Offizielle Bedienungsanleitung

Makita EG5550A

112 Seiten·2.9 MB·Generator·PDF·ENJA
Makita EG5550A
Inhaltsverzeichnis 38 Abschnitte EG2250A EG2850A EG4550A EG5550A EG6050A · GB Petrol Generator · Instructions for Use · F Groupe Electrogène Manuel d'instructions · … AnzeigenAusblenden
Page 1 of the Makita EG5550A user manual — GB Petrol Generator
Seite 1 · Zum Vergrößern klicken
Seite 1

EG2250A EG2850A EG4550A EG5550A EG6050A

GB Petrol Generator

Instructions for Use

F Groupe Electrogène Manuel d'instructions

D Generator Betriebsanleitung

I Generatore a benzina Istruzioni per l’utilizzo

NL Gebruiksaanwijzing

Benzinegenerator

E Generador a gasolina Manual de instrucciones

Makita EG5550A — GB Petrol Generator diagram (page 1)
Abb. 1 · GB Petrol Generator
Page 2 of the Makita EG5550A user manual — O
Seite 2 · Zum Vergrößern klicken
Seite 2

1 2 3 4

Makita EG5550A — 24 O I S diagram (page 2)
Abb. 2
Makita EG5550A — 24 O I S diagram (page 2)
Abb. 3
Makita EG5550A — 24 O I S diagram (page 2)
Abb. 4
Makita EG5550A — 24 O I S diagram (page 2)
Abb. 5

O

24 O I S

EG2250A EG2850A EG4550A, EG5550A, EG6050A

Makita EG5550A — O diagram (page 2)
Abb. 6
Makita EG5550A — O diagram (page 2)
Abb. 7
Makita EG5550A — O diagram (page 2)
Abb. 8
Makita EG5550A — O diagram (page 2)
Abb. 9
Page 3 of the Makita EG5550A user manual — 24 O I S
Seite 3 · Zum Vergrößern klicken
Seite 3
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 10
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 11
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 12
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 13
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 14
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 15
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 16
Makita EG5550A — 24 O I S diagram (page 3)
Abb. 17

38 39 39

Page 4 of the Makita EG5550A user manual — 24 O I S
Seite 4 · Zum Vergrößern klicken
Seite 4
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 18
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 19
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 20
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 21
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 22
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 23
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 24
Makita EG5550A — 24 O I S diagram (page 4)
Abb. 25
Page 5 of the Makita EG5550A user manual — 24 O I S
Seite 5 · Zum Vergrößern klicken
Seite 5
Makita EG5550A — 24 O I S diagram (page 5)
Abb. 26
Makita EG5550A — 24 O I S diagram (page 5)
Abb. 27
Makita EG5550A — 24 O I S diagram (page 5)
Abb. 28
Page 6 of the Makita EG5550A user manual — Explanation of general view
Seite 6 · Zum Vergrößern klicken
Seite 6

ENGLISH (Original instructions)

Explanation of general view

1. CONTROL PANEL 2. FUEL GAUGE 3. FUEL TANK CAP 4. ENGINE SWITCH 5. CHOKE LEVER 6. AIR CLEANER 7. FUEL VALVE LEVER 8. STARTER GRIP 9. ENGINE SERIAL NUMBER 10. OIL FILLER CAP/DIPSTICK 11. AC CIRCUIT PROTECTORS 12. AC CIRCUIT BREAKER 13. DC CIRCUIT PROTECTOR 14. DC OUTPUT TERMINAL 15. 230V AC RECEPTACLE (Shape of socket varies by country) 16. GROUND TERMINAL
17. MUFFLER 18. WHEEL 19. STAND 20. TRANSPORT HANDLE 21. SPARK PLUG CAP 22. I (ON) 23. O (OFF) 24. S (START) 25. ON 26. OFF 27. RECOIL STARTER 28. OPEN 29. CLOSED 30. NEGATIVE TERMINAL (BLACK) 31. POSITIVE TERMINAL (RED) 32. OIL FILLER HOLE 33. OIL LEVEL
34. UPPER LIMIT MARK 35. SEALING WASHER 36. OIL DRAIN PLUG 37. AIR CLEANER COVER 38. KNOB 39. ELEMENT 40. Properly hooked 41. Improperly hooked 42. SPARK PLUG WRENCH 43. Pipe Clamp 44. Spark arrest screen 45. Drain screw 46. Pilot lamp 47. Oil level warning lamp 48. Voltage meter 49. Current meter
  • ABOUT SAFETY The safety of the operator and others are extremely important and using this generator safely is an important responsibility. In order to make informed decisions about safety, operating procedures and other information are provided in this manual and on the labels on the generator. This information alerts the operator to potential hazards that may hurt the operator or others. As it is not practical or possible to warn you about all the hazards associated with operating or maintaining a generator, always use your own good judgment. Important safety information can be found in the following forms:
  • Safety Labels — on the generator.
  • Safety Messages — preceded by a safety symbol and one of three signal words (DANGER, WARNING, or CAUTION). These signal words mean:

