The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead‐acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Class B EMC Statements (High Voltage Models up to 3000 VA) FCC (Federal Communications Commision) Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

This UPS protects your sensitive electronic equipment from most common power problems, including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switching transients, and harmonic distortion. Power outages might occur unexpectedly and power quality can be erratic. These power problems have potential to corrupt critical data, destroy unsaved work sessions, and damage hardware — causing hours of lost productivity and expensive repairs. With the UPS, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the UPS’s unique benefi ts include:



This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
The UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
This section explains:
If any equipment received has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and fi le a claim for shipping damage. If you discover damage after acceptance, fi le a claim for concealed damage.
To fi le a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.

To unpack the cabinet and accessories: 1. Open the outer carton and remove the accessories packaged with the cabinet. 2. Carefully lift the cabinet out of the outer carton. 3. Discard or recycle the packaging in a responsible manner, or store it for future use.
Place the cabinet in a protected area that has adequate airfl ow and is free of humidity, fl ammable gas, and corrosion.
It includes:
If you ordered an optional Extended Battery Module (EBP), verify that the following additional item is included with the EBP:
The Rackmount cabinet comes with all of the hardware required for installation in a standard EIA or JIS seismic Rackmount confi guration with square and round mounting holes. The rail assemblies adjust to mount in 19” racks with a distance from front to rear around 70~76 cm (27 to 30 inches) deep.
Verify that the following rail kit items are included for each cabinet:
To assemble the components, the following tools may be needed:

CAUTION
The cabinet is heavy. Removing the cabinet from its carton requires a minimum of two people.
If installing optional EBP (S), make sure to install the EBP (S) directly below the UPS so that all wiring between the cabinets is installed behind the front covers and inaccessible to users.


4. Fix one rail assembly to the front of the rack with one M5×12 pan-head screw and one M5 cage nut. Using two M5 cage nuts and two M5×12 pan-head screws, to fi x the rail assembly to the rear of the rack. 5. Repeat Steps 3 and 4 for the other rail assembly. 6. Tighten the four butterfl y nuts in the middle of each rail assembly. 7. If installing optional cabinets, repeat Step 1 through Step 6 for each rail kit. 8. Place the UPS on a fl at, stable surface with the front of the cabinet facing to you.


9. Align the mounting brackets with the screw holes on each side of the UPS and fi x with the supplied M4×8 fl at-he- ad screws (see FIG. 5) 10. If installing optional cabinets, repeat Step 8 and 9 for each cabinet. 11. Slide the UPS and any other optional cabinets into the rack. 12. Secure the front of the UPS to the rack using one M5×12 pan-head screws and one M5 cage nuts on each side (see FIG. 6).Install the bottom screw on each side through the bottom hole of mounting bracket and the bottom hole of the rail. 13. Repeat for any optional cabinets.

This section explains:
To install the UPS:
Installing the UPS





Remarks: Please note above step 1 & 2 only for replacing batteries or adding the internal batteries. The plug will be connected properly if the UPS is with batteries installed.
3. If you are installing EBPS, see the following section, “Connecting the EBP (s),” before continuing with the UPS installation. 4. Replace the UPS front cover. To replace the cover, verify the EBP cable is routed through the knockout on the bottom of the cover if EBPS are installed. Put the front cover hooks of side with display to the cover port, put another side to the other two ports, then press it until the cover and the chassis are combined tightly. 5. If you are installing power management software, connect your computer to one of the communication ports or optional connectivity card. For the communication ports, use an appropriate cable. 6. If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the ground cable (not supplied) to the ground bonding screw. See “Rear Covers” for the location of the ground bonding screw for each model.

To install the optional EBP (s) for a UPS:
1. 1. Remove the front cover of each EBP and UPS (see FIG. 10). It is the same with the installation of the front cover. (Refer” To install the UPS “) 2. On the bottom of the UPS front cover, remove the EBP cable knockout (see FIG. 11). 3. For the bottom (or only) EBP, remove the EBP cable knockout on the top of the EBP front cover. See FIG. 12 for the location of the top EBP cable knockout. 4. If you are installing more than one EBP, for each additional EBP remove the EBP cable knockout on the top and bottom of the EBP front cover. See FIG. 12 for the location of the EBP cable knockouts.
5. Plug the EBP cable (s) into the battery connector (s) as shown in FIG. 12. Up to four EBPS may be connected to the UPS. Connect black to black,. Press the connector tightly together to ensure a proper connection. To connect a second EBP, unclip the EBP connector on the fi rst EBP and pull gently to extend the wiring to the EBP connector on the second EBP. Repeat for any additional EBPS. 6. Verify that the EBP connections are tight and the adequate bend radius and strain relief exist for each cable. 7. Replace the EBP front cover. To replace the cover, verify that the EBP cables are routed through the EBP cover knockouts, cover connects with the cover hook near the left side of the EBP cabinet. Repeat for each additional EBP. It is the same with the installation of the front cover. (Refer” to UPS installation”) 8. Verify that all wires connected between the UPS and EBP (s) are installed behind the front covers and not acces- sible to users. 9. Return to Step 4 to continue the UPS installation.




