350-30010 350-20011 350-20010 390-20010
Read the complete manual before attempting installation and activating the system.
1. DESCRIPTION The motion sensors 350-30010, 350-20010 and 350-20011 are used in combination with a daylight control module (360-35010, 360-45010, 360-45011) for lighting control. They have a detection angle of max. 90° and operate according to the Passive Infra Red (PIR) technology. - Motion sensor 350-30010 with built-in light sensor For use outdoors. Areas of application: gardens, car parks... - Motion sensor 350-20010 without built-in light sensor For use indoors. Areas of application: corridors, exhibition halls, office premises, school premises, canteens, sports halls… - Motion sensor 350-20011 without built-in light sensor For use indoors. For use in warehouses and racks (fig.1b) Accessories IP54 cap: 390-20010

350-30010 350-20011 350-20010 390-20010
(IP54) cap (390-20010) (fig.4). Bear in mind that partitions, glass, plants, furniture … block the ‘beams’ (fig.5a,b).
2.2. Installation General - Open the motion sensor by inserting a screw driver in the notch
at the bottom and turn (fig.4). - Insert the cable in the motion sensor and connect the wires to
the provided terminals. Close the motion sensor. - Fit the sensors on a wall with the bracket supplied or directly in
a corner.
Motion sensor 350-20010 / 350-30010 You can easily set the motion sensors by bending the bracket (fig.6). V indicates the bending angle and M the range in metres (fig.10a). For a max. range, the sensors have to be fitted flat against a wall (V=0°). The lens takes into account the necessary inclination to the ground.
Motion sensor 350-20011 When using the sensor in racks, angle the outer motion sensor 45° (fig.10b). This way, detection outside the rack can be avoided (fig.1b;2b).
2.3. Connection diagrams - 350-30010 (fig.7) - 350-20010 / 350-20011 (fig.8) - Parallel connection of motion sensors (fig.9) Max. 8 sensor per control module, if more motion sensors are required, provide an additional 24V DC power supply (e.g. 360-37000 or 360-47001).

350-30010 350-20011 350-20010 390-20010
2.4. Cabling Min. ±0,5mm diameter for a distance of 200m
ready for use after 1-2min (warm-up time). You can set the degree of sensitivity by means of the setting screw (fig.11). The fabric settings are suitable for use of the motion sensor under normal circumstances. If the motion sensor has a degree of sensitivity that is either too high or too low, you can optimize the detection by means of the setting screw. - You can test the detection zones by means of the built-in walk
test (fig.12).
Problem Possible cause Proposed solution
Motion sensor fails to switch on.
2.Check whether the control module is connected correctly and the sensor is powered.

350-30010 350-20011 350-20010 390-20010
Problem Possible cause Proposed solution
No / poor detection in walk test.

350-30010 350-20011 350-20010 390-20010
compliance with the statutory regulations. - This user manual has to be handed over to the user. It has to be
included in the electrical installation file and has to be passed on to any new owners. Additional copies are available on the Niko website or via the support service. - During installation, the following has to be taken into account (not
limited to list below): - The statutory laws, standards and regulations; - The state of the art technique at the moment of installation; - This user manual, which must be read within the scope of each
specific installation, only states general regulations; - The rules of proper workmanship - In case of questions, you can consult Niko’s support service or
contact a registered control organisation. Support Belgium: Support UK: +32 3 778 90 80 +44 1525877707 website : http://www.niko.be http://www.nikouk.com e-mail: [email protected] sales@nikouk.com In case of a defect, you can return your product to a registered Niko wholesaler, together with a clear description of your complaint (Conditions of use, stated defect…).

350-30010 350-20011 350-20010 390-20010
is the invoice date of purchase of the product by the consumer. If there is no invoice, the date of production applies. - The consumer is obliged to inform Niko in writing about the defect,
within two months after stating the defect. - In case of a failure to conform, the consumer has the right to a
repair or replacement (decided by Niko) free of charge. - Niko cannot be held liable for a defect or damage as a result of
an incorrect installation, improper or careless use or wrong usage or transformation of the goods. - The compulsory regulations of the national legislation concerning
the sales of consumer goods and the protection of the consumers in the countries where Niko sells, directly or via sister or daughter companies, chain stores, distributors, agents or permanent sales representatives, take priority over the rules and regulations mentioned above.

350-30010 350-20011 350-20010 390-20010

350-30010 350-20011 350-20010 390-20010

350-30010 350-20011 350-20010 390-20010

350-30010 350-20011 350-20010 390-20010
390-20010










1 7 2 3 4 5 6 8 9 10 11 12
1 7 2 3 4 5 6 8 9 10 11 12

350-30010 350-20011 350-20010 390-20010
V°
350-20010 / 350-30010 Meter
V 0° 5° 10° 20°45°
350-20010 / 350-30010

350-30010 350-20011 350-20010 390-20010
Use enclosed tape to cover lens

350-30010 350-20011 350-20010 390-20010
Min. Max.
pos. A
pos. B
nv Niko sa Industriepark West 40, BE-9100 Sint-Niklaas, Belgium
tel.: + 32 3 778 90 00 — fax: + 32 3 777 71 20
In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.
Häufige Probleme, wahrscheinliche Ursachen und Lösungen.
| Problem | Mögliche Ursache | Abhilfe | |
|---|---|---|---|
| Motion sensor fails to switch on. | 1. Incorrect connection. | 1.Check whether the sensor is connected as shown in fig.7 or 8. | p.3 |
| Motion sensor fails to switch on. | 2. The sensor is not powered (24V on terminals 1 and 2). | 2.Check whether the control module is connected correctly and the sensor is powered. | p.3 |
| No / poor detection in walk test. | 1. Front panel not fitted. | 1. Fit the front panel. | p.4 |
| No / poor detection in walk test. | 2. Incorrect location. | 2. Position the sensor as shown in fig.1, 2, 3 and 5. | p.4 |
| No / poor detection in walk test. | 3. The lens is covered/ dirty or defective. | 3. Remove the cover/clean the sensor as described in ‘5. Product maintenance’ If the lens is defective, the sensor has to be replaced. | p.4 |
Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.