WARNING: The generator is a potential source of electrical shock if misused. Do not expose the generator to moisture, rain or snow. Do not let the generator get wet, and do not operate it with wet hands. Keep this instruction manual handy for future reference. This instruction manual is considered a permanent part of the generator and should remain with the generator if resold. All information and specifications included in this publication were based on the latest production information at the time of approval for printing. Makita Corporation reserves the right, however, to discontinue or change specifications or design at any time without notice and without incurring any obligation whatsoever. No part of this publication may be reproduced without written permission.

  • CAUTION: Indicates that personal injury can result if instructions are not followed.
  • Safety Headings — such as IMPORTANT SAFETY INFORMATION.
  • Safety Section — such as GENERATOR SAFETY
  • Instructions — how to use this generator correctly and safely. Important safety information is provided throughout this manual. Read it carefully.
Page 7 of the Makita EG5550A user manual — GENERATOR SAFETY
Seite 7 · Zum Vergrößern klicken
Seite 7

GENERATOR SAFETY

SYMBOLS and MEANINGS In accordance with the European requirements (eec Directives), the specified symbols as shown in the following table are used for the products and this instruction manual.

Makita EG5550A — GENERATOR SAFETY diagram (page 7)
Abb. 29

Read the operator’s instruction manual.

Fire, open light and smoking prohibited.

Stay clear of the hot surface.

Do not connect the generator to the commercial power lines.

Exhaust gas is poisonous. Do not operate in an unventilated room.

Stop the engine before refueling.

Call for maintenance.

Keep dry.

  • If the generator is stored outdoors and is unprotected from the weather, check all of the electrical components on the control panel before each use. Moisture or ice can cause a malfunction or short circuit in the electrical components which may result in electrocution.
  • Do not connect the generator to a building’s electrical system unless an isolation switch has been installed by a qualified electrician.
  • Responsibilities of the Operator
  • The operator must know how to quickly stop the generator in case of an emergency.
  • The operator must have knowledge of the use of all generator controls, output receptacles, and connections.
  • The operator must make sure that anyone who operates the generator receives proper instruction. Do not let children operate the generator without parental supervision.

Fire and Burn Hazards • The exhaust system can become hot enough to ignite flammable materials.

  • - Keep the generator at least 3 feet (1 meter) away from structures or buildings and other equipment during use. - Do not enclose the generator in any structure. - Keep flammable materials away from the generator.
  • The muffler becomes very hot during operation and remains hot for a while after the engine is stopped. Be careful not to touch the muffler while it is hot. When storing the generator indoors, allow the engine cool before it is stored.
  • Gasoline is extremely flammable and is explosive under certain conditions. Do not smoke while refueling the generator or near where gasoline is stored. Keep flames/sparks away from where the generator is refueled or where gasoline is stored. Refuel in a wellventilated area with the engine stopped.
  • Fuel vapors are extremely flammable and may ignite after the engine is started. If fuel is spilled, wipe it up and let dry before starting the generator.
  • Carbon Monoxide Hazards
  • Exhaust from this generator poisonous carbon monoxide, a colorless and odorless gas. Inhaling carbon monoxide can cause loss of consciousness and may lead to death.
  • If the generator is operated in a closed or partially closed area, the air may contain a dangerous amount of exhaust gas.
  • Never run the generator inside a garage, house, or near open windows or doors.
  • Electric Shock Hazards
  • The generator produces enough electric power to cause a serious electrical shock or electrocution if misused.
  • Do not use the generator or an electrical appliance in wet conditions, such as rain or snow, or near a pool or sprinkler system, or with wet hands. Such action may result in electrocution. Keep the generator dry.

