Dualtech motion sensor PIR +US 350-20110 / 350-20111 Sensor base for surface mounting 390-20110

2.2. Mounting without sensor base The sensor has to be mounted in acoustic ceiling plates (false ceilings) or on a flush mounting box for fitted ceilings. The sensor has to be mounted on the ceiling by following one of the methods below: a) directly in the false ceiling by means of the supplied long screws

Read the complete manual before attempting installation and activating the system.

(fig.3a); b) by means of the supplied cable inlet, cover ring and nut. Insert the sensor cables through the cable inlet and click the inlet in

1. DESCRIPTION The dualtech motion sensor 180° (350-20110) (fig.1a) and 360° (350-20111) (fig.1b) is an intelligent motion sensor that makes use of two technologies: Passive Infra Red (PIR) and Ultrasonic (US) for an utmost precise detection (2-3cm). The dualtech motion sensor has 3 possible outputs: - NPN output (grey) responds to movement + light - NPN output (blue) responds to movement - potentialfree contact (N.O. or N.C.) responds to movement The dualtech motion sensor operates at 24V DC and can be used in combination with power supply 360-37000 or 360-47000 (230V~/24V DC), provided with a relay for switching the load. The motion sensor can be mounted on a false/fitted ceiling either directly or by means of a sensor base (390-20110) (fig.1c) enabling the cables to be inserted sidelong. Areas of application: office rooms, classrooms, conference rooms, exposi- tion rooms, restaurants.

the screw cover. Insert the inlet through a precise opening in the false ceiling and screw down the whole by means of the cover ring and nut (at the other side of the false ceiling) (fig.3b). c) Directly in a flush mounting box in a fitted or false ceiling. The openings

of the screw cover match the screw inputs of a standard flush mounting box (fig.3c).

Use the arrow on the screw cover to correctly aim the sensor (fig.3d). Make sure this arrow matches one of the arrows on the sensor, so sensor and cover interlock. Rotate the sensor until you hear the mechanism click, Indicating that the sensor is fixed. Now aim the sensor according to your wishes.

2.3. Mounting with sensor base Use the sensor base if you are mounting the sensor on a fitted ceiling (without flush mounting box). The sensor base enables to use a sidelong cable inlet. Mounting the sensor base (fig.4a) If you mount the sensor on a fitted ceiling (without flush mounting box), fix the sensor base on the ceiling by using 2 screws. Mount the sensor base in such a way, that the break out opening perfectly matches the provided cable input channels (fig.4a).

2. INSTALLATION 2.1. Mounting instructions - These products are only suitable for indoor use. - Make sure the installation is not connected to the mains when mounting

the sensor! - Take into account the location of airco or heating installations when mount-

ing the sensor. The sensor(s) has/have to be mounted at least 1m away from ventilation holes to avoid interference of air currents (fig.2). These limit the ultrasonic range and can generate false detection signals. By following the steps below, you can test the interference of air cur- rents: 1. Make sure the airco ventilator is activated. 2. Determine the place where you wish to mount the sensor. 3. Moisten your index finger and place him on that spot on the ceiling. 4. If you can feel the air current with your finger, you have to mount the sensor further away from the ventilation hole.

Mounting the sensor on the sensor plate (fig.4b) Remove the screw cover from the sensor. Insert the sensor cables via the central opening in the sensor plate. Make sure the arrows on the sensor plate match the arrows on the sensor. Push the sensor on the sensor plate and turn counterclockwise (45°) until you hear a click.

Mounting the sensor and sensor plate on the sensor base (fig.4c) Insert the sensor cables through the cable inlet opening and through the correct side opening of the sensor base (in case a sidelong cable inlet is used). Place the sensor directly below the cable inlet opening and turn ±10° in one direction. The sensor then bolts itself by means of the internal steel grip.

Page 2 of the Niko 350-20110 user manual — 350-20110 / 350-20111 / 390-20110
Seite 2 · Zum Vergrößern klicken
Seite 2

350-20110 / 350-20111 / 390-20110

Aiming the sensor (fig.4d) Once the sensor is installed and mounted on the sensor base, it can be aimed. Insert a flat screwdriver in the opening in the sensor base. Apply pressure to the steel grip while rotating the sensor. If the sensor is aimed correctly, you can remove the screwdriver. The grip bolts itself in one of the ring holes. Note: the sensor plate is provided with 29 sections that stand 5° apart in all directions.

