FIELDPOINT ™ OPERATING INSTRUCTIONS AND SPECIFICATIONS FP-PWM-520 and cFP-PWM-520 Eight-Channel, 5 V or 10–30 V PWM Output Module These operating instructions desc ribe ho w to install and use the National Instruments FP -PWM-520 and cFP- PWM-520 pulse-width modulation modules (referred to inclusiv ely as the [c]FP-PWM-520).
FP-PWM-520 and cFP-PWM-520 2 ni.com Installing the FP-PWM-520 The FP-PWM-520 mounts on a Fi eldPoint terminal base (FP-TB- x ), which provides operating power to the module. Installing the FP-PWM-520 onto a po wered terminal base does not disrupt the operation of the bank.
© National Instruments Corp. 3 FP-PWM-520 and cFP-PWM-520 Installing the cFP-PWM-520 The cFP-PWM-520 mounts on a Compact FieldPoint backplane (cFP-BP- x or cFP-180 x ), which pro vides operating po wer to the module. Installing th e cFP-PWM-520 onto a powered backplane does not disrupt the operation of the bank.
FP-PWM-520 and cFP-PWM-520 4 ni.com Wiring the [c]FP-PWM-520 The FP-TB- x terminal base ha s connections for each of the eight output channels and for an exte rnal power supply to po wer the output channels and field de vices. The cFP-CB- x connector block provides th e same connections.
© National Instruments Corp. 5 FP-PWM-520 and cFP-PWM-520 Install a 2 A maximum, fast-acti ng fuse between the external power supply and the V SUP terminal on each cha nnel. Install a 1 A maximum, fast-acting fuse suitable for the load at the V OUT terminal.
FP-PWM-520 and cFP-PWM-520 6 ni.com In the ON state, the ef fecti ve resistance between V OUT and V SU P causes a v oltage drop between th e external supply v oltage and the output voltage.
© National Instruments Corp. 7 FP-PWM-520 and cFP-PWM-520 • Disconnect the external po wer supply from the [c]FP-PWM-520. • Remov e the [c]FP-PWM-520 from the terminal base or backplane. • Po wer off the network module connected to the [c]FP-PWM-520.
FP-PWM-520 and cFP-PWM-520 8 ni.com Configuring the Output Channels A [c]FP-PWM-520 output channel uses period and duty-cycle settings to determine when the cha nnel is on or of f. T o configure the period, complete the fol lowing steps in Mea surement & Automation Explorer (MAX): 1.
© National Instruments Corp. 9 FP-PWM-520 and cFP-PWM-520 [c]FP-PWM-520, it sends initial conf igurati on information to the [c]FP-PWM-520. After the [c]FP-PWM-520 recei v es this initial information, the green READY indicator lights and the module is in normal operating mode.
FP-PWM-520 and cFP-PWM-520 10 ni.com Even though the [c]FP-PWM- 520 is designed to handle applications with hazardous potent ials, follo w these guidelines to ensure a safe total system: • There is no isolation between channels on the [c]FP-PWM- 520 .
© National Instruments Corp. 1 1 FP-PWM-520 and cFP-PWM-520 Safety Guidelines for Hazardous Locations The cFP -PWM- 520 is suitable fo r use in Class I, Di vision 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nC IIC T4 and Ex nC IIC T4 hazardous locations; and nonhazardous locations only .
FP-PWM-520 and cFP-PWM-520 12 ni.com Specifications The follo wing specif ications are typical for a range of – 40 to 70 °C unless otherwise noted. Output Characteristics Number of channels ............ ........... ... 8 Output type ...............
© National Instruments Corp. 1 3 FP-PWM-520 and cFP-PWM-520 Guaranteed trip current Re vision E and later modules ..... 12.5 A Re vision D and earlier modules ...... ........... ......... ............ 20 A T rip time Re vision E and later modules ...
FP-PWM-520 and cFP-PWM-520 14 ni.com Mechanical Dimensions Figure 5 sho ws the mechanical dimensions of the FP-PWM-520 installed on a termin al base. If you are using the cFP-PWM-520, refer to your Compact FieldPo int controller user manual for the dimensions and cabling clearance require ments of the Compact FieldPoint system.
© National Instruments Corp. 1 5 FP-PWM-520 and cFP-PWM-520 Shock and Vibration These specifications apply only to the cFP-PWM-520. NI recommends Compact FieldPoi nt if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64).
FP-PWM-520 and cFP-PWM-520 16 ni.com Electromagnetic Compatibility This product is designed to meet the requirements of the following standards of EMC for electrical equipment for measurement, control.
© National Instruments Corp. 1 7 FP-PWM-520 and cFP-PWM-520 Waste Electrical and Electronic Equipment (WEEE) EU Customers At the end of their lif e cycle, all products must be sent to a WEEE re c ycling center . F or more information about WEEE recycling centers and National Instruments WEEE init iativ es, visit ni.
FP-PWM-520 and cFP-PWM-520 18 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni.
© 2002–2007 Nati onal Instruments Corp. All rights reserved . 373357C-01 Dec07 National Instruments, NI, n i.com, and LabVIEW are trademarks of Na tional Instruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National In struments trademarks.
Ein wichtiger Punkt beim Kauf des Geräts National Instruments cFP-PWM-520 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie National Instruments cFP-PWM-520 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für National Instruments cFP-PWM-520 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von National Instruments cFP-PWM-520 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über National Instruments cFP-PWM-520 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon National Instruments cFP-PWM-520 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von National Instruments cFP-PWM-520 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit National Instruments cFP-PWM-520. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei National Instruments cFP-PWM-520 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.