Other Safety Information: • Personal protective equipment is required for any operation and maintenance.

Gasoline

Page 8 of the Makita EG5550A user manual — CONTROLS
Seite 8 · Zum Vergrößern klicken
Seite 8
  • The load must be kept within the rating stated on generator rating plate. Overloading the generator will damage the unit or shorten its life.
  • The generator must not be run at excessive speeds. Operation at excessive speeds will increase the hazards of personal injury.
  • Do not modify parts which may increase or decrease the governed speed.
  • Only use extension cords that are grounded and are a sufficient wire gauge for the application. When using an extended wire or a mobile electric net, if the wire diameter is 1.5 mm 2 , it cannot exceed the length of 60 m. If the wire diameter is 2.5 mm 2 , it cannot exceed the length of 100 m.
  • The exhaust system can become hot enough to ignite flammable materials. Do not operate the engine near flammable materials. Do not use the generator in damp conditions.
  • Do not store fuel indoors or try to refuel a generator while it is running.
  • Do not cover unit while it is being used.
  • To prevent poisoning or fire when operating, never use the generator in close proximity to flammable materials.
  • The unit must reach the operating speed before the electrical loads are connected. Disconnect the load before turning off the generator. Turn off all of the equipment powered by the generator before shutting down the generator. The unit should not be connected to other power supply outlets.
  • Protection against electrical shock is dependent on the circuit breakers specially matched to the generating set. If the circuit breaker requires replacement contact a local retailer for replacement with a circuit breaker having identical rating and performance characteristics.
  • Ensure that the generator does not have any damaged hoses, loose or missing clamps, damaged tank or cap before use. All defects should be corrected before use.
  • The installation and major repair of the generator can only be conducted by specially trained people. Before transporting the generator, drain all fuel to prevent leakage.
  • Store the generator in a well-ventilated area with the fuel tank empty.

Key position: O (OFF): Stops the engine. Key can be removed or inserted. I (ON): Runs the engine after starting. S (START): Starts the engine by operating the starter motor. *EG2250A and EG2850A equipped with I (ON)/O (OFF) switch only

Starter Grip (Fig. 5) To start the engine, pull the starter grip slowly until resistance is felt and then pull swiftly.

NOTICE: Return the starter grip back gently to prevent damage to the starter. Do not allow it to snap back against the engine. If the generator is not equipped with a 12-volt battery to operate the starter motor or if the battery does not contain enough charge to operate the starter motor, the recoil starter is used to start the engine.

Fuel Valve Lever (Fig. 6) The fuel valve is located between the fuel tank and carburetor. Fuel is allowed to flow from the fuel tank to the carburetor when the valve lever is in the “I (ON)” position. Return the fuel valve lever to the “O (OFF)” position after stopping the engine.

Choke Rod (Fig. 7) The choke is used to provide an enriched fuel mixture when starting a cold engine. Operate the choke rod manually to open and close the choke. Pull the rod out toward “CLOSED” to enrich the mixture for cold starting.

Ground Terminal (Fig. 8) The generator ground terminal is connected to the generator frame, the generator’s metal non-current- carrying parts, and each receptacle’s the ground terminals. Before using the ground terminal, consult a qualified electrician, an electrical inspector, or a local agency having jurisdiction for local codes or ordinances that apply to the intended use of the generator.

COMPONENTS (Fig. 1)

DC Terminals The DC terminals are used only for charging 12-volt automotive type batteries. The terminals are colored red and black to identify the positive (+) and negative (-) terminals, respectively. Make sure to connect the battery to the generator DC terminals with the correct polarity (battery positive to the generator red terminal and battery negative to the generator black terminal).

CONTROL PANEL (Fig. 2 & Fig. 3)

*Keep a record of the engine and frame serial numbers and the date of purchase for your future reference. Refer to these serial numbers when ordering parts and when making technical or warranty inquiries. Date of purchase: Engine serial number: Frame serial number:

DC Circuit Protector (Fig. 9) When the DC charging circuit is overloaded, there is a problem with the battery, or the connections between the battery and the generator are incorrect, the DC circuit protector automatically shuts off the DC battery charging circuit.

CONTROLS

Engine Switch (Fig. 4) Starts and stops the engine.

Page 9 of the Makita EG5550A user manual — GENERATOR USE
Seite 9 · Zum Vergrößern klicken
Seite 9

Oil Alert System (Fig. 14) The engine can be damaged if there is an insufficient amount of oil in the crankcase. The Oil Alert system prevents this from happening by automatically stopping the engine before the oil level in the crankcase falls below the safe limit (the engine switch will remain in the “I (ON)” position). When the oil alert system works, the oil level warning lamp lights up in red. The oil level should always be checked before each use, regardless of this Oil Alert system. If the engine stops and fails to restart, check the engine oil level before troubleshooting in other areas.

system ground is not connected to the AC neutral wire, if the generator is tested by a receptacle tester, it will show the same ground circuit condition as for a home receptacle.

  • AC Applications Before connecting an appliance or power cord to the generator:
  • Make sure that it is in good working condition. Faulty appliances or power cords can cause electrical shock.
  • If an appliance begins to operate in an abnormal manner, becomes slow, or stops suddenly, turn it off immediately. Disconnect the appliance, and determine whether there is a problem with the appliance or if the rated load capacity of the generator has been exceeded.
  • Make sure that the electrical rating of the tool or appliance does not exceed the generator’s rating. Never exceed the maximum power rating of the generator. Power levels between rated and maximum may be used for no more than one hour.

AC Circuit Breaker (Fig. 10) The AC circuit breaker automatically turns off if there is a short circuit or a significant overload of the generator at the receptacle. If the AC circuit breaker is turns off automatically, make sure that the appliance is working correctly and does not exceed the rated load capacity of the circuit before turning on the AC circuit breaker again. The AC circuit breaker may be used to turn the generator power on or off.

NOTICE: Substantial overloading will turn off the circuit breaker. Exceeding the time limit for maximum power operation or slightly overloading the generator may not turn off the circuit breaker or circuit protector, but will shorten the service life of the generator. Limit operation requiring maximum power to one hour. Maximum power is as follows: EG2250A: 2.2 kW EG2850A: 2.8 kW EG4550A: 4.5 kW EG5550A: 5.5 kW EG6050A: 6.0 kW For continuous operation, do not exceed the rated power. Rated power is as follows: EG2250A: 2.0 kW EG2850A: 2.6 kW EG4550A: 4.0 kW EG5550A: 5.0 kW EG6050A: 5.5 kW The total power requirements (VA) of all appliances connected to the generator must be considered. Rating information for appliances and power tools are usually listed near the model number or serial number.

AC Circuit Protector (EG4550A, EG5550A, EG6050A only) (Fig. 11) The AC circuit protectors automatically turn off if there is a short circuit or a significant overload of the generator at the 26A 230V. If an AC circuit protector turns off automatically, make sure that the appliance is working correctly and does not exceed the rated load capacity of the circuit before resetting the AC circuit protector on.

GENERATOR USE

Connections to a Building’s Electrical System A qualified electrician must make the connections for standby power to a building’s electrical system. Make sure that the connection isolates the generator power from the utility power, and complies with all applicable laws and electrical codes. A transfer switch, which isolates generator power from utility power, can be purchased through authorized Makita generator dealers.

AC Operation (Fig. 12) 1. Start the engine. 2. Turn on the AC circuit breaker. 3. Plug in the appliance.

WARNING: Electrical current from the generator may backfeed into the utility lines if connections to a building’s electrical system are made improperly. Such backfeed may electrocute utility company workers or others who come into contact with the lines during a power outage, and the generator may explode, burn, or cause fires when the utility power is restored. Consult the utility company or a qualified electrician.

NOTICE: Before connecting any appliance to the generator, make sure they are in good working condition. If an appliance begins to operate in an abnormal manner, becomes slow, or stops suddenly, turn off the ignition switch lever immediately. Then disconnect the appliance and check for signs of malfunction. Most motorized appliances require more than their rated power for startup. Do not exceed the current limit specified for any one receptacle. If an overloaded circuit causes the AC circuit breaker or AC circuit protector to turn off, reduce the

Ground System Makita portable generators are equipped with a system ground that connects generator frame components to the ground terminals in the AC output receptacles. Since the

Page 10 of the Makita EG5550A user manual — PRE-OPERATION CHECKS
Seite 10 · Zum Vergrößern klicken
Seite 10

electrical load on the circuit, wait a few minutes and then reset the AC circuit breaker or AC circuit protector.

made in the carburetor, the effect of altitude on horsepower will be even greater. High altitude performance can be improved by making specific modifications to the carburetor. If the generator is to always be operated at altitudes above 5,000 feet (1,500 meters), have your dealer perform this carburetor modification. This engine, when operated at high altitudes with the carburetor modifications for high altitude use, will meet the various emission standards throughout its useful life.

DC Operation The DC terminals are used only for charging 12-volt automotive type batteries.

Connecting the battery charging cables: 1. Before connecting the battery charging cables to a battery that is installed in a vehicle, disconnect the vehicle ground battery cable from the negative (-) terminal of the battery.

NOTICE: When the carburetor has been modified for high altitude operation, the air-fuel mixture will be too lean for use at low altitudes. Operation at altitudes below 5,000 feet (1,500 meters) with a modified carburetor may cause the engine to overheat and result in serious engine damage. For low altitude use, have your servicing dealer return the carburetor to the original factory specifications.

WARNING: The battery gives off explosive gases. Keep sparks, flames, and cigarettes away. Provide adequate ventilation when charging or using batteries. WARNING: Lead and lead components are used in battery posts, terminals, and related accessories. Always wash hands after handling. 2. Connect the positive (+) battery cable to the positive (+) terminal of the battery. 3. Connect the other end of the positive (+) battery cable to the positive (+) terminal of the generator. 4. Connect the negative (-) battery cable to the negative (-) terminal of the battery. 5. Connect the other end of the negative (-) battery cable to the negative (-) terminal of the generator. 6. Start the generator.

PRE-OPERATION CHECKS

Check Engine Oil (Fig. 13) Check the oil level before each use with the engine stopped and the generator on a stable and level surface. Use 4-stroke motor oil that meets or exceeds the requirements for API Service Category SJ or later (or equivalent). Always check the API SERVICE label on the oil container to be sure the letters SJ or later (or equivalent) are indicated. 1. Remove the oil filler cap/dipstick and wipe the dipstick clean. 2. Insert the dipstick into the filler neck and check the oil level. Do not screw in the filler cap. 3. If the oil level is low, fill to the upper limit of the oil filler neck with the recommended oil.

NOTICE: Do not start the vehicle while the battery charging cable is connected and the generator is running. Doing so may damage the vehicle or the generator. The DC circuit protector will be tripped (the “PUSH” button will extend out), if the DC circuit is overloaded, excessive current is drawn by the battery, or a wiring problem occurs. If this happens, wait a few minutes before pushing in the circuit protector to resume operation. If the DC circuit protector continues to go off, discontinue charging and consult your authorized Makita generator dealer.

Check Engine Fuel (Fig. 14) With the engine stopped, check the fuel level gauge. Refill the fuel tank if the fuel level is low.

Disconnecting the battery cables: 1. Stop the engine. 2. Disconnect the negative (-) battery cable from the negative (-) terminal of the generator. 3. Disconnect the other end of the negative (-) battery cable from the negative (-) terminal of the battery. 4. