

(d) Minimum velocity of the air (FPM).

(e) The size of the duct or plenum (cross section area).

(4) As a guide, Table 8 shows how each variable affects the absorption distance.

(5) Table 9 shows examples of typical absorption distances in air handling systems.

(6) Referring to Figure 3, ‘D’ can vary between 1 to 20 feet depending on the airflow’s:

(7) When (V) is 500 fpm, (T) is high (90 to 130°F) and (H) is low (10% to 30% rh) the ‘D’ will

be 1 to 2 feet. As the (H) goes up ‘D’ becomes longer. Similarly, as (T) goes down, ‘D’ goes up. High velocity also increases ‘D’ by moving the steam further down stream before it can mix. Multiple distributors will shorten the steam absorption distance.

Table 8. Variables That Affect Absorption Distances

Variables Effect On Absorption Distance

(NOTE↑ Increase ↓ Decrease

Air Temperature ↑ ↓

Air Temperature ↓ ↑

Air Humidity ↑ ↑

Air Humidity ↓ ↓

Large Increase of RH ↑

Small Increase of RH ↓

High Air Velocity (1000 fpm or above) ↑

Low air Velocity (between 100 and 500 fpm) ↓

Small Duct or Plenum (short distributor) ↑

Large Duct or Plenum (long distributor) ↓

(a) Velocity (V) · (b) Temperature (T) · (c) Humidity (H)

Page 37 of the Nortec NHTC user manual — Figure 3. Steam Distributor Location
Seite 37 · Zum Vergrößern klicken
Seite 37

Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifier

FPM °F °C % RH FT CM

Typical System (V) (T) (H) (D)

500 70 21 30 3.0 91 Air handler before coils

500 55 13 80 4.5 137 Air handler after cooling

900 70 21 30 3.5 107 Supply air duct, on cool, no heat

900 55 13 70 6.0 183 Supply air duct, on cool

1000 55 13 90 8.0 244 Supply air duct, on cool with high humidity

1000 110 43 10 2.5 76 Supply air duct, on heating with low humidity

1000 70 21 45 4.0 123 Return air duct conditions

2000 55 13 45 10.0 305 Supply air duct higher pressure system

5000 140 60 10 2.0 61 After operating heating coil

(V) = Velocity at distributor location (T) = Temperature at distributor location (D) = Absorption distance (visible steam) (H) = Humidity level after steam is absorbed

Nortec NHTC — Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifier diagram (page 37)
Abb. 30 · Table 9. Typical Absorption Distances, Single Distri…

Figure 3. Steam Distributor Location

Page 38 of the Nortec NHTC user manual — Table 10. Water (lbs/hr) Contained in 1000 CFM of Air
Seite 38 · Zum Vergrößern klicken
Seite 38

B. CALCULATING THE DOWN STREAM HUMIDITY LEVEL

(1) Table 10 indicates the amount of water that each 1000 CFM of duct air holds in pounds

of water per hour at various combinations or air temperature and relative humidity. Subtract the water vapour in the duct air before the steam distributor from the maximum allowed after the distributor. The chart indicates how many lbs/hr of water can be added to 1000 CFM of airflow.

Table 10. Water (lbs/hr) Contained in 1000 CFM of Air

°F 10% 20% 30% 40% 50% 60% 70% 80% 85%

50 3.52 7.04 10.56 14.06 17.60 21.12 24.65 26.16 29.92

55 4.19 8.38 12.57 16.76 20.95 25.14 29.33 33.52 35.62

60 4.97 9.94 14.91 19.88 24.85 29.82 34.79 39.76 42.25

65 5.85 11.74 17.61 23.48 29.35 35.22 41.09 46.96 49.73

70 6.94 13.80 20.82 27.78 34.70 41.64 48.58 55.52 58.99

75 8.10 16.20 24.30 32.40 40.50 48.60 56.70 64.80 68.85

80 9.46 18.92 28.36 37.84 47.30 56.76 66.22 75.68 80.41

85 11.03 22.08 33.09 44.12 55.15 66.18 77.21 88.24 93.75

90 12.80 25.60 38.40 51.20 64.00 76.80 89.60 102.4 108.80

95 14.81 29.62 44.43 59.24 74.05 88.86 103.67 118.48 125.89

100 17.10 34.20 51.20 68.40 85.50 102.60 119.60 136.80 145.54

(2) The following are two examples:

Example 1:

3000 CFM air handler with 60°F and 30% rh air before the steam distributor.

Calculate the maximum rate of steam addition without exceeding 80% rh in the duct.

60° & 80% = 39.76 lbs/hr

60° & 30% = 14.91 lbs/hr

24.85 lbs/hr can be added to 1000 CFM

x 3 (3000CFM)

74.55 lbs/hr can be added to 3000 CFM

If the load calculation of this system requires a 100 lbs/hr unit, then due to the above possible conditions, the project requires a modulating high limit humidistat to limit the humidifier output to a maximum of 74 lbs/hr and maintain 80% rh.

Example 2:

Humidification load is 30 lbs/hr. To avoid exceeding 80% rh in the duct, calculate the minimum allowable CFM at 55°F. Duct conditions are 55°F and 50% rh.

55° & 80% = 33.53 lbs/hr

55° & 50% = 20.95 lbs/hr

12.57 lbs/hr can be added to 1000 CFM

(30 lbs/hr ÷ 12.57) x 1000 = 2386 CFM minimum

Page 39 of the Nortec NHTC user manual — Figure 4. Condensate Drain Pan
Seite 39 · Zum Vergrößern klicken
Seite 39

NOTE

Maximum capacity of the NHTC/NHPC humidifier can be limited through the keypad.

C. CONTROL OF DUCT OR PLENUM SATURATION

(1) NORTEC always recommends the use of a high limit humidistat set at 85% relative

humidity in combination with an air-proving switch to assure air movement. Both of these controls are wired in series across the primary control terminals of the humidifiers so that should either of these conditions not be satisfied the humidifiers cannot operate.

(2) Low temperature, shallow ducts or branch ducts might require a field supplied

condensate drain pan and should be accessible to service and inspection (See Figure 4.).

(3) The most effective method of ensuring controlled absorption distances is to install a

modulating high limit humidistat. By controlling the down stream [after distributor(s)] humidity levels and modulating the humidifier’s output, one of the variables affecting absorption distance is now a constant. NORTEC recommends modulating high limit humidistats on all economizer systems, VAV, VVT, and systems, which are primarily cooling.

Nortec NHTC — C. CONTROL OF DUCT OR PLENUM SATURATION diagram (page 39)
Abb. 31

Figure 4. Condensate Drain Pan

Page 40 of the Nortec NHTC user manual — Figure 5. Proper Slope
Seite 40 · Zum Vergrößern klicken
Seite 40

3. STEAM RUNS AND CONDENSATE RETURNS

A. STEAM RUNS

(1) Steam runs between the humidifier and the distributors can be accomplished by using

flexible NORTEC steam hose or insulated copper pipe. The longer the steam run, including elbows, the lower the efficiency of the system. The more elbows and turns, the higher the losses become. The humidifier should be as close as possible to the distributor and the steam run should be as direct as possible.

(2) Guidelines for installation are:

(a) Locate humidifier as close as possible to the duct system.

(b) NORTEC steam hose should only be used on short steam runs below 10 feet.

(c) Minimize elbows and turns.

(d) Ensure that no condensate produced in the steam line will remain trapped. Steam

naturally flows upward and condensate naturally flows downward. Always slope the steam run towards the steam source at a 15° pitch no more (See Figure 5.).

(e) Oversize condensate line and steam line of long runs (consult your

representative).

(f) See material recommended for use in Table 11. To eliminate corrosion, NORTEC does not recommend the use of steel piping.

(g) Consult Table 12 and Table 13 for steam and condensate sizing guidelines when

using steam distributors.

Nortec NHTC — A. STEAM RUNS diagram (page 40)
Abb. 32
Nortec NHTC — A. STEAM RUNS diagram (page 40)
Abb. 33

Figure 5. Proper Slope

Figure 6. Drain Tee

see Fig 9 for proper P Trap design and installation

Page 41 of the Nortec NHTC user manual — OD)
Seite 41 · Zum Vergrößern klicken
Seite 41

Table 11. Steam Line Material

Steam Hose Copper Tube Stainless Steel Tube

Short run < 10 feet (3 m) yes yes yes

Long run > 10 feet (3 m) yes yes

Table 12. Recommended Material and Size for Steam Run

Steam Line Description lb/hr kg/hr ft m

Load Steam Run Steam Line

0-30 0-13 0-10 0-3 Copper Tube ¾" MED-L

Tubing (f" OD)

0-30 0-13 10 + 3 + Copper Tube 1"MED-L Tubing (1c" OD)

0-30 0-13 0-10 0-3 Stainless Steel

f" Tube x 0.049" thick.

0-30 0-13 10 + 3 + Stainless Steel

1c"Tube x 0.049” thick.

30-100 13-45 0-20 0-6 Copper Tube 1½" MED-L Tubing (1e"

OD)

30-100 13-45 20 + 6 + Copper Tube 2"MED-L Tubing (2c"OD)

30-100 13-45 0-20 0-6 Stainless Steel

1¾" Tube x 0.065" thick.

30-100 13-45 20 + 6 + Stainless Steel

2" Tube x 0.065" thick.

NOTE: Options shown in a bold-italic font require that reducers be used at both ends. These extra large sizes are to allow for better condensation removal in long steam runs. These sizes do not permit the use of hose couplings to connect either humidifier or distributors. NOTE: Insulate all copper or stainless steel steam lines with minimum one inch high temperature insulation.

Table 13. Recommended Condensate Line at Distributor(s)

Dispersion Method Condensate Hose Copper Tube Stainless Steel Tube

1 x Steam Distributor d" NORTEC 1328840 ¼" MED-L Tubing (d"

d" Tube 0.049" thick.

OD)

3 x Steam Distributor* d" NORTEC 1328840 ½" MED-L Tubing

e" Tube 0.049" thick

(f" OD)

Show 5 more labels / short text on this page
Material · Tube · Tube · Tube · Tube
Page 42 of the Nortec NHTC user manual — NOTE
Seite 42 · Zum Vergrößern klicken
Seite 42

(3) NORTEC recommends the use of insulated hard copper steam lines on distances of

more than 10 feet and no more than 3 elbows (90⊃). The use of flexible steam hose on runs of more than 10 feet can reduce these recommended distances in Table 14 by as much as 25%. Steam hose can crimp and cause back pressure.

Table 14. Maximum Recommended Length of Steam Runs

Unit Size Steam Output Distance Possible Losses

NH-005 5 lbs/hr 8 feet 1.0 lbs/hr

NH-010 10 lbs/hr 15 feet 1.5 lbs/hr

NH-020 20 lbs/hr 20 feet * 2.0 lbs/hr

NH-030 30 lbs/hr 25 feet * 2.5 lbs/hr

NH-050 50 lbs/hr 40 feet ** 4.0 lbs/hr

NH-075 75 lbs/hr 50 feet ** 5.0 to 10.0 lbs/hr

NH-100 100 lbs/hr 50 feet ** 5.0 to 10.0 lbs/hr

NH-150 150 lbs/hr 50 feet/cylinder ** 5.0 to 10.0 lbs/hr

NH-200 200 lbs/hr 50 feet/cylinder ** 5.0 to 10.0 lbs/hr

* Use one inch copper steam supply for longer runs. ** Use two inch copper steam supply for longer runs.

(4) Steam lines should slope upwards from the humidifier to the steam distributor. (See

Figure 7.)

(5) Flexible steam hose, if used, must be supported to avoid crimps, bends, and sags.

(Please consult local agent if proper slopes are not available.)

(6) If the steam supply line must be routed below the humidifier location, a condensate trap

‘tee’ will be required to prevent blockage at the low point in the steam line. Run the condensate hose to the nearest floor drain after trapping. (See Figure 8.)

(7) Long steam runs with improper slopes can produce spitting at the distributor because

the steam is travelling at a high velocity and will push condensate out the distributor. If a slope of 2" for every 12" of steam run cannot be achieved, then condensate must be removed before the distributor. (See Figure 4.)

B. CONDENSATE RETURN

(1) Each steam distributor has a built-in condensate return. (See Figure 9.) Flexible

condensate return hose (available from NORTEC) is recommended for routing condensate back into the humidifier’s fill cup, or to a drain. A short length of d" OD copper tubing is supplied by NORTEC when routing condensate hose back to the fill cup. Similarly, a short length of d" condensate hose is supplied to serve as a flexible coupling with field-supplied copper condensate line. Long condensate runs should be drained to a floor drain to prevent excessive condensate water from entering the cylinder.

NOTE

Excessively long steam runs (over 20 feet) may require the use of ½" OD condensate return lines – supplied by others.

Page 43 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 43 · Zum Vergrößern klicken
Seite 43

(2) Use vertical condensate leg of

Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 43)
Abb. 34 · Figure 8. Condensate Tee At Any Low Point

distributor only. Do not over-tighten clamp.

(3) Drip stations on steam mains must

be located at all low points in the system, at each elevation change and or directional change.

(4) Horizontal runs of steam must

have a 2" rise per foot (10°) when flow is going away from drip station and the steam run is to fall ½" per foot (2°) when flow is going towards drip station.

(5) In a horizontal run of the steam

main, drip stations must be located at regular intervals of 20 feet.

(6) The drip station itself is a section

of piping connected to the bottom of the main. A full size tee must be used to create a drip station to allow the condensate to fall in the drip station. Figure 7. Steam Line Connection

Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 43)
Abb. 35 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 43)
Abb. 36 · Figure 8. Condensate Tee At Any Low Point

Figure 8. Condensate Tee At Any Low Point

Figure 9. Trap To Prevent Steam In

In Steam Line

Condensate Line

Page 44 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 44 · Zum Vergrößern klicken
Seite 44

(7) Vertical drop of the drip station should be 1.5 times the diameter of the steam main but

no less then 12".

(8) Install the P trap at the botom of the drip station. The P trap height is to be a minimum

of 6 inches or 2 “ greater than the static pressure in the duct.

(9) All distributors must be individually trapped.

Page 45 of the Nortec NHTC user manual — Figure 10. Levelling the Distributor
Seite 45 · Zum Vergrößern klicken
Seite 45

4. STEAM DISTRIBUTORS (ASD, BSD, CSD)

A. STEAM DISTRIBUTORS

(1) NORTEC’s steam distributors, in use for over twenty years, are a proven design to suit

applications for the introduction of atmospheric steam.

(2) Features and benefits of steam distributors are:

(a) Expanded diameter of tube to reduce steam velocity and the potential for

condensate carryover into the duct.

(b) Positive removal of condensate.

(c) Lower mass of metal (stainless steel), which reduces ‘radiator effect and condensate’ and results in higher efficiency of humidifier output while reducing condensate formation.

(d) Designed specifically for atmospheric steam generation.

(e) Modular so that the exact quantity of distributors can be configured to meet

specific application requirements. This reduces system complexity and installation costs.

B. DISTRIBUTOR CHARACTERISTICS

(1) NORTEC steam distributors are constructed of stainless steel and include in low point

condensate return to prevent the condensate from collecting in the steam distributor. This enables entrained condensate to settle to the bottom of the steam distributor where it is removed by the condensate return. These features allow the NORTEC steam distributors to be installed level in the duct, thereby utilizing the full available width of the duct. (See Figure 10.)

Nortec NHTC — B. DISTRIBUTOR CHARACTERISTICS diagram (page 45)
Abb. 37

Figure 10. Levelling the Distributor

Page 46 of the Nortec NHTC user manual — Installation – Minimum Clearance
Seite 46 · Zum Vergrößern klicken
Seite 46

(2) Ensure the total capacity of the humidifier is not higher than the allowable maximum

steam capacity of the following distributors:

(a) ASD25 lbs/hr (9 kg/hr)
(b) BSD35 lbs/hr (13 kg/hr)
(c) CSD115 lbs/hr (45 kg/hr)

C. DISTRIBUTOR LOCATIONS AND MOUNTING

(1) NORTEC distributors can be mounted in air handlers, supply air ducts or return air

ducts. Return air ducts should only be considered if all of the return air enters the building again and is not exhausted by the air handling device. Distributors should be mounted center or low within the duct or plenum. (See Figure 11.) Laminar airflow is best. Down stream obstruction must be considered. The non-absorbed steam may affect devices like smoke detectors down stream. Total steam absorption must be accomplished before filters and silencers.

(2) Distributors come complete with a mounting plate. (See Figure 12.) Most ducts and

plenums are rigid enough to support the distributor.

(3) Longer distributors (more than 36") and distributors mounted on lighter gage sheet

metal which cannot support the distributor level in the duct will need to be supported on the end. (See Figure 10.)

D. MULTIPLE DISTRIBUTOR APPLICATIONS

(1) The use of multiple steam distributors can reduce the absorption distance in most

situations. Distributors can be manifolded together to create a grid to achieve shorter absorption distances. (Consult agent and/or see Nomogram Figure 13.