Rackmount converted to Tower plastic base installation If an EBP is needed to be placed in the middle, the assembly of plastic base is similar.
The difference is that two 1U plastic base extended boards are added in the middle. (as the following shows)


A1 - plastic base brackets
A2 - 1U plastic base bracket etended board






The installation between UPS and EBPS can be referred to Fig.16
To start up the UPS:
1. If optional EBPs are installed, verify that the EBPs are connected to the UPS. 2. Plug the equipment to be protected into the UPS, but do not turn on the protected equipment. 3. Make any necessary provisions for cord retention and strain relief. 4. Plug the detachable UPS power cord into the input connector on the UPS rear cover. 5. Plug the UPS power cord into a power outlet. The UPS front cover display illuminates. 6. The UPS will do self-test when power on. After that, the charger will charge the battery. If the output displayed on LCD is “0”, there is no output. If you need the UPS output the utility without starting the UPS when plug into the utility you need to set bPS option to “ON” on the setting mode. 7. Press the combination start up buttons on the UPS front cover for at least half a second. The UPS will start up and the LED will turn on and off sequentially. 8. Check the UPS front cover display for active alarms or notices. Resolve any active alarms before continuing. See Troubleshooting”. If the indicator is on, do not proceed until all alarms are clear.Check the UPS status from the front cover to view the active alarms. Correct the alarms and restart if necessary. 9. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loads are powe- red. 10. If optional EBPs are installed, see “Confi guring Battery settings” to set the number of installed EBPs. 11. To change any other factory-set defaults, see “User settings”.

This chapter contains information on how to use the UPS, including front cover operation, operating modes, UPS startup and shutdown, transferring the UPS between modes, and confi guring bypass settings, load segments, and battery settings.
The UPS has a three-button segmental LCD with backlight. It provides useful information about the UPS itself, load status, measurements, and settings (see FIG. 18).

Red - ON The UPS has an active alarm or fault.
Yellow - ON The UPS is in Bypass mode. The UPS is opera- ting normally on bypass during High Effi ciency operation.
Yellow - ON The UPS is in Battery mode.
Green - ON The UPS is operating normally.
Start up combination RT Press and hold this key for more than half a second to turn on the UPS or to turn off the UPS.
Shutdown/Rotating combination RT Press and hold this key for more than 2 seconds to circumrota- te the LCD.
Battery test/Mute combination Press and hold the key for more than 1 second in Line mode or economic (ECO) mode: UPS runs self-test function. Press and hold the key for more than 1 second in battery mode: UPS runs mute function.
Scroll Non-function setting mode: Press and hold the key for more than half a second (less than 2 seconds): Indicate the items of the LCD item section orderly. Press and hold this key for more than 2 seconds: Circularly and orderly display the items every 2 seconds, when press and hold the key for some time again, it will turn to output status. Function setting mode: Press and hold the key for more than half a second (less than 2 seconds): Select the set option.
Setting entry Non-function setting mode: Press and hold the key for more than 2 seconds: Function setting interface. Function setting mode: Press and hold the key for more than half a second (less than 2 seconds): Affi rm the set option. Press and hold the key for more than 2 seconds, exit from this function setting interface.
Indicator Description · Button Function description


Power up or start Six times Affi rm if the battery is connected well
Once every 2 seconds Check if the fan is blocked by object.
8 Fault mode Long beeps If display fault code and iconli- ghts, contact for maintenance when you can’t deal with it by yourself.
- indicator lights for a long time - indicator fl ashes - the status of indicator depends on other conditions

As the default or after 5 minutes of inactivity, the LCD displays the output parameters. The backlit LCD automatically dims after 5 minutes of inactivity. Press any button to restore the screen. LCD display comprises numerical value section, capacity graphics section, fan-status graphics section and charger- -status graphics section , refer to Table 4 for detail.
Numerical value section Display the corresponding numeri- cal value of inquiring items (output, load, temperature, input, battery), for example, as the graphics shows above, the output voltage is 230v, the output frequency is 50Hz.

Capacity graphics section Display the capacity of the battery and load. Every pane represents 20%capacity. As graphics shown above, the load reaches 80%-100% (5 panes), the capacity of the batte- ry is 40%-60% (3 panes). When UPS is overloaded, the icon will fl ash, when battery is weak or disconnec- ted, the icon will also fl ash.

Fan-status graphics section Display if the fan works normally. When the fan works normally, it will show the dynamic fan blades rotating; when the fan works ab- normally, the icon will keep on fl ashing with the WARNING.

Charger-status graphics section Display the status of the charger. When charger works normally, the corresponding icon will vary dynamically and orderly. when charger works abnormally, the icon will keep fl ashing When UPS is in battery mode, the number of the icons of the charger- -state section will vary according to the changeable capacity of the battery (pane).

Section Description Graphic

Press and hold the scroll key or for more than half a second (less than 2 seconds) to inquire about items. The inquired items include input, battery, output, load, temperature. Press and hold the scroll key for more than 2 seconds, LCD begins to display the items circularly and orderly which transfer to another every 2 seconds. Press and hold the key for some time again, it will return to output status.
Output Display the output voltage and output frequency of the UPS. As the following graphic shown, the output voltage is 230v & the output frequency is 50Hz.

Load Display the numerical value of the active power (WATT) and apparent power (VA) of the load. For example, as the following graphics shown: the WATT of the load is 100w, VA is 100VA (when disconnect load, it is a normal phenome- non to show a small numerical value of WATT and VA).

Temperature Display the temperature of the inverter in the UPS. As the following graphics shown: the temperature of the inverter is 37°C.

Input Display the voltage and frequency of the input. As the following graphics shown: the input voltage is 210v, input frequency is 49.8Hz.

Battery Display the voltage and capacity of the battery. As the following graphics shown: the battery voltage is 38v, the capacity of battery is 100 (the capacity of battery is approximately recko- ned according to the battery voltage).

Item Description Graphic

The UPS has setting functions. This user settings can be done under any kind of UPS working mode. The setting will take effect under certain condition. Below table describes how to set the UPS.
Table 6. User Settings
1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, the letters “ECO” will fl ash. 2. Enter the ECO setting interface. Press and hold the function setting key for more than half a second (less than 2 seconds), the letters “ECO” will stop fl ash. The “ON” (or OFF) below the ECO will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds) to determine whether the ECO function is enabled or disabled. 3. Confi rm the ECO selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the ECO setting function is completed and the “ON” or “OFF” below the “ECO” will light without fl ash. 4. If you choose “OFF”, then go to step 7, otherwise go ahead to step 5. 5. Set the ECO tolerance range. Short press the scroll keyorfor more than half a second (shorter than 2 seconds)to select the voltage range in percentage. +5%,+10%,+15%,+25% (default is +25%) then short press function setting key for more than half a second (shorter than 2 seconds)to confi rm the selection, then to set the minus range 6. To set the minus range in the same way. 7. After the minus range is confi rmed. Long press function setting key for more than 2 seconds to exit setting menu.

1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface ,short press the scroll keyfor more than half a second (less than 2 seconds) to select BPS setting, the letters “bPS” will fl ash. 2. Enter the BPS setting interface. Press and hold the function setting key for more than half a second (less than 2 seconds) at this time, the letters “bPS” will stop fl ashing. The “ON” (or OFF) below the bPS will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds) to determine whether the BPS function is enabled or disabled. 3. Confi rm the BPS selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the BPS setting function is completed and the “ON” or “OFF” below the “bPS” will light without fl ashing. 4. If you choose “OFF”, then go to step 7, otherwise go ahead to step 5. 5. Set the BPS tolerance range. Short press the scroll keyorfor more than half a second (shorter than 2 seconds)to select the voltage range in percenta- ge. +5%,+10%,+15%,+25% (default is +25%) then short press function setting key for more than half a second (shorter than 2 seconds)to confi rm the selection, then to set the minus range 6. To set the minus range in the same way. 7. After the minus range is confi rmed. Long press function setting key for more than 2 seconds to exit setting menu.

1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters “OPU” will fl ash. 2. Enter the output voltage selecting interface. Press and hold the function set- ting key for more than half a second (less than 2 seconds), then come to setting interface of output voltage OPU, at this time, the letters “OPU” will light for a long time. The numerical value below the OPU will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds), se-


lect the numerical value in accordance with “OPU” function. The provided voltages are 208v, 220v, 230v, 240,you can choose any one of them by yourself (The default is 220v). 3. Confi rm the output voltage selecting interface. After selecting numerical value, press and hold the function set- ting key for more than half a second (less than 2 seconds). Now, the OPU setting function is completed and the numerical value below the “OPU” will light without fl ashing. 4. Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the function setting, choose battery setting interface, at the moment, the letters “bAt” will fl ash. 2. Enter the battery setting interface. Press and hold the function setting key for more than half a second (less than 2 seconds), then come to setting interface of battery, the letters “bAt” will stop fl ashing. The numerical value below the “bAt” will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the numerical value in accordance with the real connected battery strings. 3. Confi rm the battery strings setting interface. After selecting numerical value, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the battery strings setting is confi rmed and the battery type value below will fl ash 4. Set the battery type in the same way. 5. Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.

1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the function setting, choose battery setting interface, at the moment, the letters “Seg 1” will fl ash. 2. Enter the load segment setting interface. Press and hold the function setting key for more than half a second (less than 2 seconds), then come to setting interface of load segment, the letters “Seg 1” will stop fl ashing. The numerical value below the “Seg 1” will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the battery voltage, 10.5v 11.0v 11.5v (default is 10.5v) 3. Confi rm the power shedding shielding battery voltage setting. After selecting numerical value, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the load shielding battery voltage setting is confi rmed. 4. Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.

1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the function setting, cho- ose EPO Input polarity setting interface, the letters “EPO” will fl ash. 2. Enter the EPO Input Polarity setting interface. Press and hold the function setting key for more than half a second (less than 2 seconds) , the letters “EPO” will stop fl ashing. The letters below the “EPO” will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the EPO input polarity, “+P” (open circuit execute EPO function) or “–P” (short circuit execute EPO function) 3. Confi rm the setting. After selecting EPO input polarity, press and hold the func- tion setting key for more than half a second (less than 2 seconds). Now, the setting is confi rmed. 4. Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.


1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the func- tion setting, choose output frequency setting interface, the letters “OPF” will fl ash. 2. Enter the output frequency of converter mode setting interface. Press and hold the function setting key for more than half a second (less than 2 seconds) , the letters “OPF” will stop fl ashing. The letters below the “OPF” will fl ash. Press and hold the scroll keyfor more than half a second (less than 2 seconds), select the output frequency, “50Hz” (output fi xed to 50Hz and active converter mode) or “60Hz” (output fi xed to 60Hz and active converter mode) or “IPF” (inactive converter mode and active normal mode) 3. Confi rm the setting. After selecting converter mode output frequency, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the setting is confi rmed. 4. Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface. IPF:UPS output frequency with the same frequency as the mains input. 50.0Hz:UPS output frequency is fi xed at 50.0Hz, independent of the mains input frequency. 60.0Hz:UPS output frequency is fi xed at 60.0Hz, independent of the mains input frequency.
Line Mode The inverter green LED is on.
When input AC mains is in line with the working conditions, UPS will work in line mode,charge the battery and protect the load.
Both the inverter green LED and battery yellow LED are on, the buzzer beeps once every 4 seconds. The WARNING red LED is on when beeping.
When the mains power down or instable, UPS will turn to battery mode at once. If the mains recovers,the UPS will transfer to line mode.
If battery low alarm activates, the indicator of fl ashes. If battery voltage reaches low limit, UPS will turn off to protect the battery. UPS will auto-restart when the mains recover.
Bypass yellow LED is on, the buzzer beeps once every 2 minutes. The WARNING red LED is on when beeping, LCD displays are accor- ding to the exact load and battery capacity. Bypass tolerance can be set by LCD. Under below conditions, the UPS will transfer to bypass mode:
ECO Mode Both the inverter green LED and bypass yellow LED are on.
When ECO enabled and the utility is in range, the UPS will work on ECO mode. If the utility in out of ECO range but still in Line range, the UPS will transfer to line mode.
Utility tolerance of ECO mode can be set.
Battery Mode · Bypass Mode


When the UPS has fault. The WARNING red LED is on and the buzzer beeps. The UPS will turn to fault mode. The UPS cuts off the output and the LCD display fault codes. At the moment, you can press the mute key to make the buzzer stop beeping temporarily to wait for maintenance. You can also press the OFF key to shut down the UPS when confi rm that there is no serious fault.
When UPS is plugged into line and not turn on , the UPS will work in standby mode to charge the battery. No indicator displays on this mode.
Turn on the UPS in line mode
1. Once mains power is plugged in, the UPS will charge the battery, at the moment, the LCD shows that the output voltage is 0, which means the UPS has no output. If it is expected to have the output of bypass, you can set the bps “ON” by LCD setting menu. 2. Press and hold the ON key for more than half a second to start the UPS, then it will start the inverter. 3. Once started, the UPS will perform a self-test function, LED will light and go out circularly and orderly. When the self-test fi nishes, it will come to line mode, the corresponding LED lights, the UPS is working in line mode.
Turn on the UPS by DC without mains power
Turn off the UPS in line mode
Turn off the UPS by DC without mains power
UPS self-test/mute test operation
1. When the UPS is in line mode, press and hold the self-test/mute key for more than 1 second, the LEDs light and go out circularly and orderly. The UPS comes to self-test mode and tests its status. It will exit automatically after fi nishing testing, and the LED indication will go back to previous status. 2. When the UPS is in battery mode, press and hold the self-test/mute key for more than 1 second, the buzzer stops beeping. If you press and hold the self-test/mute key for one more second, it will restart to beep again.
Fault Mode · Standby Mode

CONFIGURING BATTERY SETTINGS Set the UPS for the number of EBPs installed. To ensure maximum battery runtime, confi gure the UPS for the correct number of EBPs, refer to Table 8 for the appropriate setting of battery numbers and type. Use the up and down scroll keys to select the number of battery strings according to your UPS confi guration:
All UPS and EBP Cabinets Number of Battery Strings
UPS only (internal batteries) 1 (default)
UPS+2EBP 5
UPS+3EBP 7
UPS+4EBP 9
This section describes the:



Installing Communication Options and Control Terminals
To install the communication options and control terminals:
The UPS has serial communication capabilities through the USB and RS-232 communication ports or through a con- nectivity card in the available communication bay. The UPS supports two serial communication devices according to the following table:
Communication Bay USB RS-232
Any connectivity card Available Not in use
Not in use Available

To establish communication between the UPS and a computer, connect your computer to one of the UPS communication ports using an appropriate communication cable (not supplied). See FIG. 19, 20 for the communication port locations.
When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment. The cable pins for the RS-232 communication port are identifi ed in FIG. 21 and the pin functions are described in Table 9.
Pin Number Function Defi nition Direction from the UPS
1/4/6/7/8/9 No use -
2 RxD (Transmit to external device) Out
3 TxD (Receive from external device) In
5 GND (Signal cimmon) -
Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The UPS has one available communication bay for the following connectivity cards:
See FIG. 19, 20 for the location of the communication bay.
Communication Options · Independent Multiplxed


EPO is used to shut down the UPS from a distance. This feature can be used for shutting down the load and the UPS by thermal relay, for instance in the event of room overtemperature. When EPO is activated, the UPS shuts down the output and all its power converters immediately. The UPS remains on to alarm the fault.
There is also a front panel EPO option for user to initial EPO function by pressing the three switch on the front panel together. When the three switches is pressed down at the same time, the EPO function will be active, UPS will shut down and the buzzer will long beep. Pressing startup switches will not turn on the UPS unless the EPO function is deactivated by pressing the three switches together and press off switches to return normal status.
Wire Function Terminal Wire Size Rating Suggested Wire Size
EPO L1 4–0.32 mm2 (12–22 AWG) 0.82 mm2 (18 AW)
See FIG. 19, 20 for EPO location. FIG. 23 shows a schematic of the EPO connector contacts.
2 - POLARITY EPO
Abb. 23 EPO Connections
EPO Connections


Load segments are sets of receptacles that can be controlled by power management softwa- re or through the display, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep critical equipment running while you turn off other equipment. This feature allows you to save battery power.
Each UPS has two load segments:
FIG 24 Load Segments
Each UPS ships with UPSilon2000 Power Management Software. To begin installing UPSilon2000 software, see the instructions accompanying the Software Suite CD.
UPSilon2000 software provides up-to-date graphics of UPS power and system data and power fl ow. It also gives you a complete record of critical power events, and it notifi es you of important UPS or power information. If there is a power outage and the UPS battery power becomes low, UPSilon2000 software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
This section explains how to:
For the best preventive maintenance, keep the area around the UPS clean and dust‐free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the UPS at an ambient tempe- rature of 25°C (77°F).
If you store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The internal batteries charge to 80% capacity in less than 5 hours. However, we recommends that the batteries charge for

48 hours after long-term storage. If optional EBPs are installed, see the recharge times listed in Table 21. Check the battery recharge date on the shipping carton label. If the date is expired and the batteries were never recharged, do not use the UPS. Contact your service representative.
The EBP can be replaced when UPS is ON but be aware that if the utility fails at that time , the load of the UPS may NOT be protected. If you prefer to remove input power to change the batteries, see “UPS Turn on and Turn off”.
1. If the battery fault, the following steps are provided for modular unit to replace the new battery pack 2. Remove the front cover of the battery box. 3. Remove the connection cables between battery box and UPS. Release the screw of the baffl e of the battery pack as the Fig.25 shows, then remove the baffl e from the left or right. 4. Grasp the handle in front of the battery pack, take out of it and hold it, then remove the battery pack as fi g. 26 shown. 5. Hold the middle of the new battery pack, insert it. Once install the new battery pack, make sure it is completely inserted into the chassis as fi g 27 shown.
To test new batteries:
1. Plug the UPS into a power outlet for 48 hours to charge the batteries. 2. Start up the UPS by pressing the start up combination button. 3. Press the battery test combination button to activate the battery test. The UPS starts a battery test if the batteries are fully charged, the UPS is in Normal mode with no active alarms, and the bypass voltage is acceptable. During the battery test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds. The LED indicators of the front cover stop cycling when the test is completed.
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS.





This section provides the following specifi cations:
Table 10:Communication Options (All Models)

Communica tion Bay available independent communication bay for connectivity cards

EBP Model Confi guration Battery Voltage For Power Ratings




Frequency Range 45–55 Hz (50Hz)/55-65Hz (60Hz) before transfer to battery
Bypass Voltage Range +5%,+10%,+15%,+25% (+25% by default),-20%,-30%,-45% (-45% by default)

Model Default Input Voltage/Current Selectable Input Voltages Voltage Range at 100% Load
1KVAS/1KVAH 230V / 4.4A 200, 208, 220, 230, 240 160 - 290Vac
1.5KVAS/1.5KVAH 230V / 6,5A 200, 208, 220, 230, 240 160 - 290Vac
2KVAS/2KVAH 230V / 8,7A 200, 208, 220, 230, 240 160 - 290Vac
3KVAS/3KVAH 230V / 13,0A 200, 208, 220, 230, 240 160 - 290Vac


108%±5%–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
100%±5%–130%±5%: Load transfers to Fault mode after 20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode after 2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode after 15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.


108%±5%–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Harmonic Distortion


Operating Temperature 0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude

Storage Temperature -20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 0–90% noncondensing
Operating Altitude Up to 3,000 meters (9,843 ft) above sea level
FIG 29
8 Troubleshooting
The following messages are the information that users would fi nd on UPS when it meets some problems. Users can judge if the fault is caused by external factors and know how to deal with it by making full use of the information.
Fault indicator on, indicates that the UPS has detected some faults. Buzzer beeps, indicates that UPS need to be paid attention to, if beeps for a long time, it means that there is something wrong with the machine. If you need help, contact our service department, the following messages should be provided for analysis:
Following table describes typical alarm conditions.

The “INPUT” letters on LCD display section fl ashes
Anti-connection of mains live and neutral or mains is out of range
Re-connect the input power cable and make a correct connection
Battery capacity indicator fl ashes Battery low voltage or battery disconnected
Check UPS battery, connect battery well, if battery damaged, replace it
Mains normal, but UPS has no input UPS input breaker open circuit Press the breaker for reset
Short back up time Battery not fully charged Keep UPS connecting with mains power for more than 8 hours, recharge battery
UPS overload Check the usage of loads, remove some redundant devices
Battery aged When replace battery, contact franchiser to get battery and relative assembly
UPS doesn’t startup after pressing the ON key
Didn’t press the combination keys of “on”
Press the two keys at the same time
UPS has no battery connected or battery voltage low and too many loads connected
Connect UPS battery well, if battery voltage low, please turn off UPS and remove some loads, then start UPS
Fault occurs inside UPS Contact supplier for servicing
The icon of charger status on LCD display fl ashes and buzzer beeps once per second
Charger doesn’t work normally or battery aged
Contact supplier for servicing
Table 23 · Fault Cause Solution


Voltage error High positive voltage 5 1 40 80