1 Introduction

Congratulations on your recent LEGRAND purchase!

1.1 Use of the manual The manual reflects the state of the art when the equipment was put onto the market. This pub- lication conforms to the standards current on that date; the manual cannot be considered inad- equate when new standards come into force or modifications are made to the equipment. The version of the manual updated to its latest release is available on the Internet from the website http://www.ups.legrand.com

1.2 Guarantee terms The terms of the guarantee may vary depending on the country where the UPS is sold. Check the validity and duration with LEGRAND’s local sale representative.

The Manufacturer declines all indirect or direct responsibility arising from: - failure to observe the installation instructions and use of the equipment which differs from the

specifications in the manual; - use by personnel who have not read and thoroughly understood the content of the manual; - use that does not comply with the specific standards used in the country where the equipment

is installed; - modifications made to the equipment, software, functioning logic unless they have been autho-

rized by the Manufacturer in writing; - repairs that have not been authorized by the LEGRAND Technical Support Service; - damage caused intentionally, through negligence, by acts of God, natural phenomena, fire or

liquid infiltration.

1.3 Copyright The information contained in this manual cannot be disclosed to third parties. Any partial or total duplication of the manual which is not authorized in writing by the Manufacturer, by photocopy- ing or other systems, including by electronic scanning, violates copyright conditions and may lead to prosecution. LEGRAND reserves the copyright of this publication and prohibits its reproduction wholly or in part without previous written authorisation.

Page 2 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 2 Safety and Operating Instructions
Seite 2 · Zum Vergrößern klicken
Seite 2

2 Safety and Operating Instructions

This section contains important safety and operating instructions that should always be followed during the installation, use and maintenance of the UPS.

  • This product should be installed in compliance with installation rules, preferably by a qualified electrician. Incorrect installation and use can lead to risk of electric shock or fire. Before carrying out the installation, read the instructions and take account of the product’s specific mounting location. Do not open up, dismantle, alter or modify the device except where specifically required to do so by the instructions. All Legrand products must be opened and repaired exclusively by personnel trained and approved by Legrand. Any unauthorised opening or repair completely cancels all liabilities and the rights to replacement and guarantees. Use only Legrand brand accessories.
  • Ensure that the mains supply voltage and frequency match those of the UPS (see the product label and the technical specifications on chapter 7).
  • If any visible damage is found on the product during the unpacking operation, do not install the UPS but repack the unit and return it to your reseller or distributor.
  • Before operating the UPS or connecting any load equipment, ensure the UPS is connected to a properly grounded mains socket.
  • The load applied must not exceed the one indicated on the type label of the UPS.
  • The ON/OFF button of the UPS does not electrically isolate the internal parts. To isolate the UPS, unplug it from the mains power socket.
  • Do not attempt to open or disassemble the UPS; there are no user replaceable parts. Opening the case will void the warranty and introduces the risk of electric shock even when the mains plug is disconnected.
  • Since the non-detachable power supply cable acts as a separation device, the mains power supply socket shall be installed near the UPS and shall be easily accessible.
  • In case of a mains power supply failure, do not unplug the power supply cable. Earth continuity must be ensured to the connected loads.
  • Do not plug non-computer-related items such as medical, life-support and house electric equipments to the UPS output.
  • Do not plug laser printers to the UPS back-up outputs because of their high start-up current.
  • The UPS has its own internal energy source (batteries). If the UPS is switched on when no AC power is available, there is hazardous voltage at the output sockets.

The batteries inside the UPS are not user-replaceable. Servicing of batteries must be performed only by electrical hazard authorized personnel.

CAUTION: A battery can present a risk of electrical shock and burns by high short-circuit circuit current. Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces. The following precautions should be observed when working on batteries: a) Remove watches, rings or other metal objects. b) Use tools with insulated handles. c) Wear rubber gloves and boots. d) Do not lay tools or metal parts on top of batteries.

Page 3 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 2 Safety and Operating Instructions
Seite 3 · Zum Vergrößern klicken
Seite 3

2 Safety and Operating Instructions

e) Disconnect the charging source prior to connecting or disconnecting battery terminals. f) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source

from ground. Contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. The likelihood of such shock can be reduced if such grounds are removed during installa- tion and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit). g) When replacing batteries, replace with the same type and number of batteries or battery packs.

  • The UPS has dangerous high voltages on its input and output connections. Contact with these voltages may be life threatening.
  • In case of emergency, immediately turn off the equipment and disconnect the power cord from the AC power supply to disable the UPS.
  • Do not allow any liquid or any foreign object to enter the UPS.
  • The UPS is intended for indoor installation in a ventilated, controlled indoor environment with a range of temperature between 0°C (+32°F) and +40°C (+104°F) and non-condensing humidity <95%.
  • Do not install the UPS in locations with sparks, smoke and hazardous gas or where there is water and excessive humidity. Dusty, corrosive, and salty environments can damage the UPS.
  • Do not plug the UPS input into its own output.
  • Do not attach a power strip or surge suppressor to the UPS.
  • Ensure that the cables connecting the loads to the UPS are not longer than 10 meters.
  • Keep a clearance of 20 cm beyond the UPS rear panel. Avoid exposing it to direct sunlight or installing it near heat emitting appliances.
  • Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
  • Do not place the UPS near equipments that generate strong electromagnetic fields and/or near equipments that are sensible to electromagnetic fields.
  • The battery of the UPS should be recharged every 2-3 months if unused. To do so, connect the power cable to a suitable grounded mains socket.
Page 4 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 3 Installation
Seite 4 · Zum Vergrößern klicken
Seite 4

3 Installation

LEGRAND Single Phase UPS (KEOR PDU) — 3 Installation diagram (page 4)
Abb. 1 · 3 Installation
Page 5 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 3 Installation
Seite 5 · Zum Vergrößern klicken
Seite 5

3 Installation

LEGRAND Single Phase UPS (KEOR PDU) — 3 Installation diagram (page 5)
Abb. 2 · 3 Installation
Page 6 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 4.1 Overview
Seite 6 · Zum Vergrößern klicken
Seite 6

4 Operation

4.1 Overview

LEGRAND Single Phase UPS (KEOR PDU) — 4.1 Overview diagram (page 6)
Abb. 3 · 4.1 Overview
Page 7 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 4.2 Start-up procedure
Seite 7 · Zum Vergrößern klicken
Seite 7

4 Operation

4.2 Start-up procedure

4.2.1 Normal mode 1. Ensure that the mains power supply to be used has a suitable voltage/frequency and an up- stream protection rated at either 10A or 16 A. 2. Plug the UPS power cord into the mains power supply socket. 3. The UPS recharges its battery each time it is connected to a mains power supply (even if it is powered down). In this stand-by condition, it is also possible to use the USB charger port. It is recommended to charge the battery at least 4 hours before connecting the loads. 4. Connect the loads to the output sockets. 5. Press the ON/OFF button to start-up the UPS and power the loads.

INDICATION The UPS has the autorestart function. In case the mains power fail and the UPS reaches the end of the back-up time, the load is powered automatically when the mains power is back.

4.2.2 Cold start 1. Make sure the internal battery is fully charged. 2. Connect the loads in the back-up sockets. 3. Press the ON/OFF button to start-up the UPS and power the loads.

INDICATION The output frequency is set to 50 Hz.

4.3 Shutdown 1. Press and hold the ON/OFF button. 2. The UPS stops powering the back-up outlets. 3. Unplug the UPS from the mains power supply socket.

Page 8 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 4.2 Start-up procedure
Seite 8 · Zum Vergrößern klicken
Seite 8

2x 20 s 2x

3x 15 s 3x

4x 15 s 4x

< 10%

Kontrolka LED ze światłem ciągłym - LED brand continu - Stalno svijetleća LED - LED σταθερό - Folyamatos LED - LED fixo - Индикатор постоянно горит -

Voyant clignotant - Blinking LED - LED Lampeggiante - LED blinkend - LED parpadeante - Kontrolka LED migająca - LED knippert - Treptajuća LED - LED αναβοσβήνει - Villogó LED LED intermitente - Индикатор моргает -

Avertisseur sonore silencieux - Buzzer Mute - Buzzer Silenziato - Stummges - chalteter Summer - Zumbador silenciado - Wyciszenie brzęczyka - Zoemer stil - Zujalica nije uključena - Σίγαση ήχου Némítás - Alarme Silenciar - Отключить звук -

Signal sonore intermittent - Intermittent Sound - Suono Intermittente - Intermittierender Ton - Sonido intermitente - Przerywany sygnał dźwiękowy - Onderbroken geluidssignaal- Isprekidani zvuk - Διακοπτόμενος ήχος - Szakaszos sípolás - Som intermitente - Прерывистый звук -

Signal sonore continu - Continuous Sound - Suono Continuo - Kontinuierlicher Ton - Sonido continu - Ciągły sygnał dźwiękowy - Ononderbroken geluidssignaal - Kontinuirani zvuk - Συνεχής ήχος - Folyamatos sípolás - Som contínuo - Непрерывный звук -

Show 6 more labels / short text on this page
30 s · 100% - 75% · 75% - 50% · 50% - 25% · 25% - 10% · Overload
Page 9 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — INDICATION POSSIBLE CAUSE SOLUTION
Seite 9 · Zum Vergrößern klicken
Seite 9

5 Troubleshooting

INDICATION POSSIBLE CAUSE SOLUTION

Remove the loads from the UPS outlets. Turn off the UPS and disconnect it from the mains. Connect the UPS to the mains and turn on again.

Alarm LED ON UPS fault

If the problem persists, contact the LEGRAND Technical Support Service.

Disconnect some non-critical loads from the UPS outlets until the overload ceases

with the UPS working in

The UPS doesn’t work in stored energy mode

If the backup time remains unsatisfactory after 8 hours of battery charging, contact the LEGRAND Technical Support Service

Low battery or battery

or the backup time is shorter than its intended

Check that all power cords are properly connected. If the problem persists, contact the LEGRAND Technical Support Service.

The UPS is working normally but the loads are

The UPS fuse blew up Replace the fuse with a new one

The UPS works on battery

mode even though the mains power is available

Check that the UPS works on another socket. If so, have the initial mains power supply socket checked by a qualified electrician.

The mains power supply

socket is not supplying

power to the UPS

Shut down immediately the UPS. Unplug the UPS from the mains socket and contact the LEGRAND Technical Support Service.

Strange noise or smell UPS fault

Show 6 more labels / short text on this page
Intermittent alarm sound · Overload · normal mode · fault · performance · not powered
Page 10 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 6.2 Dismantling
Seite 10 · Zum Vergrößern klicken
Seite 10

6 Warehousing and dismantling

6.1 Warehousing The UPS must be stored in an environment with a room temperature between +20°C (+68°F) and +25°C (+77°F) and humidity less than 95% (not condensing). The battery installed inside the UPS is lead/acid sealed and does not require maintenance (VRLA). The battery should be charged for 8 hours every 3 months by connecting the UPS to the mains supply socket. Repeat this procedure every two months if the storage ambient temperature is above +25°C (+77°F).

6.2 Dismantling

DANGER Dismantling and disposal operations may only be done by a qualified electrician. These instruc- tions are to be considered indicative: in every country there are different regulations with regard to the disposal of electronic or hazardous waste such as batteries. It is necessary to strictly adhere to the standards in force in the country where the equipment is used. Do not throw any component of the equipment in the ordinary rubbish.

Batteries must be disposed of in a site intended for the recovery of toxic waste. Disposal in the traditional rubbish is not allowed. Apply to the competent agencies in your countries for the proper procedure.

It is important to dismantle the various parts the UPS consists of. For these operations, Personal Protective Equipment must be worn. Sub-divide the components separating the metal from the plastic, from the copper and so on ac- cording to the type of selective waste disposal in the country where the equipment is dismantled.

If the dismantled components must be stored before being properly disposed, be careful to keep them in a safe place protected from atmospheric agents to avoid soil and groundwater contamination.

For the disposal of electronic waste it is necessary to refer to the industry standards.

This symbol indicates that in order to prevent any negative effects on the environment and on people, this product should be disposed of separately from other household waste, by taking it to authorised collection centres, in accordance with the EU countries local waste disposal legislations. Disposing of the product without following local regu- lations may be punished by law. It is recommended to check that this equipment subject to WEEE legislations in the country where it is used.

Page 11 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 7 Technical specifications
Seite 11 · Zum Vergrößern klicken
Seite 11

7 Technical specifications

LEGRAND Single Phase UPS (KEOR PDU) — 7 Technical specifications diagram (page 11)
Abb. 4 · 7 Technical specifications

3 103 30 3 103 31 3 103 32 3 103 33 3 110 16 3 110 17 3 110 18 3 110 19

Rated frequency 50 / 60 Hz ± 5 Hz with auto-sensing

Rated frequency 50 / 60 Hz ± 1 Hz with auto-sensing (battery mode)

Batteries Number of batteries 1 Battery type lead-acid sealed without maintenance (VRLA) Unitary capacity 9 Ah Rated Battery Voltage 12 Vcc

Backup time 10 min. (calculated with one typical workstation)

Protection against total discharge Typical recharge time 4-6 hours

Page 12 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 7 Technical specifications
Seite 12 · Zum Vergrößern klicken
Seite 12

3 103 30 3 103 31 3 103 32 3 103 33 3 110 16 3 110 17 3 110 18 3 110 19 Communication and management

Alarms Visual (LED), Audible (buzzer)

Against overload, overvoltage and short-circuit

Dimensions W x H x D (mm) 440 x 86 x 148

Net weight (kg) 5,1

Operating temperature 0ºC to +40ºC +32ºF to +104ºF

Operating relative humidity

Storage temperature +20ºC to +25ºC

Noise level at 1 m < 40 dB

IP code IP 20

Reference directive and standards

Safety 2014/35/EU Directive EN 62040-1

EMC 2014/30/EU Directive EN 62040-2

Show 6 more labels / short text on this page
Replaceable input fuse · Protections · Backfeed Overtemperature · Mechanical characteristics · Environmental conditions · +68ºF to +77ºF
Page 13 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 7 Technical specifications
Seite 13 · Zum Vergrößern klicken
Seite 13
Page 13 of the LEGRAND Single Phase UPS (KEOR PDU) user manual — 7 Technical specifications
Quellen

Referenzen & Links

In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.

Frage zu LEGRAND Single Phase UPS (KEOR PDU) stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu LEGRAND Single Phase UPS (KEOR PDU)