Nortec NHTC — D. MULTIPLE DISTRIBUTOR APPLICATIONS diagram (page 46)
Abb. 38

CAUTION

THESE INSTALLATION GUIDELINES APPLY FOR DUCT VELOCITIES UNDER 2000 FT/ MIN (610 M/MIN), PLEASE CONSULT FACTORY FOR HIGHER VELOCITIES

CAUTION

PLEASE MAKE SURE NO OBSTACLES (ELBOW, FILTER, OR DIFFUSER) ARE LOCATED AFTER THE DISTRIBUTOR IN THE DIRECTION OF THE AIRFLOW CLOSER THAN THE ABORPTION DISTANCE CALCULATED FOR YOUR APPLICATION.

CAUTION

FOR APPLICATIONS WITH HIGH STATIC PRESSURES PLEASE CONSULT FACTORY Figure 11. Single Steam Distributor

Installation – Minimum Clearance

Page 47 of the Nortec NHTC user manual — Figure 13. Humidification Distance Nomogram
Seite 47 · Zum Vergrößern klicken
Seite 47
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 47)
Abb. 39 · Figure 8. Condensate Tee At Any Low Point

Figure 12. Cutting Duct For Mounting

Nortec NHTC — Figure 12. Cutting Duct For Mounting diagram (page 47)
Abb. 40 · Figure 12. Cutting Duct For Mounting

Figure 13. Humidification Distance Nomogram

Page 48 of the Nortec NHTC user manual — Figure 14. Best Location for Multiple Steam
Seite 48 · Zum Vergrößern klicken
Seite 48

CAUTION

UNLESS YOU KNOW THE EXACT ABORPTION DISTANCE REQUIRED FOR THE STEAM ABSORPTION INTO THE AIR STREAM, THE DISTRIBUTOR SHOULD BE LOCATED AT LEAST 8-10 FT (2-3 M) AWAY FROM ANY OBSTACLE IT MAY CONDENSE ON (ELBOW, DIFFUSER, FILTER, ETC.)

(2) Duct vertical clearance requirements for standard steam distributors are as follows:

(a) ASD - 8 in. vertical duct height for 1st ASD - 5.5 in. additional duct height for each additional ASD = ROUNDDOWN (‘DuctHeight’ - 8")/5.5) + 1

(b) BSD - 10 in. vertical duct height for 1st BSD - 6.375 in. additional duct height for each additional BSD = ROUNDDOWN (‘DuctHeight’ - 10")/6.375) + 1

(c) CDS - 14 in. vertical duct height for 1st CSD - 9 in. additional duct height for each additional CSD = ROUNDDOWN (‘DuctHeight’ - 14")/9) + 1

NOTE

These requirements apply to vertical arrangements of multiple distributors ONLY. Diagonal arrangements utilize an alternative method.

E. LOCATION OF STEAM DISTRIBUTORS WITHIN AN AIR HANDLER

(1) Humidify after the heating

coil (H/C) so that absorption will occur in the 3 to 4 feet before the cooling coil (C/C). If steam carries over and condenses on the coil, any excess water will be drained away. There is little chance of condensation on the blower, blower motor, or fan isolation components, especially if you use a modulating high limit humidistat. All steam distributors should be 8" from the H/C and evenly spaced. If wetting is a problem, add more steam distributors. (See Nomogram Figure 13 and Figure 14).

Nortec NHTC — E. LOCATION OF STEAM DISTRIBUTORS WITHIN AN AIR HANDLER diagram (page 48)
Abb. 41

F. DISTRIBUTOR ABSORPTION DISTANCE

(1) The water vapor discharged from

the steam distributor must be adequately mixed with air to prevent condensation on downstream components. The nomogram in figure 13 will

Figure 14. Best Location for Multiple Steam

Distributors in AHU

Page 49 of the Nortec NHTC user manual — Figure 15. Roof Top Units 2-20 Tons –
Seite 49 · Zum Vergrößern klicken
Seite 49

determine the number of steam distributors that must be use for short saturation distances.

(2) If the ‘Saturation Distance’ for one steam distributor is not sufficient, add more steam

distributors until the minimum saturation distance is attained. (See Figure 13.)

(3) To determine the number of distributors required, complete the following list:

(a) Air humidity after humidification %rh. (A high limit humidistat should be set

at 80 – 85% to prevent wetting of ducts.)

(b) Air temperature before humidification

(c) Air velocity in duct ft/min.

(d) Maximum steam mass flow lbs/hr.

(e) Active zone H of steam distributor in. (See Figure 13.)

NOTE

The manufacturer recommends the appropriate distance modification factors when filters or humidification sensors are installed downstream. For applications that are outside of the Nomogram’s range, please consult a NORTEC representative.

G. TYPICAL APPLICATIONS

(1) Representations of typical applications are found in Figure 15 and Figure 16.

H. DISTRIBUTOR DIMENSIONS

(1) Distributor dimensions for the various distributor models can be found in

Chapter 10-30.

Nortec NHTC — H. DISTRIBUTOR DIMENSIONS diagram (page 49)
Abb. 42
Nortec NHTC — H. DISTRIBUTOR DIMENSIONS diagram (page 49)
Abb. 43

Figure 15. Roof Top Units 2-20 Tons –

Figure 16. Small Units On Residential

Typical Location

Furnaces

Page 50 of the Nortec NHTC user manual — Figure 17. SAM-e Tubes
Seite 50 · Zum Vergrößern klicken
Seite 50

5. SHORT ABSORPTION MANIFOLD (SAM-e)

A. GENERAL

(1) NORTEC’s best performing steam absorption system for use in Air Handling Units and

duct systems where short steam absorption distance is critical.

(2) The SAM-e, Figure 17, distributes clean steam, precisely controlled, uniformly into the

entire air stream, void of any condensate spray. Steam distribution takes place via distributor tubes with integrated nozzles. The steam is kept dry as condensate is drained through the main header.

(3) The stainless steel distribution tubes are typically mounted vertically but can also be

mounted horizontally (10° slope) for vertical airflow applications. The distribution tubes come equipped with evenly spaced stainless steel nozzles providing optimum steam distribution, over the entire length of the tube.

(4) The nozzles extend into the center of the distribution tube ensuring only condensate

free steam is released. (See Figure 18.) Condensate drains out of the distribution tubes, through the header, eliminating the need for jacketed tubes. A permanent bond between the nozzle and distribution tube is made when the nozzle is pressed into the tube. The nozzles and tubes have the same thermal expansion characteristics guaranteeing a permanent union. The specifically sized orifices ensure consistent output from each nozzle.

Nortec NHTC — A. GENERAL diagram (page 50)
Abb. 44
Nortec NHTC — A. GENERAL diagram (page 50)
Abb. 45

Figure 17. SAM-e Tubes

Figure 18. Cross-Section of Distributor Pipe

Page 51 of the Nortec NHTC user manual — B. DETERMINING THE STEAM ABSORPTION DISTANCE
Seite 51 · Zum Vergrößern klicken
Seite 51

(5) The features of the short absorption manifold are:

(a) Inlets/Outlets located on same side, one access point required.

(b) All stainless steel distributors and nozzles ensure permanent bond.

(c) Stainless steel header with rubber grommet seals for easy installation of distribution tubes.

(d) Adjustable mounting frame available for quick and easy installation.

(e) Available with 3", 6", 9", or 12" center-to-center distributor spacing.

(f) Atmospheric steam source.

(g) Two year limited warranty.

B. DETERMINING THE STEAM ABSORPTION DISTANCE

NOTE

Visit www.humidity.com to download our Humidification Engineering & Loadsizing Program (H.E.L.P.) to help you calculate the absorption distance.

(1) Injecting steam into the air requires a certain amount of time before the steam is

absorbed completely.

(2) In a moving air stream, this time results in the steam moving a fixed distance from the

manifold before it is fully absorbed.

(3) Knowing the absorption distance will ensure that steam will not condense on any

critical components following the steam distribution area.

(4) The system should be designed to eliminate the possibility of wetting internal

components by positioning the manifold in the optimum location and by keeping the absorption distance to a minimum.

(5) The absorption distance can be calculated using the Z ratio. The Z ratio and the

following method may be used as a guide to calculate the absorption in various air handlers, and ducts with different conditions. It can be calculated as follows:

(RHah - RHbh) Z = (100 - RHbh) RHah = Percentage of relative humidity after humidification. RHbh = Percentage of relative humidity before humidification.

Example 1:

  • 55°F (12.8°C)/ 12% RH - Conditions before humidification.
  • 20 000 CFM (33 980 m 3 /h)
  • 400 lbs/hr (181 kg/hr) load

Using the H.E.L.P. Software or a psychrometric chart you can find that the humidity conditions after adding 400 lbs/hr (181 kg/h) of steam, are 55°F (12.8°C) 61% rh.

Thus giving:

RHbh = 12%

RHah = 61%

Z= (61 - 12) / (100 - 12) = 0.56

Page 52 of the Nortec NHTC user manual — D. CONDENSATE LOSSES
Seite 52 · Zum Vergrößern klicken
Seite 52

(6) Absorption Distances:

3" centers = 7" (18 cm)

6" centers = 9" (23 cm)

9" centers = 12" (31 cm)

12" centers = 18" (46 cm)

(7) Reference Figures 19, 20, 21 and 22 to determine the center-to-center spacing

required.

NOTES

1. The absorption distance data is based on 55°F (13°C) minimum temperature before humidification.
2. Data is based on velocities between 200 fpm (101 cm/s) and 2500 fpm (1270 cm/s).
3. Absorption distance: This is the distance between the SAM-e and the first obstruction (coil, elbow, damper, etc.) and the first obstruction steam may hit. Traces of steam may pass this obstruction, but will not condense, leaving obstructions dry.
4. If any of the duct AHU conditions are changed, the absorption distance may change due to increase or decrease in duct temperatures, amount of fresh air, various outside conditions, set point requirements, etc. If this occurs, re-calculate the absorption distance, and determine if the SAM-e needs to be modified or relocated.

C. STATIC AIR PRESSURE

(1) Table 15 shows the static pressure loss created by a SAM-e in various velocities.

Table 15. Air Pressure Loss in AHU/Duct

Air Pressure Loss (inches of water column)

3" (7.6 cm) 6" (15.2 cm) 9" (22.7 cm) 12" (30.5 cm)

500 (255) 0.01 (0.02) 0.01 (0.02) No measurable data

750 (383) 0.03 (0.08) 0.01 (0.02)

1000 (510) 0.05 (0.013) 0.02 (0.05)

1250 (638) 0.07 (0.18) 0.03 (0.08)

1500 (765) 0.09 (0.23) 0.04 (0.10) 0.01 0.01

1750 (893) 0.10 (0.25) 0.06 (0.15) 0.01 0.01

2000 (1020) 0.12 (0.30) 0.08 (0.20) 0.01 0.01

D. CONDENSATE LOSSES

(1) The SAM-e will condense some of the steam generated by the NORTEC humidifiers.

To compensate for this loss in capacity, we must increase the calculated humidification load accordingly. Refer to Table 16.

Air Velocity fpm · (cm/s) · SAM-e Tube Spacing

Page 53 of the Nortec NHTC user manual — Figure 21. Absorption Distance – 9" Centers
Seite 53 · Zum Vergrößern klicken
Seite 53
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 53)
Abb. 46 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 53)
Abb. 47 · Figure 8. Condensate Tee At Any Low Point

Figure 19. Absorption Distance – 3" Centers

Figure 20. Absorption Distance – 6" Centers

Nortec NHTC — Figure 19. Absorption Distance – 3" Centers diagram (page 53)
Abb. 48 · Figure 19. Absorption Distance – 3" Centers
Nortec NHTC — Figure 19. Absorption Distance – 3" Centers diagram (page 53)
Abb. 49 · Figure 19. Absorption Distance – 3" Centers

Figure 21. Absorption Distance – 9" Centers

Figure 22. Absorption Distance –

12" Centers

Page 54 of the Nortec NHTC user manual — H. SAM-e STEAM TUBE SELECTION
Seite 54 · Zum Vergrößern klicken
Seite 54

(2) NORTEC recommends the installation of a condensate drain on the steam inlet run

prior to entering the SAM-e.

Table 16. Condensate Loss

Condensate Losses (% of Maximum Capacity)

Air Velocity fpm (cm/s)

55°F 70°F

500 (255) 15% 12%

1000 (510) 20% 15%

E. CORRECT CHOICE OF PRODUCT APPLICATIONS (WITHIN SAM-e)

(1) The SAM-e has been designed exclusively for use in building ventilation duct systems,

where manufacturing, processing and hi-tech activities are conducted. Applications that do not conform to the design parameters are not recommended and will be at the user’s own risk. NORTEC produces a wide range of different humidification systems to suit virtually all normal applications, and will be happy to recommend the most appropriate system to suit each particular requirements.

F. SAM-e DIMENSIONS

(1) Dimensions for the SAM-e and mini SAM-e can be found in Figure 6 and Figure 7 in

Chapter 10-30.

G. SAM-e HEADER SELECTION

(1) NORTEC offers different ranges of manifolds to cover capacities and duct sizes. The

absorption distance and capacity required will determine the center to center spacing between each steam tube on the header. There are four options: 3" (7.6 cm), 6" (15.2 cm), 9" (22.9 cm) or 12" (30.5 cm). The smaller the spacing, the more tubes the header can accommodate, thus giving a better absorption distance and greater capacity. (See Tables 17 to 20.)

(2) The header remains the same for in-duct or outside duct mounting, for atmospheric

steam, and for vertical or horizontal flow applications. (See Figure 23.)

(3) Atmospheric manifolds with a capacity over 801 lbs/hr (362 kg/hr) will include a second

steam inlet on the header. Consult factory submittal drawings for specific details.

(4) Select the header part number associated with your duct or air handling unit’s width.

For example, if the duct width is 80" (198.11 cm), select part number 150-3279 for 3" (7.6 cm) center-to-center spacing.

H. SAM-e STEAM TUBE SELECTION

(1) Constructed of 1.5" (3.81 cm) OD 304 stainless steel tubing, the steam tubes can

accommodate duct heights between 18" (45.72 cm) - 144" (365.76 cm) for in-duct header mounting. For smaller duct applications, a mini SAM-e can accommodate sizes starting at 12" (30.5 cm) wide x 8" (20.3 cm) high. (See Figure 20.) Each steam tube has a different amount of stainless steel nozzles to evenly disperse steam into the duct or air handling unit. The nozzles take the steam from the center of the tube, eliminating any need for jacket heating, and a temperature switch. All the accumulating condensate is drained vertically down to the main header, and then out the condensate drain. NORTEC’s unique ‘slip in’ installation method makes for a very quick and effortless assembly. (See Figure 24.)

Page 55 of the Nortec NHTC user manual — Figure 24. SAM-e Tubes
Seite 55 · Zum Vergrößern klicken
Seite 55

(2) There is a selection of four types of

Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 55)
Abb. 50 · Figure 8. Condensate Tee At Any Low Point

steam tubes. Each are capable of distributing different capacities. To select the steam tube for your application refer to Table 17.

Type A 15 lbs/hr (7 kg/hr) Type B 35 lbs/hr (16 kg/hr) Type B+ 55 lbs/hr (25 kg/hr) Type C 75 lbs/hr (34 kg/hr)

(3) The humidifiers maximum capacity

and SAM-e header will determine the steam tube type required. The selected header will determine how many steam tubes are required, refer to Tables 18, 19, 20 and 21. Remember to calculate your condensate losses.

Figure 23. SAM-e Header

Nortec NHTC — Figure 23. SAM-e Header diagram (page 55)
Abb. 51 · Figure 23. SAM-e Header
Nortec NHTC — Figure 23. SAM-e Header diagram (page 55)
Abb. 52 · Figure 23. SAM-e Header

Figure 24. SAM-e Tubes

Figure 25. Steam Inlet

Page 56 of the Nortec NHTC user manual — Table 17. SAM-e Tube Matrix
Seite 56 · Zum Vergrößern klicken
Seite 56

I. SAM-e STEAM INLET CONFIGURATION SELECTION

(1) Atmospheric Steam (NH, GS, SE)

(a) The steam inlet, Figure 25, is determined by the selected humidifier. Refer to

submittals, Chapter 10-30 to determine the size of steam outlet required.

(b) For a typical SAM-e installation, see Figure 26.

J. MINI SAM-e

(1) For the mini SAM-e installation, refer to Tables 18, 19, 20 and 21 for headers, tubes

and inlet configuration.

Table 17. SAM-e Tube Matrix

*In-Duct Height in. (cm)

TYPE A 15 lbs/hr (7 kg/hr)

TYPE B 35 lbs/hr (16 kg/hr)

TYPE B+ 55 lbs/hr (25 kg/hr)

TYPE C 75 lbs/hr (34 kg/hr)

in. (cm)

18 (45.7) 1503388 N/A N/A N/A 5.5 (14.0) 1504697 1504697

Nortec NHTC — Table 17. SAM-e Tube Matrix diagram (page 56)
Abb. 53 · Table 17. SAM-e Tube Matrix

24 (61.0) 1503389 1503411 N/A N/A 11.5 (29.2) 1503469 30 (76.2) 1503390 1503412 1509391 N/A 17.5 (44.5) 1503469 36 (91.4) 1503391 1503413 1509392 1503440 23.5 (59.7)

1503470 42 (106.7) 1503392 1503414 1509393 1503441 29.5 (74.9)

1503470 48 (121.9) 1503393 1503415 1509394 1503442 35.5 (90.2)

54 (137.2) 1503394 1503416 1509395 1503443 41.5 (105.4)

60 (152.4) 1503395 1503417 1509396 1503444 47.5 (120.7)

66 (167.6) 1503396 1503418 1509397 1503445 53.5 (136.9)

72 (182.9) 1503397 1503419 1509398 1503446 59.5 (151.1)

78 (198.1) 1503398 1503420 1509399 1503447 65.5 (166.4)

84 (213.4) 1503399 1503421 1509400 1503448 71.5 (181.5)

90 (228.6) 1503400 1503422 1509401 1503449 77.5 (196.9)

96 (243.8) 1503401 1503423 1509402 1503450 83.5 (212.1)

102 (259.1) 1503402 1503424 1509403 1503451 89.5 (227.3)

108 (274.3) 1503403 1503425 1509404 1503452 95.5 (242.6)

114 (289.6) 1503404 1503426 1509405 1503453 101.5 (257.8)

120 (304.8) 1503405 1503427 1509406 1503454 107.5 (273.1)

126 (320.0) 1503406 1503428 1509407 1503455 113.5 (288.3)

132 (335.3) 1503407 1503429 1509408 1503456 119.5 (303.5)

138 (350.5) 1503408 1503430 1509409 1503457 125.5 (318.8)

144 (365.8) 1503409 1503431 1509410 1503458 131.5 (334.0)

Show 11 more labels / short text on this page
Outside- · In-duct Optional Mounting · ‘L’ Dimension · Duct Optional Mounting · Steam Tube Profile · Frame · Frame · 1503471 · 1503471 · 1503472 · 1503472
Page 57 of the Nortec NHTC user manual — 1¾" OD 1509837
Seite 57 · Zum Vergrößern klicken
Seite 57

Table 18. Mini SAM-e Headers – 3"

Maximum Capacity Atmospheric lbs/hr (kg/hr)

in. (cm) Steam Tubes Qty Header Part Number

MA MB MC

12 (30.5) 3 1509811 30 (14) 60 (27) 90 (41)

18 (45.7) 5 1509812 50 (23) 100 (45) 150 (68)

24 (60.9) 7 1509813 70 (32) 140 (64) 210 (95)

Table 19. Mini SAM-e Headers – 6"

Maximum Capacity Atmospheric lbs/hr (kg/hr)

in. (cm) Steam Tubes Qty Header Part Number

MA MB MC

12 (30.5) 2 1509814 20 (9) 40 (18) 60 (27)

18 (45.7) 3 1509832 30 (14) 60 (27) 90 (41)

24 (60.9) 4 1509833 40 (18) 80 (36) 120 (54)

Table 20. Mini SAM-e Tubes

*In-Duct Height in. (cm)

TYPE MA

TYPE MB

TYPE MC

10 lbs/hr (25 kg/hr)

20 lbs/hr (9 kg/hr)

30 lbs/hr (14 kg/hr)

in. (cm) Steam Tube Profile

8 (20.3) 1509788 N/A N/A

4½" (11.4)

Nortec NHTC — 8 (20.3) 1509788 N/A N/A diagram (page 57)
Abb. 54

10 (25.4) 1509789 N/A N/A 6½" (16.5)

12 (30.5) 1509790 1509797 1509804 8½" (21.6)

14 (36.6) 1509791 1509798 1509805 10½" (26.7)

16 (40.6) 1509792 1509799 1509806 12½" (31.8)

18 (45.7) 1509793 1509800 1509807 14½" (36.8)

20 (50.8) 1509794 1509801 1509808 16½" (41.9)

22 (55.9) 1509795 1509802 1509809 18½" (47.0)

24 (60.0) 1509796 1509803 1509810 20½" (52.1)

Table 21. Mini Inlet Configurations – For Atmospheric Steam Unit

SAM-e Steam Inlet Part Number

f" OD 1509839

1¾" OD 1509837

2 X 1¾" OD 1509838

Show 6 more labels / short text on this page
Duct Width · Duct Width · In-duct Optional Mounting · ‘L’ Dimension · Frame · Not Required
Page 58 of the Nortec NHTC user manual — Figure 26. Typical SAM-e Installation for Atmospheric Steam Applications
Seite 58 · Zum Vergrößern klicken
Seite 58
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 58)
Abb. 55 · Figure 8. Condensate Tee At Any Low Point

Figure 26. Typical SAM-e Installation for Atmospheric Steam Applications

Page 59 of the Nortec NHTC user manual — Figure 27. NH Series Humidifier With
Seite 59 · Zum Vergrößern klicken
Seite 59

6. BLOWER PACKS (BOBP, RMBP)

WARNING

STEAM DISTRIBUTOR ON THE BUILT-ON AND REMOTE BLOWER PACKS HAVE A HOT SURFACE THAT COULD RESULT IN BURNS IF TOUCHED. NORTEC RECOMMENDS MOUNTING AT LEAST 8 FEET ABOVE THE FLOOR.

A. BLOWER PACKS

(1) Optional blower packs are used to distribute steam to localized areas such as computer

rooms or in areas that do not have a built-in air distribution system.

(2) Blower packs are available integrally mounted on humidifier BOBP, (See Figure 27.) or

detached and field-piped and wired to humidifier RMBP. (See Figure 28.)

(3) Blower packs consist of a matching powder coated steel cabinet containing: three axial

blowers with finger guards powered by 120 VAC or line voltage humidifiers, with built-in multi-tap transformer (when necessary), fuse, high temperature plastic distributor with stainless steel lid, horizontal and vertical adjustment knobs for directional control, built- in thermostat to activate blowers, speed control rocker switch and safety loop relay.

(4) Refer to Table 22 for ceiling and frontal clearances required for blower packs.

Dimensions apply to both built-on and remote-mounted versions of blower packs.

(5) Mount remote blower pack(s) using factory supplied wall mounting bracket with

clearances as recommended in Table 22.

Nortec NHTC — A. BLOWER PACKS diagram (page 59)
Abb. 56
Nortec NHTC — A. BLOWER PACKS diagram (page 59)
Abb. 57

Figure 27. NH Series Humidifier With

Figure 28. NH Series Remote Mounted

Built-On Blower Pack

Blower Pack

Page 60 of the Nortec NHTC user manual — Table 22. Ceiling and Frontal Clearances for Blower Packs
Seite 60 · Zum Vergrößern klicken
Seite 60

Table 22. Ceiling and Frontal Clearances for Blower Packs

NH Series Model Minimum Number Of

in. (cm)

in. (cm)

005 1 18 (45) 30 (76)

010 1 18 (45) 30 (76)

020 1 18(45) 36 (91)

030 1 18 (45) 72 (183)

050 1 36 (91) 84 (213)

075 1 42 (106) 144 (366)

100 1 48 (122) 156 (396)

150 2* 42 (106) 144 (396)

200 2* 48 (122) 156 (396)

Minimum Ceiling Clearance · Minimum Front Clearance · Blower Packs

Page 61 of the Nortec NHTC user manual — C. MODULATING CONTROLS
Seite 61 · Zum Vergrößern klicken
Seite 61

7. CONTROLS

A. GENERAL

(1) NORTEC humidifiers all accept on/off controls for their security loop. Many NORTEC

humidifiers can also accept modulating or transducer signals for control (See the features section for each specific model).

CAUTION

REGARDLESS OF SELECTING ON/OFF OR MODULATING CONTROL METHOD, NORTEC HUMIDIFIERS MUST HAVE CLOSED CIRCUIT ACROSS ITS ON/OFF SECURITY LOOP CONTROL TERMINAL TO OPERATE. NORTEC HIGHLY RECOMMENDS THE USE OF A HIGH LIMIT HUMIDISTAT AND AN AIR PROVING SWITCH IN SERIES FOR THIS FUNCTION.

B. ON/OFF CONTROLS

(1) On/Off controls are used in all NORTEC humidifier security loops. The digital

humidistat can also be used as a space humidity controller. These controls include:

(a) Air Proving Switch – duct mounted, pressure differential switch, adjustable set

point from 0.07 IWC to 12.0 IWC, good for positive, negative or differential pressure applications, stops humidifier if duct air pressure is not sensed. Turns humidifier off if air handler fails.

(b) Duct Mounted Digital Humidistat – control or high limit, adjustable set point from

15-90% rh with accuracy fixed at ±3% at 25°C, operating range of 0-95% rh, closes on humidity drop for control and opens on rise for high limit duct application.

(c) Wall Mounted Digital Humidistat – control or high limit, adjustable set point from 15-90% rh with accuracy fixed at ±3% at 25°C, operating range of 0-95% rh, closes on humidity drop for control and opens on rise for high limit application.

(d) On/Off Controls Supplied by Others – Can be used as long as they have a dry set

of contacts capable of passing a 24-VAC, 2-A maximum signal.

C. MODULATING CONTROLS

(1) Modulating Controls are used to send a modulating demand signal to the NORTEC

humidifier. Different models can accept different signals (see features section for each specific model) NORTEC supplied controllers send a 0-10 VDC demand signal. This signal can be used as a control and in some models can also be used as a modulating high limit. These controls include:

(a) Wall Mounted Digital Humidistat with Integrated Sensor – control or high limit,

adjustable set point from 15-90% rh with accuracy fixed at ±3% at 25°C, outputs a 0-10 VDC signal.

(b) Wall Mounted Digital Humidistat Without Sensor – control or high limit, adjustable

set point from 15-90% rh with accuracy fixed at ±3% at 25°C, outputs a 0-10 VDC signal. Requires a remote transducer sensor supplying a 2-10 VDC signal.

(c) Duct Mounted Digital Humidistat With Sensor – This package comes with both a remote sensor and a wall mounted controller without sensor. Control or high limit, adjustable set point from 15-90% rh with accuracy fixed at ±3% at 25°C, outputs a 0-10 VDC signal.

Page 62 of the Nortec NHTC user manual — Figure 29. Set Point Versus Outdoor Temperature
Seite 62 · Zum Vergrößern klicken
Seite 62

(d) Modulating Demand Signal Supplied by Others – A signal that is a linear demand

signal that rises on need for humidity can be used in conjunction with NORTEC humidifiers. See features section for a list of which models can accept which signal)

D. OUTDOOR TEMPERATURE SETBACK

(1) The outdoor temperature setback sensor is used to prevent condensation on windows

or other surfaces that are adjacent to outdoor air. This sensor can be used in conjunction with the NORTEC controls mentioned above (both the on/off and modulating demand signal controllers) The sensor allows the controller to override the set point to prevent the humidifier from humidifying when condensation could be possible. (See Figure 29.) Locate the temperature sensor near the fresh air intake. This will ensure accurate representation of the outdoor air temperature.

E. TRANSDUCER SENSORS

(1) Transducer Sensors are signals sent back to either a controller or back to the

humidifier. Limited models can accept a direct transducer signal. (See features section for each specific model) The sensors include:

(a) Wall Mounted Humidity Transducer – Sensor, output of 2-10 VDC, range of 0 to

95% rh.

(b) Duct Mounted Humidity Transducer – Sensor, output of 2-10 VDC, range of 0 to

95% rh.

(c) Transducer Sensor By Others – Humidity sensors that rise linearly with the sensed rh in the room.

Nortec NHTC — E. TRANSDUCER SENSORS diagram (page 62)
Abb. 58

Figure 29. Set Point Versus Outdoor Temperature

Page 63 of the Nortec NHTC user manual — G. NORTEC ONLINE
Seite 63 · Zum Vergrößern klicken
Seite 63

F. POSITIONING CONTROLS AND SENSORS

(1) When positioning controls and sensors, ensure other factors do not influence these

devices and give incorrect inputs to the unit. Some of these influences are:

(a) The wall humidistat should not be installed on an outside wall or hot or cold

surface.

(b) The sensor should be installed away from any heat source and away from direct

sunlight and away from any water vapor producing source.

(c) The wall surface should be flat and clean.

(d) Any draft originating from the wall interior should be prevented from interacting

with the humidity sensor. A vapor barrier should be installed.

(e) Location of sensor must be representative of space humidity therefore avoid

drafts, temperature variation or overhangs that may prevent the sensor from sensing an accurate representation of the space humidity.

(f) Duct sensors should be placed in a location that assures any and all absorption has been accomplished.

G. NORTEC ONLINE

(1) NORTEC OnLine enables secure, internet based monitoring, simplifies interoperability

and automated email service notification. Using standard Internet Explorer, version 6.0 or newer, NORTEC OnLine provides both monitoring and control, from any location with Internet access, for a period of one year. (See Figure 30.) During the service period, NORTEC OnLine will also generate automatic e-mails when scheduled service is required and/or abnormal operation occurs. Up to three customer(s) e-mail addresses may be added to the automatic notification feature, to provide instant notification.

(2) NORTEC OnLine factory technicians will remotely view each humidifier weekly and

record key status information, which will be used for an annual report to the key customer contact. This contact will also receive notification of corrections, or service recommendations from the NORTEC OnLine technician responding to automated e-mail notifications.

(3) The factory-installed NORTEC OnLine controller is located internally to the humidifier.

(4) Key features of NORTEC Online include:

(a) Graphical representation of humidifier performance

(c) Adjust %rh set point(s), if equipped

(d) Adjust manual Limited Capacity

(e) Automated e-mail advisories for scheduled service or abnormal conditions

(f) Up to fifty incidents, of factory direct support and follow-up

(g) First year of remote access includes factory direct monitoring

(h) Weekly checks by NORTEC OnLine factory technicians

(i) Remote factory diagnostics and programming capability

(j) Individual account access to www.norteconline.com

(k) Monitor up to seventy parameters from each humidifier

(b) Enable/disable humidifier

Page 64 of the Nortec NHTC user manual — Figure 30. NORTEC OnLine Monitoring
Seite 64 · Zum Vergrößern klicken
Seite 64
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 64)
Abb. 59 · Figure 8. Condensate Tee At Any Low Point

Figure 30. NORTEC OnLine Monitoring

Page 65 of the Nortec NHTC user manual — H. NORTEC LINKS
Seite 65 · Zum Vergrößern klicken
Seite 65

(l) Access to service history

(m) Option to add up to seven slave humidifiers to each NORTEC OnLine module

(n) Monitor up to eight humidifiers (one master, seven slaves) with one Internet

(o) Up to three years of coverage can be purchased at time of order

(p) Secure 128-bit Internet connectivity (SSL)

(5) Different networking configurations may be achieved and are mostly dependant on the

type of network present at the site. Specify at the time of order using the form in Figure 31. Connection options include:

(a) Static IP connection

(b) DHCP (dynamic IP)

(d) Dial-up modem connection.

H. NORTEC LINKS

(1) Provides a network connection to a BMS system using one of the following protocols:

(d) Modbus (Standard on the NHTC and NHTC Outdoor)

(e) Johnson N2.

(2) NORTEC Links provides monitoring and control allowing humidifier(s) to communicate

to your Building Management System (BMS). The controller is factory installed and is located internally to the humidifier. NORTEC Links can be integrated with NHTC, NHSC/DI, GSTC/SETC technologies. Simply specify at time of order, using the form in Figure 32, what operating protocol you are using BACnet IP, BACnet MSTP, LonWorks, Modbus or Johnson N2.

(3) Some features of NORTEC links are:

(a) Digital feedback for unit standby/humidifying mode.

(b) Digital feedback for service required.

(c) Digital feedback for fault indication.

(d) System demand display.

(e) Control enable/disable.

(4) Combined with direct sensor connection to either the humidifiers or BMS it is also

capable of:

(a) Control room set point

(b) Control high limit set point

(c) Control room %rh

(d) Control high limit %rh.

Show 5 more labels / short text on this page
connection · (c) GPRS connection · (a) BACnet IP · (b) BACnet MSTP · (c) LonWorks
Page 66 of the Nortec NHTC user manual — J. NORTEC CONTROLLER DIMENSIONS
Seite 66 · Zum Vergrößern klicken
Seite 66

I. TYPICAL INSTALLATION LAYOUT FOR NHTC/NHPC

(1) The following are examples of typical control installation possibilities. There are many

more configurations possible, be sure to consider the application and positioning as a priority. Figures 33, 34, 35, and 36 show typical control installation.

J. NORTEC CONTROLLER DIMENSIONS

(1) See dimensions in Chapter 10-30.

Page 67 of the Nortec NHTC user manual — Figure 31. NORTEC Online Configuration Form
Seite 67 · Zum Vergrößern klicken
Seite 67

NORTEC ONLINE CONFIGURATION FORM

Please complete the information below.

Attention: Date:

Company: Fax #:

FromPage: of
SubjectNORTEC Online Information

G FOR YOUR INFORMATION G RESPONSE REQUESTED

Agent P.O. Number____________________ Sales Order Number: ____________________

Desired NORTEC Online Connection Type: ‰ Static IP connection ‰ DHCP (dynamic IP) ‰ GPRS connection ‰ Dial-up modem connection

Settings for Static IP Connection: Module IP Address: Subnet Mask: Default Gateway Address: Primary DNS: Secondary DNS:

Setting for GPRS Connection: User Name: Password/PIN Code: APN String: Connection String:

Settings for Dial-up Modem ConnectionUser Name: ____________________ Password: ____________________ Phone Number to dial: ____________________

Be sure to include complete dial-up number string such as area code if necessary.

Humidifier Ordering Email Addresses for Event Notification: Email Contact 1: Email Contact 2: Email Contact 3:

End User Information Time Zone: Company Name: Address: Phone Number: Main Contact Person:

Figure 31. NORTEC Online Configuration Form

Show 13 more labels / short text on this page
Humidifier Model/Size · Unit Designation · Desired Unit · Order · Lead Humidifier · Unit 1 · Unit 2 · Unit 3 · Unit 4 · Unit 5 · Unit 6 · Unit 7 · Unit 8
Page 68 of the Nortec NHTC user manual — Figure 32. NORTEC Links Form
Seite 68 · Zum Vergrößern klicken
Seite 68

NORTEC LINKS FORM Please complete the information below.

Attention: Date:

Company: Fax #:

FromPage: of
SubjectNORTEC Links Information

G FOR YOUR INFORMATION G RESPONSE REQUESTED

MESSAGE

Agent P.O. Number____________________ Sales Order Number: ____________________
Desired NORTEC Links Option‰ BACnet/IP ‰ BACnet/MSTP ‰ Johnson N2 ‰ LonWorks

Settings for BACnet/IP only: Default Gateway Address: Network Number: Subnet Mask: Module IP Address:

Humidifier Ordering:

For all GS/SE humidifiers equipped with NORTEC Links and NH units with BACNET/IP.

Figure 32. NORTEC Links Form

Show 16 more labels / short text on this page
Humidifier Model/Size · Desired Unit Order · Lead Humidifier · Unit 1 · Unit 2 · Unit 3 · Unit 4 · Unit 5 · Unit 6 · Unit 7 · Unit 8 · Unit 9 · Unit 10 · Unit 11 · Unit 12 · Unit 13
Page 69 of the Nortec NHTC user manual — Modulating Wall Mounted Space Controller
Seite 69 · Zum Vergrößern klicken
Seite 69
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 69)
Abb. 60 · Figure 8. Condensate Tee At Any Low Point

Figure 33. Humidifier Controlled by Air Proving, On/Off Duct Mounted High Limit and

Modulating Wall Mounted Space Controller

Nortec NHTC — Modulating Wall Mounted Space Controller diagram (page 69)
Abb. 61 · Modulating Wall Mounted Space Controller

Figure 34. Humidifier Controlled by Air Proving, Modulating Duct Mounted High Limit and

Modulating Wall Mounted Space Controller

Page 70 of the Nortec NHTC user manual — Modulating Duct Mounted Return Air Sensor with Networking Option
Seite 70 · Zum Vergrößern klicken
Seite 70
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 70)
Abb. 62 · Figure 8. Condensate Tee At Any Low Point

Figure 35. Humidifier Controlled by Air Proving, Modulating Duct Mounted High Limit and

Modulating Wall Mounted Return Air Sensor with Wall Mounted Controller

Nortec NHTC — Modulating Wall Mounted Return Air Sensor with Wall Mounted Controller diagram (page 70)
Abb. 63 · Modulating Wall Mounted Return Air Sensor with Wall…

Figure 36. Humidifier Controlled by Air Proving, Duct Mounted High Limit Sensor and

Modulating Duct Mounted Return Air Sensor with Networking Option

Page 71 of the Nortec NHTC user manual — SPECIFICATIONS
Seite 71 · Zum Vergrößern klicken
Seite 71

SPECIFICATIONS

Page 72 of the Nortec NHTC user manual — B. PRODUCTS
Seite 72 · Zum Vergrößern klicken
Seite 72

SPECIFICATIONS

1. HUMIDIFIERS

A. GENERAL

(1) Work Included

(a) NORTEC NH Series electrode steam humidifier(s) as indicated on drawing(s) and

as indicated on schedule(s).

(b) Complete and operable humidification system (which meets applicable building

codes).

(c) Equipment start-up and project inspection by qualified factory trained representative.

(2) Submittals

(a) Submit product data under provisions of Section 15010. Include product

description, model, dimensions, component sizes, rough-in requirements, service sizes, and finishes. Include rated capacities, operating weights, furnished specialties, and accessories.

(b) Include piping details, plans, elevations, sections, details of components, and

dispersion tubes. Submit wiring diagrams including power, signal, and control wiring.

(3) References

(a) Certifications, C-UL_US Listed.

(b) ISO 9001-2000.

(c) ANSI/NFPA 70 – National Electrical Code.

(d) ARI 640, ‘Standard for Commercial and Industrial Humidifiers’.

(e) ASHRAE SSPC 135 BACnet, ANSI/EIA 709.1 LonTalk.

(4) Warranty

(a) Product shall be warranted to be free from defects in material and workmanship for

a period of two years after installation or 30 months from manufacturers ship date, whichever date is earlier. If operating with NORTEC web-based service program warranty is extended to 42 months from ship date.

B. PRODUCTS

(1) Electrode Steam Humidification System – NORTEC Model NHTC

(a) NORTEC NHTC electrode steam generating system using regular type potable

water supply.

(b) Packaged unit, wall mounted, requiring steam distributor(s) or Short Absorption

Manifold(s) for mounting into AHU/duct(s) or Remote/Built-On Mounted Blower Pack(s) for direct space applications. Refer to Humidifier Dispersion Options in paragraph B.(4).

(c) Atmospheric pressure steam generation and mineral separation contained within an electrode steam cylinder(s). Resistive element technology and boiler steam (pressure steam) technology not acceptable. The disposable electrode steam cylinder shall have:

1 Published life expectancy.

Page 73 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 73 · Zum Vergrößern klicken
Seite 73

2 Published replacement pricing.

3 Cylinder seams must be spin welded to ensure long-term water tightness and leak resistance.

4 Integral electronics to ensure safe operation.

5 High water sensor circuitry to prevent over filling.

6 Efficient operation over a wide range of water conditions.

7 Simple maintenance without disassembly or removal of humidifier. No specialized tools required.

8 Full output and maximum energy efficiency through entire cylinder life.

9 ‘Drain through bottom’ to ensure highest mineral concentration is effectively removed. Simple skimmers are not acceptable.

10 Large perforated strainer at drain outlet to prevent blockage of drain valve or drain lines.

11 Tool-less primary electrical connection for use with factory installed, spring loaded, gold plated connectors.

12 Safety characteristics ensuring no current flow with absence of water, independent of safety controls. Resistive element not acceptable.

(d) Unit(s) to be complete with:

1 ‘Total Controller’ microprocessor to control all humidifier functions with interface capabilities for remote communication technologies, including Internet or BMS requirements.

2 Advanced water management utilizing the patented Proportional plus Integral Autoadaptive control system for optimal energy efficiency, water usage and cylinder life.

3 Microprocessor controlled fill valve and drain valve allowing automatic water management.

4 Internal drain water tempering to ensure maximum 140°F (60°C) drain water.

5 Integral fill cup with minimum 1-inch (25-mm) air gap to prevent back siphoning.

6 Smart cylinder EPROM for improved operation providing:

a Cylinder identification with model, data, and capacity.

b Cylinder self diagnostics ensuring safe operation.

c End of cylinder life status.

d Cylinder run time in hours.

7 Full cylinder indication and pre-notification of automatic shutdown at end of cylinder life.

8 Automatic pulse feature to clean any obstruction from the drain solenoid valve when needed.

9 Automatic off-season shut-down (after 3 days of ‘no call’) will completely drain the cylinder(s) and automatically restart on call for humidity. Adjustable on/off and time sequence. Provides extended cylinder life, while ensuring stagnant water does not remain in the system.

Page 74 of the Nortec NHTC user manual — (2) Humidifier Controls (NHTC and NHTC Outdoor)
Seite 74 · Zum Vergrößern klicken
Seite 74

10 Accepts a signal from BMS/BAS system or modulating humidistat.

11 Single or dual channel signal acceptance.

12 Isolated plumbing and electrical compartment with cabinet made of 18-gauge powder coat paint finish and 20 gauge plumbing electrical door. Modular plumbing and electrical fully assembled and pre-wired (no field assembly required).

13 Removable door (no special tools required) to allow user full front access of plumbing and electrical sections.

14 Plumbing door interlock safety switch to allow power interruption when installing or servicing the humidifier.

15 Standard of acceptance NORTEC NHTC Series.

16 C-UL_US listed.

(2) Humidifier Controls (NHTC and NHTC Outdoor)

(a) Total Controller microprocessor with the following features or functions:

1 Full function user interface with touch type keypad and backlit alphanumeric graphic display with trend log.

2 Real time clock indicating date and time with battery back up.

3 Built-in controller with adjustable set point, proportional range, and integral for use with humidity transducers.

4 Acceptance of industry standard (analogue continuous control demand signal [0-5 VDC] [1-5] [0-10 VDC] [0-20 mA] [4-20 mA]) relative humidity transducers.

5 Keypad programming to configure, monitor and control humidifier parameters on graphic backlit display

a Relative humidity set point and actual conditions in space from humidity transducer.

b Relative humidity set point and actual conditions in duct for variable air volume (VAV) applications from humidity transducer.

c Relative humidity high limit set point and actual from humidity transducer.

d System demand in lbs/hr (kg/hr).

e On screen service history with date stamp.

f On screen fault history with troubleshooting list and date stamped.

g On screen attention indication.

h Security loop status open/close.

i Control Channel 1 demand %.

j Control Channel 2 demand %.

k Control mode (single or dual modulation).

l Control type (demand or rh proportional, rh proportional + integral).

17 Spec

Page 75 of the Nortec NHTC user manual — HUMIDIFIER CONTROLS NHPC
Seite 75 · Zum Vergrößern klicken
Seite 75

m Manual capacity output adjustment range of 20-100%.

n Humidifier model, capacity, software version.

o Cylinder model # and capacity rating.

p Humidifier run time weighted hours.

q Date and time (year, month, day, hour and minute).

r Stand by heating to increase steam production response time.

s Rapid modulation capability reduces response time upon start-up.

t Short cycling detection and correction diagnostics.

u Foam detection and correction capability.

v Scroll through start-up and troubleshooting checklist on graphical display.

w Self-diagnostics during start-up to system test to prevent unsafe operation of the unit(s).

x User adjustable drain/flush frequency.

HUMIDIFIER CONTROLS NHPC

(b) Proportional Controller microprocessor with following features or functions:

1 Graphic function display with user interface with touch type key pad.

2 Acceptance of industry standard [analogue continuous control demand signal [0-1Vdc] [1-5Vdc] [0-10 Vdc] [2-10 Vdc] [0-16 Vdc] [0-20 mA]

3 Keypad/Display to monitor and control humidifier parameters.

a System demand in lbs/hr (kg/hr).

b Security loop status open/close.

c Control Channel 1 demand %.

d Manual capacity output adjustment range of 20-100%.

e Self-diagnostics during start-up to system test to prevent undase operation of the Unit[s].

f Control signal type.

g Software version.

1 Internal communications via Modbus RTU protocol provides monitoring and control allowing humidifier(s) to communicate to Building Management System (BMS). Supporting a RS485 port with a configuration of 9600bps, 8-bits, no parity, one stop bit shall support the following variables:

a Change Cylinder – Indicates cylinder needs to be replaced (read).

b Channel 1 Input – Humidifier input value being supplied to channel 0- 100% (read/write).

c Channel 1 Set point – Control channel 1 setpoint for relative humidity in space 0-100% (read/write).

d Channel 2 Input – Humidifier input value being supplied to channel 0- 100% (read/write).

(c)

Page 76 of the Nortec NHTC user manual — (3) Remote Monitoring And Control Options (NHTC and NHTC OUTDOOR only)
Seite 76 · Zum Vergrößern klicken
Seite 76

e Channel 2 Set point – Control channel 2 setpoint for relative humidity in space 0-100% (read/write).

f System Demand – Indicates humidifier system demand based on input signal calculations 0-100% (read).

g Demand/rh_Configuration Parameter – Configures humidifier to accept demand or %rh signal(s) (read/write).

h Remote fault Indication – System fault indication and alarm status (read).

i Network Sensors – Allows network-enabled sensing or control (read/write).

j Remote Disable – Provides remote humidifier enable/disable system control. (read/write).

k Remote Service Indication – Provides remote humidifier service indication (read).

l Remote Status Indication – Provides remote humidifier on/standby system status indication (read).

(3) Remote Monitoring And Control Options (NHTC and NHTC OUTDOOR only)

ReferenceSection 15900 - Building Controls and Automation

(a) NORTEC OnLine web based monitoring and control from any location with Internet

access, using standard Internet Explorer, version 6.0 or newer.

(b) NORTEC OnLine remote monitoring hardware using secure

Connection> or or or Internet communication protocols.

(c) NORTEC OnLine Monitoring Service (NOMeS) with weekly humidifier examination by factory direct technicians for first year, renewable/extendable up three consecutive years.

(d) One additional year (third year), extended humidifier warranty when renewed/

extended for third year of NORTEC OnLine Monitoring Service (NOMeS).

(e) Packaged accessory, factory installed and ready for customer supplied

or communication connection.

(f) Package will include the listed items in either paragraph (f) 1 through 17 or paragraph (g) 1 through 7:

1 Internet accessible graphical representation of humidifier performance.

2 Remotely enable/disable humidifier.

3 Remotely adjust rh% set point(s), if equipped.

4 Remotely adjust ‘limited capacity’.

5 Automated e-mail advisories for scheduled service or abnormal conditions.

6 Up to three customer e-mail addresses available for automated e-mail advisories.

7 Up to 50 incidents, of factory direct support and follow-up per humidifier.

8 First year of remote access includes factory direct monitoring.

9 Weekly checks by NORTEC OnLine factory technicians.

10 Remote factory diagnostics and programming capability.

Page 77 of the Nortec NHTC user manual — ASD, BSD, CSD
Seite 77 · Zum Vergrößern klicken
Seite 77

11 Individual account access to www.norteconline.com

12 Monitor up to seventy parameters from each humidifier.

13 Access to service history.

14 Option to add up to or ‘slave’ humidifiers to each NORTEC OnLine module.

15 Monitor up to or with one or connection.

16 Up to three years of coverage can be purchased at time of order, extending humidifier limited warranty to three years.

17 Communication using secure 256-bit Internet connectivity (SSL) and Jabber protocol.

(g) NORTEC Links remote building management system capability using BACnet

MSTP, BACnet /IP LonTalk, or Johnson N2 networks for monitoring and controlling. The package will include:

1 Variable definitions, addresses, and values.

2 For complete function capabilities refer to 1.B.(2)(a)6.

3 Monitor up to 13 humidifiers (one master, 12 slaves) using a single interface.

4 External Interface File (XIF) for LonWorks integration.

5 Protocol Implementation Conformance Statement (PICS) for BACnet integration.

6 BACnet Interoperability Building Blocks (BIBBS) for BACnet Services.

7 User graphic with trending charts, complete with all humidifier details. Refer to 1.B.(2)(a)6.

(4) Humidifier Dispersion Options

(a) Single Tube(s) Steam Dispersion with condensate drain – NORTEC Model(s)

ASD, BSD, CSD

1 Allows for direct introduction of steam into a duct system or air handling unit. Distributor tube is made of stainless steel and can be installed in a horizontal, upflow, or downflow duct applications.

2 Steam inlet connection size is f" (22.2 mm) O.D for ASD, BSD models and 1¾" (44.5 mm) for CSD model.

3 Rated capacities per single dispersion tube(s) model - ASD up to 25 lbs/hr, BSD up to 35 lbs/hr and CSD up to 115 lbs/hr.

4 All single tube(s) distributors have an integral condensate return, allows for condensate produced at the distributor to be drained through a d" (9.5 mm) drain leg either back to the humidifier or to a convenient floor drain.

(b) Wall Mounted Direct Steam Dispersion System – NORTEC Model(s) RMBP or

BOBP (for NHTC and NHPC only)

1 Packaged unit, wall mounted allows for direct space/room humidification when steam introduction into a ducted system is not feasible.

Page 78 of the Nortec NHTC user manual — C. EXECUTION
Seite 78 · Zum Vergrößern klicken
Seite 78

2 The factory assembled blower pack includes an integral steam distributor, three tubeaxial (box) fans, fusing, wall mounting bracket, and air proving safety circuitry.

3 Primary and control voltage terminal blocks facilitate field connections between the humidifier.

4 Blower pack may be remote mount or built-on the humidifier.

(c) Short Absorption Manifold – NORTEC Model SAM-e

1 Short Absorption Manifold designed for atmospheric steam humidifiers or pressurized steam from a boiler, to directly inject the steam into ducted air for humidification.

a Absorption distance characteristic shall prevent water accumulation on any induct surfaces beyond ___in. (___mm) downstream of the steam dispersion panel.

b Steam dispersion panel consisting of a (one) horizontal stainless steel header supplying steam to a bank of closely spaced 3" (7.6 cm) or 6" (15.2 cm) or 9" (22.9 cm) or 12" (30.5 cm) vertical tubes, as necessary to meet absorption distance requirements, and to reduce condensation losses.

c Single horizontal stainless steel header to provide steam to vertical distributor tubes and to reduce condensation losses. Dual header systems creating unnecessary condensation, or systems needing to be installed on a partition or requiring blank off plates are not acceptable.

d Header design is primarily round tube to minimize pressure drop. Square headers are not acceptable.

e Steam inlet and condensate return located on the same side and at the bottom of the header to allow single point entry and floor mounting.

f Headers and tubes are 304 stainless steel construction.

g Vertical stainless steel distribution tubes to promote condensate evacuation. Horizontal distributor tubes are not accepted.

h Distribution tubes shall include threaded standoffs for trouble free attachment to factory supplied support bracket.

i Stainless steel nozzle inserts ensure condensate free steam is discharged from the center of the distribution tubes. Systems without nozzle inserts, or other than stainless steel, are not acceptable.

j Stainless steel nozzle inserts shall have metered orifices, sized to provide even distribution of the discharged steam, spaced for optimum steam absorption.

k Nozzles of dissimilar metals are likely to dislodge due to inconsistent rates of expansion and therefore not accepted.

l Adjustable mounting frame available for quick and easy installation.

C. EXECUTION

(1) Examination

(a) Examine ducts, air handling units, and conditions for compliance with requirements

for installation tolerances and other conditions affecting performance.

Page 79 of the Nortec NHTC user manual — (5) Training
Seite 79 · Zum Vergrößern klicken
Seite 79

(b) Examine roughing-in for piping systems to verify actual locations of piping

connections before humidifier installation.

(c) Proceed with installation only after unsatisfactory conditions have been corrected.

(2) Installation

(a) Install humidifiers and steam dispersion panels per manufacturers’ instructions.

(b) Seal humidifier dispersion-tube duct penetrations with flange.

(c) Install with required clearance for service and maintenance.

(3) Commissioning

(a) System verification testing is part of the commissioning process. Verification

testing shall be performed by the contractor and witnessed and documented by the commissioning authority. Refer to section 01810, Commissioning, for system verification tests and commissioning requirements; or

(b) Manufacturer's Field ServiceEngage a factory-authorized service representative

to inspect field-assembled components and equipment installation, including piping and electrical connections. Report results in writing. Responsibilities include:

1 Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

2 Operational Test: After electrical circuitry has been energized, start units to confirm proper unit operation. Remove malfunctioning units, replace with new units, and retest.

3 Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

(4) Testing

(a) System testing is accomplished through either of the following methods:

1 System verification testing is part of the commissioning process. Verification testing shall be performed by the contractor and witnessed and documented by the commissioning authority. Refer to section 01810, Commissioning, for system verification tests and commissioning requirements; or

2 Manufacturer’s Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including piping and electrical connections. Report results in writing. Responsibilities include:

a Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

b Operational Test: After electrical circuitry has been energized, start units to confirm proper unit operation. Remove malfunctioning units, replace with new units, and retest.

c Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

(5) Training

(a) Equipment training can be accomplished in one of the following two ways:

Page 80 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 80 · Zum Vergrößern klicken
Seite 80

1 Training of the owner’s operation and maintenance personnel is required in co-operation with the commissioning authority. Provide competent, factory authorized personnel to provide instruction to operation and maintenance personnel concerning the location, operation, and troubleshooting of the installed systems. The instruction shall be scheduled in coordination with the commissioning authority after submission and approval of formal training plans. Refer to System Demonstrations, section 01670, for contractor training requirements. Refer to section 01810, Commissioning, for further contractor training requirements; or

2 Engage a factory-authorized service representative to train owner’s maintenance personnel to adjust, operate, and maintain humidifiers.

a Train owner’s maintenance personnel on procedures and schedules for starting and stopping, troubleshooting, servicing, and maintaining equipment and schedules.

b Review data in maintenance manuals. Refer to Division 1 Section Contract Closeout.

c Review data in maintenance manuals. Refer to Division 1 Section Operation and Maintenance Data.

d Schedule training with owner, through architect, with at least seven days advance notice.

Page 81 of the Nortec NHTC user manual — 10-30 SUBMITTALS
Seite 81 · Zum Vergrößern klicken
Seite 81

10-30 SUBMITTALS

Page 82 of the Nortec NHTC user manual — E. BLOWER PACK
Seite 82 · Zum Vergrößern klicken
Seite 82

1. SUBMITTAL DESCRIPTIONS

A. INTRODUCTION

(1) The information found in this section is general in nature and consists of part numbers, product descriptions and options, dimensions, specifications and equipment features.

B. NH UNIT

(1) The different wiring connections to the humidifier unit can be found in Figure 2. All wiring is to be in accordance with existing national and local electrical codes.

(2) Performance data for single and double units can be found in Figure 3, Figure 4, and Figure 5.

(3) NH Series unit options and common accessories universal are found in Tables 1 and 2.

C. DISTRIBUTORS

(1) A description of the accessories for the steam distributor can be found in Table 3.

(2) Dimensions for the steam distributor are found in Figure 6, Figure 7, Figure 8.

D. SAM-e

(1) This section identifies the dimensions for the various configurations and components that make up a SAM-e installation.

(2) General dimensions for the SAM-e and Mini SAM-e are found in Figures 9 and 10.

(3) For an in-duct/AHU installation without mounting frame refer to Figure 11.

(4) For an in-duct/AHU installation with mounting frame refer to Figure 12.

(5) For an outside duct installation without mounting frame refer to Figure 13.

(6) For an outside duct installation with mounting frame refer to Figure 14.

(7) For a vertical duct installation refer to Figure 15.

(8) For outside duct mounting cover plates refer to Figure 16.

(9) For atmospheric SAM-e adapter dimensions refer to Figure 17.

(10) For atmospheric steam header and adapter configuration refer to Figure 18.

E. BLOWER PACK

(1) Remote Blower Packs

(a) Remote blower packs are powered from the NH humidifier from a primary

voltage terminal block provided and fed from the leaving side of the unit contactor to operate blower pack in conjunction with unit operation. A matching terminal block is incorporated in the blower pack. Field wiring is required

Page 83 of the Nortec NHTC user manual — F. CONTROLS
Seite 83 · Zum Vergrößern klicken
Seite 83

between the NH unit and remote blower pack terminal blocks or can be powered by a seperate 12 ov supply.

(b) Disk thermostat mounted on the top of steam distributor will start the fan when

steam is generated and will allow to cool down the blower pack when there is no call for humidity.

(c) A minimum of two (2) 050-100 RMBP’s are required with the NH-150 or NH-

200 units. It is recommended that four (4) RMBP’s be used to reduce the steam absorption distances.

(d) It is recommended that a minimum of two (2) remote blower packs be used on

NH 075-100 units to reduce the steam absorption distances.

(e) For recommended ceiling and frontal clearances, see Chapter 10-10.

(f) For blower pack dimensions refer to Figure 19, Figure 20, Figure 21.

(2) Built-On Blower Pack (NHTC and NHPC only)

(a) Built-on blower packs are factory mounted and wired to operate in conjunction

with the humidifier. Factory installed and wired manual reset thermostat will not allow humidifier operation if blower pack becomes overheated.

(b) Built-on blower packs are not available on NH 150-200. Remote blower packs

can be used with these units, multiple blower packs are required on NH 150- 200.

(c) Built-ON Blower Pack, Wall Mounted Direct Steam Distribution System. Allows

for direct space/room humidification when steam introduction into a ducted system is not feasible. The factory assembled Built-On Blower Pack includes an integral steam distributor, three direct drive fans for quiet operation, fan adjustable louvers for installation flexibility, fusing and safety circuitry with fan airflow rate at a total of 330 cfm.

(d) It is recommended that a minimum of two (2) remote blower packs be used on

NH 075-100 units to reduce the steam absorption distances.

(e) For recommended ceiling and frontal clearances, see Chapter 10-10. Note

minimum frontal clearance is 36" (91 cm).

(f) For blower pack dimensions refer to Figure 19, Figure 20, and Figure 21.

F. CONTROLS

(1) NHTC/NHPC humidifiers can be easily modified to accept a control signal from a modulating humidity controller as supplied by others. Controller must have a built- in adjustable %rh set point. Signal from controller must increase with a drop in sensed %rh below set point. Humidifier will respond by controlling unit output between 0% and 100% of rated capacity to match changes in load requirements.

(2) Double circuit humidifiers (NH 150-200) will require two external controllers by others to enable each circuit to operate independently of the other. Alternatively,

Page 84 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 84 · Zum Vergrößern klicken
Seite 84

coupled circuits can be specified. Coupled circuits will enable the two circuits to be operated from one controller without compromising the safety features of the humidifier (order Part No.146-9000).

(3) The humidifier shall be controlled directly using a humidity sensor (transducer) supplied by others. The sensor will be field wired to the humidifier for a direct control at the humidifier. The same sensor(s) can be shared in parallel to a Building Automation System for monitoring purposes. Allows keypad setpoint of rh and display of actual sensed rh on the NHTC’s graphical display.

(4) Double circuit humidifiers (NHTC 150-200) will require two external sensors by others to enable each circuit to operate independently of the other. Alternatively, coupled circuits can be specified. Coupled circuits will enable the two circuits to be operated from one sensor without compromising the safety features of the NHTC humidifier (order Part No.146-9000).

(5) All controls are available from the factory as options. If controls were not ordered with the humidifier, they may be purchased/supplied by others. The following information is relevant to all controls, factory supplied or otherwise.

(6) A, B and C are to be wired in series (only one path for current) across terminals 1 and 2 on the low voltage control terminal strip, or replaced with a jumper wire for constant operation.

(a) The Control On/Off Humidistat is wired to make on drop in humidity, break on

rise. Set to desired %rh.

(b) The High Limit On/Off Humidistat is wired to make on drop in humidity, break

on rise. Set to a higher set point (max. 85%rh) as a safety to prevent saturation.

(c) The Air Proving On/Off Switch is wired to make when sensing air flow, break

when no air flow. As a safety to prevent saturation when no air flow.

(7) The factory offers various versions of A, B and C to suit each application. In general, A is essential, whereas B and C are highly recommended.

(8) Field wiring from humidistat to humidifier and between devices should be 18 AWG or heavier.

(9) The low voltage control terminal strip is provided in the electrical compartment. The internal side is factory wired. The external side is to be field wired, unless the external controls have been cabinet mounted at the factory.

(10) Each unit is supplied with a wiring diagram adhered to the inside face of the

cabinet door.

Page 85 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 85 · Zum Vergrößern klicken
Seite 85
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 85)
Abb. 64 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 85)
Abb. 65 · Figure 8. Condensate Tee At Any Low Point

Figure 1. Low Voltage Control Terminal Strip

(11) A and B: Mount any wall humidistat (control or high limit) over a standard electrical box at a height similar to a typical thermostat. Any wall humidistat should be in a location representative of the overall space being humidified and not in the path of a blower pack or an air supply grille.

(12) A: Mount any duct control humidistat in a location representative of the overall air humidity, usually the return duct. Do not mount it directly in front of the steam distributor or in a turbulent or mixing zone. Mount it where the air’s humidity and temperature are uniform and representative air is over-humidified or approaching saturation.

Page 86 of the Nortec NHTC user manual — Figure 2. Primary (Line) Voltage Wiring to Unit
Seite 86 · Zum Vergrößern klicken
Seite 86
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 66 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 67 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 68 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 69 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 70 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 71 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 72 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 86)
Abb. 73 · Figure 8. Condensate Tee At Any Low Point

Figure 2. Primary (Line) Voltage Wiring to Unit

Page 87 of the Nortec NHTC user manual — Figure 3. Physical Data – NHTC/NHPC 005-030
Seite 87 · Zum Vergrößern klicken
Seite 87
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 87)
Abb. 74 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 87)
Abb. 75 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 87)
Abb. 76 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 87)
Abb. 77 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 87)
Abb. 78 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 87)
Abb. 79 · Figure 8. Condensate Tee At Any Low Point

Figure 3. Physical Data – NHTC/NHPC 005-030

Page 88 of the Nortec NHTC user manual — Figure 4. Physical Data – NHTC/NHPC 050-100
Seite 88 · Zum Vergrößern klicken
Seite 88
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 88)
Abb. 80 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 88)
Abb. 81 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 88)
Abb. 82 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 88)
Abb. 83 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 88)
Abb. 84 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 88)
Abb. 85 · Figure 8. Condensate Tee At Any Low Point

Figure 4. Physical Data – NHTC/NHPC 050-100

Page 89 of the Nortec NHTC user manual — Figure 5. Physical Data – NHTC/NHPC 150-200
Seite 89 · Zum Vergrößern klicken
Seite 89
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 89)
Abb. 86 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 89)
Abb. 87 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 89)
Abb. 88 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 89)
Abb. 89 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 89)
Abb. 90 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 89)
Abb. 91 · Figure 8. Condensate Tee At Any Low Point

Figure 5. Physical Data – NHTC/NHPC 150-200

Page 90 of the Nortec NHTC user manual — Figure 6. Distributor Dimensions (Sheet 1 of 3)
Seite 90 · Zum Vergrößern klicken
Seite 90
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 90)
Abb. 92 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 90)
Abb. 93 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 90)
Abb. 94 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 90)
Abb. 95 · Figure 8. Condensate Tee At Any Low Point

Unit Model NH 005-020 NH 030 NH 045-100 NH 135-200 Distributor Model ASD BSD CSD CSD No. of Cylinders 1 1 1 2 No. of Outlets/Cylinder 1 1 1 2 OD of Cylinder Outlet (NHTC,P,B) f" f" f" 1¾" OD of Cylinder Outlet (NHSC/DI) 1¾" Distributor Model

Dimensions – in.(mm) Minimum Duct A

B

Length –

in. (mm)

D ASD 12 2 (51) 1.75 (44) 10 (254) 12 (305) ASD18 2 (51) 1.75 (44) 16 (406) 18 (457) ASD 24 2.25 (57) 1.75 (44) 20 (508) 24 (609) ASD 30 2.25 (57) 1.75 (44) 26 (660) 30 (762) ASD 36 2.25 (57) 1.75 (44) 32 (813) 36 (914) ASD 42 2.5 (64) 2 (51) 38 (965) 42 (1066) ASD 48 2.5 (64) 2 (51) 44 (1118) 48 (1219) ASD 54 2.5 (64) 2 (51) 50 (1270) 54 (1371) ASD 60 3 (76) 2.5 (64) 56 (1422) 60 (1524) ASD 66 3 (76) 2.5 (64) 62 (1575) 66 (1676)

Figure 6. Distributor Dimensions (Sheet 1 of 3)

Page 91 of the Nortec NHTC user manual — Model
Seite 91 · Zum Vergrößern klicken
Seite 91

Distributor

Dimensions – in (mm) Minimum Duct A B C Length – in. (mm) BSD 12 2 (51) 1.75 (44) 10 (254) 12 (305) BSD 18 2 (51) 1.75 (44) 16 (406) 18 (457) BSD 24 2.25 (57) 1.75 (44) 20 (508) 24 (609) BSD 30 2.25 (57) 1.75 (44) 26 (660) 30 (762) BSD 36 2.25 (57) 1.75 (44) 32 (813) 36 (914) BSD 42 2.5 (64) 2 (51) 38 (965) 42 (1066) BSD 48 2.5 (64) 2 (51) 44 (1118) 48 (1219) BSD 54 2.5 (64) 2 (51) 50 (1270) 54 (1371) BSD 60 3 (76) 2.5 (64) 56 (1422) 60 (1524) BSD 66 3 (76) 2.5 (64) 62 (1575) 66 (1676) BSD 72 3 (76) 2.5 (64) 68 (1727) 72 (1828) BSD 78 4 (102) 3.5 (89) 47 (1880) 78 (1981) BSD 84 4 (102) 3.5 (89) 80 (2032) 84 (2133) BSD 90 4 (102) 3.5 (89) 86 (2184) 90 (2286) BSD 96 4 (102) 3.5 (89) 92 (2337) 96 (2438) BSD 102 4 (102) 3.5 (89) 98 (2489) 102 (2590) NOTES: 1. ASD Maximum rated output 25 lbs/hr (11.4 kg/hr). 2. BSD Maximum rated output 35 lbs/hr (15.9 kg/hr). 3. CSD Maximum rated output 115 lbs/hr (52.3 kg/hr). 4. Steam Distributors tube made of stainless steel. 5. Steam inlet and end cap made of fine rated plastic. 6. Distributor is adjustable for horizontal or downflow application.

Model

Figure 7. Distributor Dimensions (Sheet 2 of 3)

Page 92 of the Nortec NHTC user manual — Model
Seite 92 · Zum Vergrößern klicken
Seite 92
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 92)
Abb. 96 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 92)
Abb. 97 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 92)
Abb. 98 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 92)
Abb. 99 · Figure 8. Condensate Tee At Any Low Point

Distributor

Dimensions – in (mm) Minimum Duct A B C Length – in. (mm) CSD 24 1.75 (44) 1.55 (39) 20 (508) 24 (305) CSD 30 2 (51) 2 (51) 26 (406) 30 (457) CSD 36 2 (51) 2 (51) 32 (508) 36 (609) CSD 42 2.25 (57) 2 (51) 38 (660) 42 (762) CSD 48 2.25 (57) 2 (51) 44 (813) 48 (914) CSD 54 2.25 (57) 2 (51) 50 (965) 54(1066) CSD 60 2.5 (64) 2.5 (64) 56 (1118) 60 (1219) CSD 66 2.5 (64) 2.5 (64) 62 (1270) 66 (1371) CSD 72 2.5 (64) 2.5 (64) 68 (1422) 72 (1524) CSD 78 3 (76) 2.5 (64) 74 (1575) 78 (1676) CSD 84 3 (76) 2.5 (64) 80 (1727) 84 (1828) CSD 90 4 (102) 3 (76) 86 (1880) 90 (1981) CSD 96 4 (102) 3 (76) 92 (2032) 96 (2133) CSD 102 4 (102) 3 (76) 98 (2184) 102 (2286) CSD 108 4 (102) 3 (76) 104 (2337) 108 (2438) CSD 114 5 (127) 4.5 (114) 110 (2489) 114 (2590) CSD 120 5 (127) 4.5 (114) 116 (2945) 120 (3046) CSD 126 5 (127) 4.5 (114) 122 (3097) 126 (3198) CSD 132 6 (152) 5.5 (140) 128 (3249) 132 (3350) CSD 138 6 (152) 5.5 (140) 134 (3401) 138 (3502) CSD 144 6 (152) 5.5 (140) 140 (3553) 144 (3654)

Model

Figure 8. Distributor Dimensions (Sheet 3 of 3)

Page 93 of the Nortec NHTC user manual — Figure 9. SAM-e General Dimensions
Seite 93 · Zum Vergrößern klicken
Seite 93
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 100 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 101 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 102 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 103 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 104 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 105 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 106 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 107 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 93)
Abb. 108 · Figure 8. Condensate Tee At Any Low Point

Duct Width A B C Duct Height D (Tube Height) E min. E max. in cm in cm in cm in cm in cm in cm in cm in cm 18 45.7 13 1/8 33.3 14 7/8 37.8 16 1/4 41.3 18 45.7 6.25 15.9 17.063 43.3 24.604 62.5 24 61.0 19 1/8 48.6 20 7/8 53.0 22 1/4 56.5 24 61.0 12.25 31.1 23.063 58.6 30.604 77.7 30 76.2 25 1/8 63.8 26 7/8 68.3 28 1/4 71.8 30 76.2 18.25 46.4 29.063 73.8 36.604 93.0 36 91.4 31 1/8 79.1 32 7/8 83.5 34 1/4 87.0 36 91.4 24.25 61.6 35.063 89.1 42.604 108.2 42 106.7 37 1T/8 94.3 38 7/8 98.7 40 1/4 102.2 42 106.7 30.25 76.8 41.063 104.3 48.604 123.5 48 121.9 43 1/8 109.5 44 7/8 114.0 46 1/4 117.5 48 121.9 36.25 92.1 47.063 119.5 54.604 138.7 54 137.2 49 1/8 124.8 50 7/8 129.2 52 1/4 132.7 54 137.2 42.25 107.3 53.063 134.8 60.604 153.9 60 152.4 55 1/8 140.0 56 7/8 144.5 58 1/4 148.0 60 152.4 48.25 122.6 59.063 150.0 66.604 169.2 66 167.6 61 1/8 155.3 62 7/8 159.7 64 1/4 163.2 66 167.6 54.25 137.8 65.063 165.3 72.604 184.4 72 182.9 67 1/8 170.5 68 7/8 174.9 70 1/4 178.4 72 182.9 60.25 153.0 71.063 180.5 78.604 199.7 78 198.1 73 1/8 185.7 74 7/8 190.2 76 1/4 193.7 78 198.1 66.25 168.3 77.063 195.7 84.604 214.9 84 213.4 79 1/8 201.0 80 7/8 205.4 82 1/4 208.9 84 213.4 72.25 183.5 83.063 211.0 90.604 230.1 90 228.6 85 1/8 216.2 86 7/8 220.7 88 1/4 224.2 90 228.6 78.25 198.8 89.063 226.2 96.604 245.4 96 243.8 91 1/8 231.5 92 7/8 235.9 94 1/4 239.4 96 243.8 84.25 214.0 95.063 241.5 102.604 260.6 102 259.1 97 1/8 246.7 98 7/8 251.1 100 1/4 254.6 102 259.1 90.25 229.2 101.063 256.7 108.604 275.9 108 274.3 103 1/8 261.9 104 7/8 266.4 106 1/4 269.9 108 274.3 96.25 244.5 107.063 271.9 114.604 291.1 114 289.6 109 1/8 277.2 110 7/8 281.6 112 1/4 285.1 114 289.6 102.25 259.7 113.063 287.2 120.604 306.3 120 304.8 115 1/8 292.4 116 7/8 296.9 118 1/4 300.4 120 304.8 108.25 275.0 119.063 302.4 126.604 321.6 126 320.0 121 1/8 307.7 122 7/8 312.1 124 1/4 315.6 126 320.0 114.25 290.2 125.063 317.7 132.604 336.8 132 335.3 127 1/8 322.9 128 7/8 327.3 130 1/4 330.8 132 335.3 120.25 305.4 131.063 332.9 138.604 352.1 138 350.5 133 1/8 338.1 134 7/8 342.6 136 1/4 346.1 138 350.5 126.25 320.7 137.063 348.1 144.604 367.3 144 365.8 139 1/8 353.4 140 7/8 357.8 142 1/4 361.3 144 365.8 132.25 335.9 143.063 363.4 150.604 382.5

Figure 9. SAM-e General Dimensions

Page 94 of the Nortec NHTC user manual — Figure 10. General Mini SAM-e Dimensions
Seite 94 · Zum Vergrößern klicken
Seite 94
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 94)
Abb. 109 · Figure 8. Condensate Tee At Any Low Point

Duct Width A Duct Height B C in cm in cm in cm in cm in cm 12 30.5 11 1/16 28.1 8 20.3 7 7/8 20.0 4 7/16 11.3 18 45.7 17 1/16 43.3 10 25.4 9 7/8 25.1 6 7/16 16.4 24 61.0 23 1/16 58.6 12 30.5 11 7/8 30.2 8 7/16 21.4 14 35.6 13 7/8 35.2 10 7/16 26.5 16 40.6 15 7/8 40.3 12 7/16 31.6 18 45.7 17 7/8 45.4 14 7/16 36.7 20 50.8 19 7/8 50.5 16 7/16 41.8 22 55.9 21 7/8 55.6 18 7/16 46.8 24 61.0 23 7/8 60.6 20 7/16 51.9

Figure 10. General Mini SAM-e Dimensions

Page 95 of the Nortec NHTC user manual — Figure 11. In-Duct / AHU Installation Without Mounting Frame Installation
Seite 95 · Zum Vergrößern klicken
Seite 95
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 110 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 111 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 112 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 113 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 114 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 115 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 116 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 117 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 95)
Abb. 118 · Figure 8. Condensate Tee At Any Low Point

Figure 11. In-Duct / AHU Installation Without Mounting Frame Installation

Page 96 of the Nortec NHTC user manual — Figure 12. In-Duct / AHU Installation With Mounting Frame Installation
Seite 96 · Zum Vergrößern klicken
Seite 96
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 119 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 120 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 121 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 122 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 123 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 124 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 125 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 126 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 127 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 128 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 129 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 130 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 131 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 132 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 133 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 134 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 135 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 136 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 137 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 96)
Abb. 138 · Figure 8. Condensate Tee At Any Low Point

Figure 12. In-Duct / AHU Installation With Mounting Frame Installation

Page 97 of the Nortec NHTC user manual — Figure 13. Outside Duct Installation Without Mounting Frame Installation
Seite 97 · Zum Vergrößern klicken
Seite 97
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 139 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 140 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 141 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 142 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 143 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 144 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 145 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 146 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 97)
Abb. 147 · Figure 8. Condensate Tee At Any Low Point

Figure 13. Outside Duct Installation Without Mounting Frame Installation

Page 98 of the Nortec NHTC user manual — Figure 13. In-Duct / AHU Installation With Mounting Frame Installation
Seite 98 · Zum Vergrößern klicken
Seite 98
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 148 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 149 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 150 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 151 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 152 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 153 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 154 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 155 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 156 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 157 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 158 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 159 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 160 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 161 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 162 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 98)
Abb. 163 · Figure 8. Condensate Tee At Any Low Point

Figure 13. In-Duct / AHU Installation With Mounting Frame Installation

Page 99 of the Nortec NHTC user manual — Figure 8. Condensate Tee At Any Low Point
Seite 99 · Zum Vergrößern klicken
Seite 99
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 164 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 165 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 166 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 167 · Figure 8. Condensate Tee At Any Low Point

Figure 14. Vertical Duct Installation

Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 168 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 169 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 170 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 99)
Abb. 171 · Figure 8. Condensate Tee At Any Low Point

Figure 15. Outside Duct Mounting Cover Plates

Page 100 of the Nortec NHTC user manual — Figure 16. Atmospheric SAM-e Adapter Dimensions
Seite 100 · Zum Vergrößern klicken
Seite 100
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 172 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 173 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 174 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 175 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 176 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 177 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 178 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 179 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 180 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 181 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 182 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 183 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 184 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 185 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 186 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 187 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 188 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 189 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 190 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 100)
Abb. 191 · Figure 8. Condensate Tee At Any Low Point

Figure 16. Atmospheric SAM-e Adapter Dimensions

Page 101 of the Nortec NHTC user manual — Figure 17. Atmospheric Steam Header and Adapter Configuration
Seite 101 · Zum Vergrößern klicken
Seite 101
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 192 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 193 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 194 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 195 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 196 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 197 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 198 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 199 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 200 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 201 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 202 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 203 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 204 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 205 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 206 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 207 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 208 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 101)
Abb. 209 · Figure 8. Condensate Tee At Any Low Point

Figure 17. Atmospheric Steam Header and Adapter Configuration

Page 102 of the Nortec NHTC user manual — Figure 18. Physical Data for Remote Mounted Blower Pack
Seite 102 · Zum Vergrößern klicken
Seite 102
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 102)
Abb. 210 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 102)
Abb. 211 · Figure 8. Condensate Tee At Any Low Point

Figure 18. Physical Data for Remote Mounted Blower Pack

Page 103 of the Nortec NHTC user manual — Figure 19. Physical Data Units with Optional Built-On Blower Packs
Seite 103 · Zum Vergrößern klicken
Seite 103
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 103)
Abb. 212 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 103)
Abb. 213 · Figure 8. Condensate Tee At Any Low Point

Figure 19. Physical Data Units with Optional Built-On Blower Packs

Page 104 of the Nortec NHTC user manual — Figure 20. Physical Data Units with Optional Built-On Blower Packs
Seite 104 · Zum Vergrößern klicken
Seite 104
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 104)
Abb. 214 · Figure 8. Condensate Tee At Any Low Point

Figure 20. Physical Data Units with Optional Built-On Blower Packs

Page 105 of the Nortec NHTC user manual — Figure 21. Wall Digital Humidistat
Seite 105 · Zum Vergrößern klicken
Seite 105
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 215 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 216 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 217 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 218 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 219 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 220 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 221 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 222 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 105)
Abb. 223 · Figure 8. Condensate Tee At Any Low Point

Wall Digital Humidistat Dimensions A B C D E F in. cm in. cm in. cm in. cm in. cm in. cm 4.4 12.2 2.9 7.2 1.2 3.0 0.6 1.6 1.7 4.3 1.7 4.3

Figure 21. Wall Digital Humidistat

Page 106 of the Nortec NHTC user manual — Figure 22. Duct Sensor
Seite 106 · Zum Vergrößern klicken
Seite 106
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 224 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 225 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 226 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 227 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 228 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 229 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 230 · Figure 8. Condensate Tee At Any Low Point
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 106)
Abb. 231 · Figure 8. Condensate Tee At Any Low Point

Duct Sensor Dimensions A B C D E F in. cm in. cm in. cm in. cm in. cm in. cm 3.5 8.9 7.9 20.0 1.7 4.2 4.4 11.2 3.9 9.6 3.5 8.9

Figure 22. Duct Sensor

Page 107 of the Nortec NHTC user manual — 2522172 FACTORY PROVIDED EXTERNAL DRAIN AIR-GAP - REDUCER
Seite 107 · Zum Vergrößern klicken
Seite 107
Nortec NHTC — Figure 8. Condensate Tee At Any Low Point diagram (page 107)
Abb. 232 · Figure 8. Condensate Tee At Any Low Point

2. SUBMITTALS

A. INTRODUCTION

(1) The following pages are intended to be used by the engineer to determine the

component quantities required.

B. INSTALLATION COMPONENT SELECTION

(1) The following Tables 1 through 15 will enable the engineer to select components for

this installation.

Table 1. NH Series Unit Options

Part No. Description Qty

2522160 FILLCUP EXTENSION KIT NHTC/NHPC - 2 Required for 150 or 200

2522162 DRAIN WATER COOLER 005-020, to temper drain water below 120°F (49°C)

2522163 DRAIN WATER COOLER 030, to temper drain water below 120°F (49°C)

2522164 DRAIN WATER COOLER 050-075, to temper drain water below 120°F (49°C)

2522165 DRAIN WATER COOLER 100, to temper drain water below 120°F (49°C)

2522166 DRAIN WATER COOLER 150, to temper drain water below 120°F (49°C)

2522167 DRAIN WATER COOLER 200, to temper drain water below 120°F (49°C)

2522168 FOAM DETECTION NHTC HARDWARE

2522169 FOAM DETECTION NHPC HARDWARE

2522170 REMOTE FAULT INDICATION NHTC/NHPC

1469535 HIGH HUMIDITY ALARM PACKAGE ON/OFF high limit duct stat w/indicator

1469536 LOW HUMIDITY ALARM PACKAGE ON/OFF low limit duct stat w/indicator

1469537 HIGH HUMIDITY ALARM PACKAGE ON/OFF high limit wall stat w/indicator

1469538 LOW HUMIDITY ALARM PACKAGE ON/OFF low limit wall stat w/indicator

2522172 FACTORY PROVIDED EXTERNAL DRAIN AIR-GAP - REDUCER

146-9000 COUPLED CIRCUIT FOR DOUBLE UNIT

2522800 KEEPWARM, ALLOWING WATER TEMPERATURE IN THE CYLINDER TO BE MAINTAINED AT 160°F (70°) FOR QUICK RESPONSE UPON A CALL FOR HUMIDITY. NHTC OPTION ONLY.

2522803 UNIT NETWORKING NHTC AND NHTC OUTDOOR UP TO 1600 LBS/HR ONE PACKAGE REQUIRED FOR EACH ADDITIONAL SLAVE HUMIDIFIER DOUBLE UNIT 150/200 COUNTS AS 2 PACKAGES

Page 108 of the Nortec NHTC user manual — 1506165 DISTRIBUTOR SST ASD 12
Seite 108 · Zum Vergrößern klicken
Seite 108

Table 2. Common Accessories Universal

Part No. Description Qty

1458807 DOUBLE CHECK VALVE FOR WATER INLET LINE

1429527 DRAIN WATER SUMP PUMP (HIGH TEMPERATURE)

1329505 IN-LINE WATER FILTER 5 micron filter

1469595 POCKET HYGRO-THERMOMETER DIGITAL DISPLAY

1329561 REPLACEMENT WATER FILTERS 1 micron

1329506 REPLACEMENT WATER FILTERS 5 micron

Table 3. Steam Distributors

Part No. Description Qty

1506165 DISTRIBUTOR SST ASD 12

1506166 DISTRIBUTOR SST ASD 18

1506167 DISTRIBUTOR SST ASD 24

1506168 DISTRIBUTOR SST ASD 30

1506169 DISTRIBUTOR SST ASD 36

1506170 DISTRIBUTOR SST ASD 42

1506171 DISTRIBUTOR SST ASD 48

1506172 DISTRIBUTOR SST ASD 54

1506173 DISTRIBUTOR SST ASD 60

1506174 DISTRIBUTOR SST ASD 66

1506175 DISTRIBUTOR SST BSD 12

1506176 DISTRIBUTOR SST BSD 18

1506177 DISTRIBUTOR SST BSD 24

1506178 DISTRIBUTOR SST BSD 30

1506179 DISTRIBUTOR SST BSD 36

1506180 DISTRIBUTOR SST BSD 42

1506181 DISTRIBUTOR SST BSD 48

1506182 DISTRIBUTOR SST BSD 54

1506183 DISTRIBUTOR SST BSD 60

1506184 DISTRIBUTOR SST BSD 66

1506185 DISTRIBUTOR SST BSD 72

1506186 DISTRIBUTOR SST BSD 78

1506187 DISTRIBUTOR SST BSD 84

1506188 DISTRIBUTOR SST BSD 90

1506189 DISTRIBUTOR SST BSD 96

Page 109 of the Nortec NHTC user manual — 1506190 DISTRIBUTOR SST BSD 102
Seite 109 · Zum Vergrößern klicken
Seite 109

Table 3. Steam Distributors (cont)

Part No. Description Qty

1506190 DISTRIBUTOR SST BSD 102

1506191 DISTRIBUTOR SST CSD 24

1506192 DISTRIBUTOR SST CSD 30

1506193 DISTRIBUTOR SST CSD 36

1506194 DISTRIBUTOR SST CSD 42

1506195 DISTRIBUTOR SST CSD 48

1506196 DISTRIBUTOR SST CSD 54

1506197 DISTRIBUTOR SST CSD 60

1506198 DISTRIBUTOR SST CSD 66

1506199 DISTRIBUTOR SST CSD 72

1506200 DISTRIBUTOR SST CSD 78

1506201 DISTRIBUTOR SST CSD 84

1506202 DISTRIBUTOR SST CSD 90

1506203 DISTRIBUTOR SST CSD 96

1506204 DISTRIBUTOR SST CSD 102

1506205 DISTRIBUTOR SST CSD 108

1506206 DISTRIBUTOR SST CSD 114

1506207 DISTRIBUTOR SST CSD 120

1506208 DISTRIBUTOR SST CSD 126

1506209 DISTRIBUTOR SST CSD 132

1506210 DISTRIBUTOR SST CSD 138

1506211 DISTRIBUTOR SST CSD 144

Table 4. Steam Distributor Accessories

Part No. Description Qty

Large Size Steam Distribution Accessories (>33 lb/hr)

1329633 STEAM SUPPLY LINE TEE 1e" x 1e" x 1e" OD

1329664 LARGE STEAM SUPPLY HEADER 1 INTO 3 1e" OD connections

1859602 SPLITTING MANIFOLD 1 INTO 2 1½" to f" x f" OD

1859603 SPLITTING MANIFOLD 1 INTO 3 1e" to f" x f" x f" OD

1329643 BALANCING VALVE MANUAL FOR 1e" LINE

Page 110 of the Nortec NHTC user manual — NOTE
Seite 110 · Zum Vergrößern klicken
Seite 110

Table 4. Steam Distributor Accessories (cont)

Part No. Description Qty

Small Size Steam Distribution Accessories (<33 lb/hr)

1329642 BALANCING VALVE MANUAL TYPE FOR f" LINE

1329663 SMALL STEAM SUPPLY HEADER 1 INTO 3 f" x f" x f" x f"

1329662 STEAM SUPPLY LINE TEE f" x f" x f" OD

1328810 INSULATED FLEXIBLE STEAM SUPPLY HOSE Actual f" ID fits with ASD and BSD type steam distributors, used with models 030 and smaller humidifiers.

NOTE

It is recommended that all runs of steam piping be run in hard copper with ½" thick foam insulation and that flexible steam hose always be used to make a flexible coupling to the steam distributor and the cylinder steam outlet.

1328820 INSULATED FLEXIBLE STEAM SUPPLY HOSE Actual 1¾" ID fits with CSD type steam distributors, used with models 050 to 200 humidifiers.

NOTE

It is recommended that all runs of steam piping be run in hard copper with ½" thick foam insulation and that flexible steam hose always be used to make a flexible coupling to the steam distributor and the cylinder steam outlet.

1328840 CONDENSATE RETURN HOSE Rubber, d" ID, fits over d" OD copper tube condensate leg on all steam distributors, factory supplied/installed with built on blower packs. Copper can be used for condensate lines provided that condensate hose always be used to make a flexible coupling to the steam distributor.

1329634 SMALL STEAM SUPPLY HOSE CONDENSATE TRAP TEE f" x f" x d" OD, must be used at low points in steam supply hose to prevent condensate build-up that would result in blockage, or to remove excessive condensate can be routed to fill cup if humidifier is below trap, or to any floor drain.

1329635 LARGE STEAM SUPPLY HOSE CONDENSATE TRAP TEE 1e" x 1e" x d" OD, must be used at low points in steam supply hose to prevent condensate build-up that would result in steam blockage, or to remove excessive condensate due to long steam lines, condensate can be routed to fill cup for recycling if humidifier is below trap, or to any floor drain.

1507846 STEAM LINE REDUCER 1¾" to f" Copper

1508165 STEAM LINE REDUCER 1¾" to f" Stainless Steel

Show 4 more labels / short text on this page
Feet · Feet · Feet · Other Accessories
Page 111 of the Nortec NHTC user manual — Table 5. SAM-e Header
Seite 111 · Zum Vergrößern klicken
Seite 111

Table 5. SAM-e Header

Part No. Description Qty

1503269 3" CENTERS, 18" (45.7 cm) WIDE 3 Steam tubes

1503270 3" CENTERS, 24" (61.0 cm) WIDE 5 Steam tubes

1503271 3" CENTERS, 30" (76.2 cm) WIDE 7 Steam tubes

1503272 3" CENTERS, 36" (91.4 cm) WIDE 9 Steam tubes

1503273 3" CENTERS, 42" (106.7 cm) WIDE 11 Steam tubes

1503274 3" CENTERS, 48" (121.9 cm) WIDE 13 Steam tubes

1503275 3" CENTERS, 54" (137.2 cm) WIDE 15 Steam tubes

1503276 3" CENTERS, 60" (152.4 cm) WIDE 17 Steam tubes

1503277 3" CENTERS, 66" (167.6 cm) WIDE 19 Steam tubes

1503278 3" CENTERS, 72" (182.9 cm) WIDE 21 Steam tubes

1503279 3" CENTERS, 78" (198.1 cm) WIDE 23 Steam tubes

1503280 3" CENTERS, 84" (213.4 cm) WIDE 25 Steam tubes

1503281 3" CENTERS, 90" (228.6 cm) WIDE 27 Steam tubes

1503282 3" CENTERS, 96" (243.8 cm) WIDE 29 Steam tubes

1503283 3" CENTERS, 102" (259.1 cm) WIDE 31 Steam tubes

1503284 3" CENTERS, 108" (274.3 cm) WIDE 33 Steam tubes

1503285 3" CENTERS, 114" (289.6 cm) WIDE 35 Steam tubes

1503286 3" CENTERS, 120" (304.8 cm) WIDE 37 Steam tubes

1503287 3" CENTERS, 126" (320.0 cm) WIDE 39 Steam tubes

1503288 3" CENTERS, 132" (335.3 cm) WIDE 41 Steam tubes

1503289 3" CENTERS, 138" (350.5 cm) WIDE 43 Steam tubes

Page 112 of the Nortec NHTC user manual — Table 5. SAM-e Header (cont)
Seite 112 · Zum Vergrößern klicken
Seite 112

Table 5. SAM-e Header (cont)

Part No. Description Qty

1503290 3" CENTERS, 144" (365.8 cm) WIDE 45 Steam tubes

– – – 3" CENTERS, 144+" (365.8+ cm) WIDE Consult factory

1503309 6" CENTERS, 18" (45.7 cm) WIDE 2 Steam tubes

1503310 6" CENTERS, 24" (61.0 cm) WIDE 3 Steam tubes

1503331 6" CENTERS, 30" (76.2 cm) WIDE 4 Steam tubes

1503312 6" CENTERS, 36" (91.4 cm) WIDE 5 Steam tubes

1503313 6" CENTERS, 42" (106.7 cm) WIDE 6 Steam tubes

1503314 6" CENTERS, 48" (121.9 cm) WIDE 7 Steam tubes

1503315 6" CENTERS, 54" (137.2 cm) WIDE 8 Steam tubes

1503316 6" CENTERS, 60" (152.4 cm) WIDE 9 Steam tubes

1503317 6" CENTERS, 66" (167.6 cm) WIDE 10 Steam tubes

1503318 6" CENTERS, 72" (182.9 cm) WIDE 11 Steam tubes

1503319 3" CENTERS, 78" (198.1 cm) WIDE 12 Steam tubes

1503320 6" CENTERS, 84" (213.4 cm) WIDE 13 Steam tubes

1503321 6" CENTERS, 90" (228.6 cm) WIDE 14 Steam tubes

1503322 6" CENTERS, 96" (243.8 cm) WIDE 15 Steam tubes

1503323 6" CENTERS, 102" (259.1 cm) WIDE 16 Steam tubes

1503324 6" CENTERS, 108" (274.3 cm) WIDE 17 Steam tubes

1503325 6" CENTERS, 114" (289.6 cm) WIDE 18 Steam tubes

1503326 6" CENTERS, 120" (304.8 cm) WIDE 19 Steam tubes

1503327 6" CENTERS, 126" (320.0 cm) WIDE 20 Steam tubes

Page 113 of the Nortec NHTC user manual — Table 5. SAM-e Header (cont)
Seite 113 · Zum Vergrößern klicken
Seite 113

Table 5. SAM-e Header (cont)

Part No. Description Qty

1503328 6" CENTERS, 132" (335.3 cm) WIDE 21 Steam tubes

1503329 6" CENTERS, 138" (350.5 cm) WIDE 22 Steam tubes

1503330 6" CENTERS, 144" (365.8 cm) WIDE 23 Steam tubes

– – – 6" CENTERS, 144+" (365.8+ cm) WIDE Consult factory

1506789 9" CENTERS, 36" (91.4 cm) WIDE 3 Steam tubes

1506790 9" CENTERS, 48" (121.9 cm) WIDE 5 Steam tubes

1506791 9" CENTERS, 60" (152.4 cm) WIDE 7 Steam tubes

1506792 9" CENTERS, 72" (182.9 cm) WIDE 9 Steam tubes

1506794 9" CENTERS, 84" (213.4 cm) WIDE 11 Steam tubes

1506795 9" CENTERS, 96" (243.8 cm) WIDE 13 Steam tubes

1506796 9" CENTERS, 108" (274.3 cm) WIDE 15 Steam tubes

1507729 9" CENTERS, 120" (304.8 cm) WIDE 17 Steam tubes

1507730 9" CENTERS, 132" (335.3 cm) WIDE 19 Steam tubes

1507731 9" CENTERS, 144" (365.8 cm) WIDE 21 Steam tubes

– – – 9" CENTERS, 144+" (365.8+ cm) WIDE Consult factory

1506797 12" CENTERS, 36" (91.4 cm) WIDE 3 Steam tubes

1506798 12" CENTERS, 48" (121.9 cm) WIDE 4 Steam tubes

1506799 12" CENTERS, 60" (152.4 cm) WIDE 5 Steam tubes

1506800 12" CENTERS, 72" (182.9 cm) WIDE 6 Steam tubes

1506801 12" CENTERS, 84" (213.4 cm) WIDE 7 Steam tubes

1506802 12" CENTERS, 96" (243.8 cm) WIDE 8 Steam tubes

Page 114 of the Nortec NHTC user manual — Table 7. SAM-e Tube Matrix
Seite 114 · Zum Vergrößern klicken
Seite 114

Table 5. SAM-e Header (cont)

Part No. Description Qty

1506803 12" CENTERS, 108" (274.3 cm) WIDE 9 Steam tubes

1506804 12" CENTERS, 120" (304.8 cm) WIDE 10 Steam tubes

1506805 12" CENTERS, 132" (335.3 cm) WIDE 11 Steam tubes

1506806 12" CENTERS, 144" (365.8 cm) WIDE 12 Steam tubes

– – – 12" CENTERS, 144+" (365.8+ cm) WIDE Consult factory

Table 6. Adjustable Mounting Frame for SAM-e

Part No. Description Qty

1504697 MOUNTING FRAME SAM-e 9" to 15"

1503469 MOUNTING FRAME SAM-e 16" to 27"

1503470 MOUNTING FRAME SAM-e 28" to 51"

1503471 MOUNTING FRAME SAM-e 52" to 99"

Table 7. SAM-e Tube Matrix

Part No. Description Qty

1503388 TYPE A, 18" (45.7 cm) WIDE 15 lbs/hr (7 kg/hr)

1503389 TYPE A, 24" (61.0 cm) WIDE 15 lbs/hr (7 kg/hr)

1503390 TYPE A, 30" (76.2 cm) WIDE 15 lbs/hr (7 kg/hr)

1503391 TYPE A, 36" (91.4 cm) WIDE 15 lbs/hr (7 kg/hr)

1503392 TYPE A, 42" (106.7 cm) WIDE 15 lbs/hr (7 kg/hr)

1506393 TYPE A, 48" (121.9 cm) WIDE 15 lbs/hr (7 kg/hr)

1503394 TYPE A, 54" (137.2 cm) WIDE 15 lbs/hr (7 kg/hr)

1503395 TYPE A, 60" (152.4 cm) WIDE 15 lbs/hr (7 kg/hr)

Page 115 of the Nortec NHTC user manual — Table 7. SAM-e Tube Matrix (cont)
Seite 115 · Zum Vergrößern klicken
Seite 115

Table 7. SAM-e Tube Matrix (cont)

Part No. Description Qty

1503396 TYPE A, 66" (167.6 cm) WIDE 15 lbs/hr (7 kg/hr)

1503397 TYPE A, 72" (182.9 cm) WIDE 15 lbs/hr (7 kg/hr)

1503398 TYPE A, 78" (198.1 cm) WIDE 15 lbs/hr (7 kg/hr)

1503399 TYPE A, 84" (213.4 cm) WIDE 15 lbs/hr (7 kg/hr)

1503400 TYPE A, 90" (228.6 cm) WIDE 15 lbs/hr (7 kg/hr)

1503401 TYPE A, 96" (243.8 cm) WIDE 15 lbs/hr (7 kg/hr)

1503402 TYPE A, 102" (259.1 cm) WIDE 15 lbs/hr (7 kg/hr)

1503403 TYPE A, 108" (274.3 cm) WIDE 15 lbs/hr (7 kg/hr)

1503404 TYPE A, 114" (289.6 cm) WIDE 15 lbs/hr (7 kg/hr)

1503405 TYPE A, 120" (304.8 cm) WIDE 15 lbs/hr (7 kg/hr)

1503406 TYPE A, 126" (320.0 cm) WIDE 15 lbs/hr (7 kg/hr)

1503407 TYPE A, 132" (335.3 cm) WIDE 15 lbs/hr (7 kg/hr)

1503408 TYPE A, 138" (350.5 cm) WIDE 15 lbs/hr (7 kg/hr)

1503409 TYPE A, 144" (365.8 cm) WIDE 15 lbs/hr (7 kg/hr)

1503411 TYPE B, 24" (61.0 cm) WIDE 35 lbs/hr (16 kg/hr)

1503412 TYPE B, 30" (76.2 cm) WIDE 35 lbs/hr (16 kg/hr)

1503413 TYPE B, 36" (91.4 cm) WIDE 35 lbs/hr (16 kg/hr)

1503414 TYPE B, 42" (106.7 cm) WIDE 35 lbs/hr (16 kg/hr)

1506415 TYPE B, 48" (121.9 cm) WIDE 35 lbs/hr (16 kg/hr)

1503416 TYPE B, 54" (137.2 cm) WIDE 35 lbs/hr (16 kg/hr)

1503417 TYPE B, 60" (152.4 cm) WIDE 35 lbs/hr (16 kg/hr)

Page 116 of the Nortec NHTC user manual — Table 7. SAM-e Tube Matrix (cont)
Seite 116 · Zum Vergrößern klicken
Seite 116

Table 7. SAM-e Tube Matrix (cont)

Part No. Description Qty

1503418 TYPE B, 66" (167.6 cm) WIDE 35 lbs/hr (16 kg/hr)

1503419 TYPE B, 72" (182.9 cm) WIDE 35 lbs/hr (16 kg/hr)

1503420 TYPE B, 78" (198.1 cm) WIDE 35 lbs/hr (16 kg/hr)

1503421 TYPE B, 84" (213.4 cm) WIDE 35 lbs/hr (16 kg/hr)

1503422 TYPE B, 90" (228.6 cm) WIDE 35 lbs/hr (16 kg/hr)

1503423 TYPE B, 96" (243.8 cm) WIDE 35 lbs/hr (16 kg/hr)

1503424 TYPE B, 102" (259.1 cm) WIDE 35 lbs/hr (16 kg/hr)

1503425 TYPE B, 108" (274.3 cm) WIDE 35 lbs/hr (16 kg/hr)

1503426 TYPE B, 114" (289.6 cm) WIDE 35 lbs/hr (16 kg/hr)

1503427 TYPE B, 120" (304.8 cm) WIDE 35 lbs/hr (16 kg/hr)

1503428 TYPE B, 126" (320.0 cm) WIDE 35 lbs/hr (16 kg/hr)

1503429 TYPE B, 132" (335.3 cm) WIDE 35 lbs/hr (16 kg/hr)

1503430 TYPE B, 138" (350.5 cm) WIDE 35 lbs/hr (16 kg/hr)

1503431 TYPE B, 144" (365.8 cm) WIDE 35 lbs/hr (16 kg/hr)

1509391 TYPE B+, 30" (76.2 cm) WIDE 55 lbs/hr (25 kg/hr)

1509392 TYPE B+, 36" (91.4 cm) WIDE 55 lbs/hr (25 kg/hr)

1509393 TYPE B+, 42" (106.7 cm) WIDE 55 lbs/hr (25 kg/hr)

1509394 TYPE B+, 48" (121.9 cm) WIDE 55 lbs/hr (25 kg/hr)

1509395 TYPE B+, 54" (137.2 cm) WIDE 55 lbs/hr (25 kg/hr)

1509396 TYPE B+, 60" (152.4 cm) WIDE 55 lbs/hr (25 kg/hr)

1509397 TYPE B+, 66" (167.6 cm) WIDE 55 lbs/hr (25 kg/hr)

Page 117 of the Nortec NHTC user manual — Table 7. SAM-e Tube Matrix (cont)
Seite 117 · Zum Vergrößern klicken
Seite 117

Table 7. SAM-e Tube Matrix (cont)

Part No. Description Qty

1509398 TYPE B+, 72" (182.9 cm) WIDE 55 lbs/hr (25 kg/hr)

1509399 TYPE B+, 78" (198.1 cm) WIDE 55 lbs/hr (25 kg/hr)

1509400 TYPE B+, 84" (213.4 cm) WIDE 55 lbs/hr (25 kg/hr)

1509401 TYPE B+, 90" (228.6 cm) WIDE 55 lbs/hr (25 kg/hr)

1509402 TYPE B+, 96" (243.8 cm) WIDE 55 lbs/hr (25 kg/hr)

1509403 TYPE B+, 102" (259.1 cm) WIDE 55 lbs/hr (25 kg/hr)

1509404 TYPE B+, 108" (274.3 cm) WIDE 55 lbs/hr (25 kg/hr)

1509405 TYPE B+, 114" (289.6 cm) WIDE 55 lbs/hr (25 kg/hr)

1509406 TYPE B+, 120" (304.8 cm) WIDE 55 lbs/hr (25 kg/hr)

1509407 TYPE B+, 126" (320.0 cm) WIDE 55 lbs/hr (25 kg/hr)

1509408 TYPE B+, 132" (335.3 cm) WIDE 55 lbs/hr (25 kg/hr)

1509409 TYPE B+, 138" (350.5 cm) WIDE 55 lbs/hr (25 kg/hr)

1509410 TYPE B+, 144" (365.8 cm) WIDE 55 lbs/hr (25 kg/hr)

1503440 TYPE C, 36" (91.4 cm) WIDE 75 lbs/hr (34 kg/hr)

1503441 TYPE C, 42" (106.7 cm) WIDE 75 lbs/hr (34 kg/hr)

1503442 TYPE C, 48" (121.9 cm) WIDE 75 lbs/hr (34 kg/hr)

1503443 TYPE C, 54" (137.2 cm) WIDE 75 lbs/hr (34 kg/hr)

1503444 TYPE C, 60" (152.4 cm) WIDE 75 lbs/hr (34 kg/hr)

1503445 TYPE C, 66" (167.6 cm) WIDE 75 lbs/hr (34 kg/hr)

1503446 TYPE C, 72" (182.9 cm) WIDE 75 lbs/hr (34 kg/hr)

1503447 TYPE C, 78" (198.1 cm) WIDE 75 lbs/hr (34 kg/hr)

Page 118 of the Nortec NHTC user manual — Table 8. SAM-e Inlet and Adapter Configurations
Seite 118 · Zum Vergrößern klicken
Seite 118

Table 7. SAM-e Tube Matrix (cont)

Part No. Description Qty

1503448 TYPE C, 84" (213.4 cm) WIDE 75 lbs/hr (34 kg/hr)

1503449 TYPE C, 90" (228.6 cm) WIDE 75 lbs/hr (34 kg/hr)

1503450 TYPE C, 96" (243.8 cm) WIDE 75 lbs/hr (34 kg/hr)

1503451 TYPE C, 102" (259.1 cm) WIDE 75 lbs/hr (34 kg/hr)

1503452 TYPE C, 108" (274.3 cm) WIDE 75 lbs/hr (34 kg/hr)

1503453 TYPE C, 114" (289.6 cm) WIDE 75 lbs/hr (34 kg/hr)

1503454 TYPE C, 120" (304.8 cm) WIDE 75 lbs/hr (34 kg/hr)

1503455 TYPE C, 126" (320.0 cm) WIDE 75 lbs/hr (34 kg/hr)

1503456 TYPE C, 132" (335.3 cm) WIDE 75 lbs/hr (34 kg/hr)

1503457 TYPE C, 138" (350.5 cm) WIDE 75 lbs/hr (34 kg/hr)

1503458 TYPE C, 144" (365.8 cm) WIDE 75 lbs/hr (34 kg/hr)

Table 8. SAM-e Inlet and Adapter Configurations

Part No. Description Qty

1503479 Inlet Adapter Kit 1, SAM-e, 100 lbs/hr 1.75"

1503480 Inlet Adapter Kit 2, SAM-e, 200 lbs/hr 2x1.75"

1503481 Inlet Adapter Kit 3, SAM-e, 300 lbs/hr 3x1.75"

1503482 Inlet Adapter Kit 4, SAM-e, 400 lbs/hr 4x1.75"

1503483 Inlet Adapter Kit 5, SAM-e, 500 lbs/hr 5x1.75"

1503484 Inlet Adapter Kit 6, SAM-e, 600 lbs/hr 6x1.75"

1503485 Inlet Adapter Kit 7, SAM-e, 700 lbs/hr 7x1.75"

1503486 Inlet Adapter Kit 8, SAM-e, 800 lbs/hr 8x1.75"

2. Consult SAM-e Shop Drawings for more details.
3. All adapters come complete with hose/clamp connections for all outlets.
4. All electrode humidifiers must run individual steam lines directly to SAM-e.
Page 119 of the Nortec NHTC user manual — Table 10. Built-On Blower Pack
Seite 119 · Zum Vergrößern klicken
Seite 119

Table 9. Remote Blower Pack

Part No. Description Qty

2530893 Remote Blower Pack 5 - 30 lbs/hr 110-120V

2530891 Remote Blower Pack 5 - 30 lbs/hr 208V

2530889 Remote Blower Pack 5 - 30 lbs/hr 220-240V

2530892 Remote Blower Pack 5 - 30 lbs/hr 277V

2530888 Remote Blower Pack 5 - 30 lbs/hr 380V

2530887 Remote Blower Pack 5 - 30 lbs/hr 440-480V

2530886 Remote Blower Pack 5 - 30 lbs/hr 550-600V

2530900 Remote Blower Pack 50 - 100 lbs/hr 110-120V

2530898 Remote Blower Pack 50 - 100 lbs/hr 208V

2530897 Remote Blower Pack 50 - 100 lbs/hr 220-240V

2530899 Remote Blower Pack 50 - 100 lbs/hr 277V

2530896 Remote Blower Pack 50 - 100 lbs/hr 380V

2530895 Remote Blower Pack 50 - 100 lbs/hr 440-480V

2530894 Remote Blower Pack 50 - 100 lbs/hr 550-600V

Table 10. Built-On Blower Pack

Part No. Description Qty

2522142 Built-on Blower Pack, NHTC/NHPC 005 120V

2522143 Built-on Blower Pack, NHTC/NHPC 010-030 208V

2522144 Built-on Blower Pack, NHTC/NHPC 010-030 220-240V

2522145 Built-on Blower Pack, NHTC/NHPC 010-030 277V

2522147 Built-on Blower Pack, NHTC/NHPC 010-030 380V

2522148 Built-on Blower Pack, NHTC/NHPC 010-030 440-480V

2522149 Built-on Blower Pack, NHTC/NHPC 010-030 550-600V

2524849 Built-on Blower Pack, NHTC/NHPC 050-100 208V

2524850 Built-on Blower Pack, NHTC/NHPC 050-100 220-240V

2524851 Built-on Blower Pack, NHTC/NHPC 050-100 277V

2524852 Built-on Blower Pack, NHTC/NHPC 050-100 308V

2524853 Built-on Blower Pack, NHTC/NHPC 050-100 440-480V

2524854 Built-on Blower Pack, NHTC/NHPC 050-100 550-600V

Page 120 of the Nortec NHTC user manual — Table 12. Modulating Control By NORTEC
Seite 120 · Zum Vergrößern klicken
Seite 120

Table 11. Controls – ON/OFF

Part No. Description Qty

2520259 DIGITAL HUMIDISTAT WALL MOUNTED ON/OFF On/off wall mounted humidistat applicable as control humidistat or high limit 10% to 90% RH range with 5% non-adjustable differential.

2520273 DIGITAL HUMIDISTAT DUCT MOUNTED ON/OFF PACKAGE On/off duct mounted humidistat, applicable as a control humidistat or high limit, 15% to 90% RH range with 4% non-adjustable differential.

132-9109 PRESSURE ELECTRIC SWITCH On/off, remote mounted, 3 to 20 PSIG range, factory set to 13 PSIG with 2 to 6 PSIG fully adjustable differential, factory set to 3 PSIG. For use with pneumatic humidistat (by others).

132-9203 AIR PROVING On/off duct mounted, pressure differential switch, 0.07 IWC to 12.0 IWC fully adjustable operating range, good for positive, negative or differential pressure applications, stops humidifier if no differential pressure is sensed.

146-9000 COUPLED CIRCUITS Factory internally wired in parallel to enable control of double circuit unit from one set of external controls. Applies to NHTC 150 and 200 models only.

Table 12. Modulating Control By NORTEC

Part No. Description Qty

2520266 DIGITAL WALL CONTROLLER WITH DUCT SENSOR PACKAGE This is a digital LCD setpoint controller with a duct mounted humidity sensor used for modulating high limit or control.

2520261 DIGITAL WALL CONTROLLER WITHOUT INTEGRAL SENSOR This is a digital LCD setpoint controller to be used with one or all of the following remote sensors: remote wall sensor, remote duct sensor and outdoor duct mounted temperature sensor.

1510142 DIGITAL WALL CONTROLLER WITH INTEGRAL SENSOR This is a digital LCD setpoint controller with a wall mounted humidity sensor used for humidity control in the space.

2520263 OUTDOOR DUCT MOUNT TEMPERATURE SET BACK This sensor can be mounted directly onto the fresh air intake of the ventilation duct. The humidistat controller reads the outdoor temperature and resets the humidity control setpoint to prevent condensation in windows or building structures. Use with modulating controllers above.

1509857 REMOTE DUCT SENSOR This humidity sensor can be mounted directly onto the return ventilation as the main controlling sensor. It can also be used as a supply high limit sensor. It must be used in conjunction with any other controller for remote sensing.

1509858 REMOTE WALL SENSOR This humidity sensor can be mounted on a wall as the main controlling sensor. It must be used in conjunction with any other controller for remote sensing.

Show 10 more labels / short text on this page
Control ____ · High Limit ____ · Control ____ · High Limit ____ · Control ____ · High Limit ____ · Control ____ · High Limit ____ · Control ____ · High Limit ____
Page 121 of the Nortec NHTC user manual — Table 14. Modulating Demand Signal By Others Dual Channel
Seite 121 · Zum Vergrößern klicken
Seite 121

Table 13. Modulating Demand Signal By Others Single Channel

Part No. Description Qty

2523060 0 - 5 Vdc single channel Demand signal acceptance

2523062 0 - 20 mA single channel Demand signal acceptance

2523064 4 - 20 mA single channel Demand signal acceptance

2523066 0 - 10 Vdc single channel Demand signal acceptance

2523090 0 - 16 Vdc single channel Demand signal acceptance

2523092 1 - 5 Vdc single channel Demand signal acceptance

2523094 2 - 10 Vdc single channel Demand signal acceptance

2523096 0 - 20 Vdc single channel Demand signal acceptance

Table 14. Modulating Demand Signal By Others Dual Channel

Part No. Description Qty

2523061 0 - 5 Vdc dual channel Demand signal acceptance

2526063 0 - 20 mA dual channel Demand signal acceptance

2523065 4 - 20 mA dual channel Demand signal acceptance

2523089 0 - 10 Vdc dual channel Demand signal acceptance

2523091 0 - 16 Vdc dual channel Demand signal acceptance

2523093 1 - 5 Vdc dual channel Demand signal acceptance

2523095 2 - 10 Vdc dual channel Demand signal acceptance

2523097 0 - 20 Vdc dual channel Demand signal acceptance

Part No. Description Qty

2523100 0 - 5 Vdc single channel Transducer singal acceptance

2523101 0 - 5Vdc dual channel Transducer singal acceptance

2523102 0 - 20 mA single channel Transducer signal acceptance

2523104 0 - 20 mA dual channel Transducer signal acceptance

2523105 4 - 20 mA single channel Transducer signal acceptance

2523107 4 - 20 mA dual channel Transducer signal acceptance

2523110 0 - 10 Vdc single channel Transducer signal acceptance

2523111 0 - 10 Vdc dual channel Transducer signal acceptance

2523112 0 - 16 Vdc single channel Transducer signal acceptance

2523113 0 - 16 Vdc dual channel Transducer signal acceptance

2523114 1 - 5 Vdc single channel Transducer signal acceptance

2523115 1 - 5 Vdc dual channel Transducer signal acceptance

2523116 2 - 10 Vdc single channel Transducer signal acceptance

Page 122 of the Nortec NHTC user manual — 2522468 FUSING NHTC/PC 020-030/208-240/3
Seite 122 · Zum Vergrößern klicken
Seite 122

2523117 2 - 10 Vdc dual channel Transducer signal acceptance

2523118 0 - 20 Vdc single channel Transducer signal acceptance

2523119 0 - 20 Vdc dual channel Transducer signal acceptance

Table 16. NORTEC OnLine Options (NHTC only)

Part No. Description Qty

1509780 NORTEC ONLINE Static IP Option for NHTC

1509781 NORTEC ONLINE DHCP Option for NHTC

1509782 NORTEC ONLINE GPRS Option for NHTC

1509783 NORTEC ONLINE Dial-Up Option for NHTC

1509784 NORTEC ONLINE Slave Option for NHTC

Table 17. NORTEC Links Options (NHTC only)

Part No. Description Qty

2525534 NORTEC LINKS 2 FOR NHTC BACnet/IP

2527106 NORTEC LINKS 2 FOR NHTC BACnet/MSTP

2527108 NORTEC LINKS 2 FOR NHTC Johnson N2

2527107 NORTEC LINKS 2 FOR NHTC LonWorks

2522194 NORTEC LINKS 2 FOR NHTC Slave

remote monitoring and control using only BAS/BMS support Modbus

Table 18. NH Series Fusing Options

Part No. Description Qty

2522468 FUSING NHTC/PC 020-030/208-240/3

2522470 FUSING NHTC/PC 005-020/120-277/1

2522471 FUSING NHTC/PC 010-020/380-600/1

2522472 FUSING NHTC/PC 020-030/440-600/3

2522474 FUSING NHTC/PC 050-075/208-240/3

2522475 FUSING NHTC/PC 050-075/40-600/3

2522476 FUSING NHTC/PC 100/208-240/3

2522477 FUSING NHTC/PC 100/440-480/3

Page 123 of the Nortec NHTC user manual — Distributor Information
Seite 123 · Zum Vergrößern klicken
Seite 123

2522478 FUSING NHTC/PC 100/550-600/3

2522479 FUSING NHTC/PC 150/208-240/3

2522480 FUSING NHTC/PC 150/440-600/3

2522481 FUSING NHTC/PC 200/208-240/3

2522482 FUSING NHTC/PC 200/440-480/3

2522483 FUSING NHTC/NHPC 200/550-600/3

C. SCHEDULE

Humidifier Information

Zone Label Zone Load Humidifier Output External Protection

Humidifier Label Humidifier Model Voltage/Phase (VAC) ___ Requirement (A)

Control Information

Demand On/Off Transducer

By Nortec By Others By Nortec By Others By Nortec By Others

Air Proving By Nortec By Others None (Blower Pack)

Distributor Information

Blower Pack Built On G Remote Mounted G None (Duct) G

Duct Information Width ___________ Length ___________ Vertical Airflow G

Distributor ASD/BSD/CSD? No. Of Distributors Length

SAM-e Header Length Types of Tubs

No. of Tubes Length

Space Control · High Limit

Page 124 of the Nortec NHTC user manual — WARRANTY
Seite 124 · Zum Vergrößern klicken
Seite 124

WARRANTY

(1) Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE

COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.

(2) THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing

replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.

(3) The warranties set forth herein are in lieu of all other warranties expressed or implied

by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.

(4) THE COMPANY’s limited warranty on accessories, not of the companies manufacture,

such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.

(5) THE COMPANY makes no warranty and assumes no liability unless the equipment is

installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.

(6) THE COMPANY makes no warranty and assumes no liability whatsoever for

consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.

(7) THE COMPANY makes no warranty and assumes no liability whatsoever for damage

resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.

(8) THE COMPANY makes no warranty and assumes no liability whatsoever for

equipment that has failed due to ambient conditions when installed in locations having climates below 14°F (-10°C) during January or above 104°F (40°C) during July. (See Table 1: Weather Design Data above).

(9) THE COMPANY retains the right to change the design, specification and performance

criteria of its products without notice or obligation.

Page 125 of the Nortec NHTC user manual — INSTALLATION DATE (MM/DD/YYYY)
Seite 125 · Zum Vergrößern klicken
Seite 125

INSTALLATION DATE (MM/DD/YYYY)

MODEL #

SERIAL #

CYLINDER #

Nortec NHTC — INSTALLATION DATE (MM/DD/YYYY) diagram (page 125)
Abb. 233

Cylinder Replacement Date (MM/DD/YYYY)

Nortec NHTC — INSTALLATION DATE (MM/DD/YYYY) diagram (page 125)
Abb. 234
Nortec NHTC — INSTALLATION DATE (MM/DD/YYYY) diagram (page 125)
Abb. 235
Nortec NHTC — INSTALLATION DATE (MM/DD/YYYY) diagram (page 125)
Abb. 236

Authorized Agent:

U.S.A. Walter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: northamerica.climate@waltermeier.com WEBSITE: www.humidity.com

CANADA Walter Meier (Climate Canada) Ltd. 2740 Fenton Road Ottawa, ON K1T 3T7 TEL: 1-866-NORTEC-1 FAX: (613) 822-7964

Quellen

Referenzen & Links

In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.

Frage zu Nortec NHTC stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Nortec NHTC

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Nortec NHTC PDF-Anleitung

125 Seiten·2.8 MB·Luftbefeuchter·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…