- cut out mask (fig.10) This mask is calibrated on the inside, so it can easily be adjusted to any situation. For the areas in which you want motion detection, you can simply cut out the sections from the mask. For the areas in which you do not want motion detection, you can just leave the sections in.

3. SETTINGS AND USE When taking into use, the sensor is set to automatic/intelligent mode. You are recommended to use mode 3.1 Only use mode 3.2 in specific cases.

2.4. Connections fig. 5: wiring diagram of a dualtech motion sensor (350-20110 / 350-20111) and power supply 360-37000. The sensor is part of a SELV system (insulation class 2). Cabling sensor: ±0,5mm diameter for a distance of 200m

3.1. Automatic/intelligent mode (fabric settings) After mounting and connecting the sensor, you do NOT have to make additional settings. For the first 4 weeks after connection, the sensor operates in training mode. During this period, the sensitivity of the sensor and the switch off delay (timer) are tuned to the detected activity. This way, the sensor learns during which (busy) periods of the day there has to be a max. sensitivity and adjusts the switch off delay so the time during which the lighting is switched ‘ON’ is minimalized.

2.5. Sensor range (fig.6) The detection range goes for a mounting height of 2,5m in a room without furniture. The max. ceiling height is 3m. Note: By placing the cover cap, the detection range can be limited. Waving, typing and other subtle movements are considered small movements. Walking is the best example of a large movement. Remark regarding fig.6: These detection diagrams are based on measurements in open, unseparated rooms. Take into account that partitions as mobile walls, can limit both the ultrasonic and infrared ranges of the sensor. The infrared lens requires min. 25% (free) sight to an object to be able to detect it.

3.2. Modifying the sensor setttings In order to make other settings, you have to remove the safety ring (cap at the front of the sensor, fig.3b) by means of a small, flat screwdriver. You see two ranges of 4 dipswitches (A and B) and 4 colored potentiometers (red, black, green and blue) (fig.11). a) Dipswitches When taking into use, the two ranges of dipswitches are set to ‘OFF’. In this position, the sensor operates in automatic/intelligent mode

Covering the infrared lens For certain installation, the infrared range has to be limited by placing a mask. This prevents the sensor from being activated mistakenly if the infrared range reaches out into the hall through an open door. This mask kit contains 3 masks: (dualtech motion sensor 350-20110 does not contain a mask for conference rooms). For mounting a mask, remove the safety ring (cap at the front of the sensor, fig.3b) by means of a small, slotted screwdriver.

b) Colored potentiometers By means of the 4 potentiometers, the sensitivity, switch off delay and daylight level can be set.

- mask for conference rooms (fig.8) If you mount a sensor in the middle of a large room, the mask for confer- ence rooms limits the infrared range. This mask is used when the dualtech motion sensor is mounted in the middle of a long, rectangular room (e.g. a conference room). This mask provides a more rectangular infrared range and prevents detection through open doors out into the hall. - 180° masker (fig.9) If the sensor is mounted in a doorway, you have to prevent the infrared range from reaching out into the hall.

c) Setting the sensitivity Note: in manual mode, the sensor operates according to the set value, in automatic mode, the sensor can automatically increase the sensitivity if necessary. The sensor cannot become less sensitive than the preset sensitivity. In automatic mode, you are recommended to preserve the fabric settings for sensitivity. Red potentiometer: setting the infrared sensitivity (PIR). Turn the poten- tiometer clockwise to increase the sensitivity. Recommended (fabric) setting: 75%.

Page 3 of the Niko 350-20110 user manual — 350-20110 / 350-20111 / 390-20110
Seite 3 · Zum Vergrößern klicken
Seite 3

350-20110 / 350-20111 / 390-20110

DS Function Off On

A1 Auto / Manually Automatic The 3 sensor outputs operate automatically.

Manual -Blue output (movement) gives a continuous signal, the lighting is switched on continuously. -Grey output (movement + light) operates automatically. - Potentialfree contact operates automatically.

A2 Threshold value Auto threshold adjustment During the training period, the sensor learns when the detection has to be less or more sensitive in order to switch on the lighting.

High sensitivity The sensor has a high degree of sensitivity to switch on the lighting.

A3 LED indication LED indication on LED indication off

A4 Restart training period Saving the information Erase all and restart training period (on: 5s – off)

B1 Strong air current compensation Compensation off Compensation on If the sensor is placed too close to an air current (e.g. airco), he can mistakenly be activated. If the air current compensation is activated, the sensor is less sensitive.

B2 Doorway Installation above doorway?

No Yes Extra sensitivity right below the sensor.

B3 Switch off delay Automatic adjustment During the training period, the sensor learns to optimize the switch off delay, so the time during which the lighting is switch ON can be minimized.

Use manual settings The sensor operates according to the set switch off delay (black potentiometer).

B4 Sensitivity Automatic adjustment During the training period, the sensor learns when the detection has to be less or more sensitive in order to switch on the lighting. This in order to optimize the operation.

Use manual settings The sensor operates according to the set sensitivity (green + red potentiomete

Green potentiometer: setting the ultrasonic sensitivity (US). The ultrasonic sensor makes the motion sensor extremely sensitive for small movements (2–3cm). Turn the potentiometer clockwise to increase the sensitivity. Recommended (fabric) setting: 50%.

training period and minimizes the delay afterwards to make the time during which te lighting is switched on as short as possible. Recommended (fabric) setting: 25%.

e) Setting the switch off delay (timer) in test mode (8s) 1. Turn the black key to set the timer to max. (100%). 2. Turn the key to min. (0%). 3. The timer is set to 8s test mode for 1h, then automatically returns to 8min. 4. In order to manually exit the 8s test mode, turn clockwise to just above 8min.

d) Setting the switch off time (black potentiometer) Min. 8min – max. 40min Turn the potentiometer clockwise to increase the switch off delay. In manual mode, the sensor operates according to the set switch off delay. In automatic mode, the sensor increases the switch off delay during the

Page 4 of the Niko 350-20110 user manual — 350-20110 / 350-20111 / 390-20110
Seite 4 · Zum Vergrößern klicken
Seite 4

350-20110 / 350-20111 / 390-20110

f) Setting the daylight level The daylight level makes sure the lighting is not switched on when there is sufficient daylight. The sensor has to be mounted on a place with natural incident daylight – if possible.

Degree of humidity 0 to 95% Protection degree IP40, flush mounting, indoors Weight 142g

Output short circuit protected Blue wire (movement) NPN, max. 50mA Grey wire (movement+light) NPN, max. 50mA Relay (movement) - potentialfree two-way contact,

g) Setting ‘light not on’ level If the photocell measures this set light level (lux), the lighting does not switch on, even if motion is detected. From the moment this daylight level is reached, there is sufficient incident daylight in the room. If the daylight level drops below the set value, the lighting is switched on if motion is detected.

max. 24V DC, 500mA - blue/white = common - black/white = N.C (unused = blue/black, closed) - yellow/white = N.O (used = blue/yellow, closed)

h) Lux range (fig.12, blue potentiometer) Min. 10lx: Turn the potentiometer completely counterclockwise. The lighting is never switched on, even if motion is detected. Max. 10lx: Turn the potentiometer completely clockwise. The lighting is always switched on. Normal: the normal range is 200 to 600lx. Recommended (fabric) setting: 50% (+/-500lx).

Settings Infrared (red potentiometer) aut./man. (red LED) Ultrasound (green potentiometer) aut./man. (green LED)

How to make the settings Wait until the daylight level in the room is sufficiently high before making the settings. - Enter the dimmer’s test mode - Set the daylight level to max.: turn the blue potentiometer completely

Automatic setting (green LED) Dipswitch to OFF automatic Dipswitch to ON manual

clockwise. The lighting is switched on, regardless of the daylight level. Turn the key counterclockwise for approx. 30°. - Check: Go away from the sensor. Stand still and wait until the lighting is

Dipswitch from OFF to ON A1. overrule blue wire continuously on grey for movement + light A2. sensitivity IR + ultrasound high sensitivity A3. LED switch off LED A4. undo settings OFF-ON-OFF B1. compensation air current higher compensation B2. mounting above door stronger signal required B3. time setting manual setting 8-40min A2. setting IR + ultrasound setting potentiometers manually

switched off. Then move to the degree that the lighting shoud normally be switched on. - Setting the desired daylight level: If the lighting is switched on, turn the

blue potentiometer another 30°. Go away from the sensor, wait until the lighting is switched off and repeat the test. Repeat until the lighting remains switched off.

4. TECHNICAL DATA Mains supply 24V DC ±10% Power consumption 180° sensor max. 18mA Power consumption 360° sensor max. 33mA Light sensitivity (lux) (blue potentiometer).10-1.000lx man. Timer (black potentiometer) 8-40min. aut./man. Ultrasonic frequency 32kHz, standard Ambient temperature 0 to 40°C
Page 5 of the Niko 350-20110 user manual — 350-20110 / 350-20111 / 390-20110
Seite 5 · Zum Vergrößern klicken
Seite 5

350-20110 / 350-20111 / 390-20110

5. LEGAL WARNINGS - The installation has to be carried out by a qualified person and in compliance
6. GUARANTEE PROVISIONS - Period of guarantee: 2 years from date of delivery. The delivery date is

with the statutory regulations. - This user manual has to be handed over to the user. It has to be included in

the invoice date of purchase of the product by the consumer. If there is no invoice, the date of production applies. - The consumer is obliged to inform Niko in writing about the defect, within

the electrical installation file and has to be passed on to any new owners. Additional copies are available on the Niko website or via the support service. - During installation, the following has to be taken into account (not limited

two months after stating the defect. - In case of a failure to conform, the consumer has the right to a repair or

replacement (decided by Niko) free of charge. - Niko cannot be held liable for a defect or damage as a result of an incorrect

to list below): - The statutory laws, standards and regulations; - The state of the art technique at the moment of installation; - This user manual, which must be read within the scope of each specific

installation, improper or careless use or wrong usage or transformation of the goods. - The compulsory regulations of the national legislation concerning the

installation, only states general regulations; - The rules of proper workmanship - In case of questions, you can consult Niko’s support service or contact

sales of consumer goods and the protection of the consumers in the countries where Niko sells, directly or via sister or daughter companies, chain stores, distributors, agents or permanent sales representatives, take priority over the rules and regulations mentioned above.

a registered control organisation. Support Belgium: Support UK: +32 3 778 90 80 +44 1525877707 website : http://www.niko.be http://www.nikouk.com e-mail: [email protected] sales@nikouk.com In case of a defect, you can return your product to a registered Niko wholesaler, together with a clear description of your complaint (Conditions of use, stated defect…).

Page 6 of the Niko 350-20110 user manual — Technical drawings
Seite 6 · Zum Vergrößern klicken
Seite 6
Niko 350-20110 — Technical drawings diagram (page 6)
Abb. 1 · Technical drawings
Page 7 of the Niko 350-20110 user manual — Technical drawings
Seite 7 · Zum Vergrößern klicken
Seite 7
Niko 350-20110 — Technical drawings diagram (page 7)
Abb. 2 · Technical drawings
Page 8 of the Niko 350-20110 user manual — Technical drawings
Seite 8 · Zum Vergrößern klicken
Seite 8
Niko 350-20110 — Technical drawings diagram (page 8)
Abb. 3 · Technical drawings

Red Black Gray (Movement + light) Blue (Movement) Black/White Yellow/White

NB! The detection area is given for a mounting height of 2,5 meters in premises without furniture. Note: Max. ceiling height is 3 m

Page 9 of the Niko 350-20110 user manual — Technical drawings
Seite 9 · Zum Vergrößern klicken
Seite 9
Niko 350-20110 — Technical drawings diagram (page 9)
Abb. 4 · Technical drawings

A mask isn’t needed on a corner mounted sensor. The sensor can’t see hallway traffic

Page 10 of the Niko 350-20110 user manual — PM350-20110R08331
Seite 10 · Zum Vergrößern klicken
Seite 10
Niko 350-20110 — Technical drawings diagram (page 10)
Abb. 5 · Technical drawings

Blue 50% Max. 1000 lux Daylight level Min. 10 lux Black 25% Min. 8 min. Timer Max. 40 min.

nv Niko sa Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel.: + 32 3 778 90 00 — fax: + 32 3 777 71 20

e-mail[email protected] — www.niko.be

PM350-20110R08331

Quellen

Referenzen & Links

In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.

Frage zu Niko 350-20110 stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Niko 350-20110

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.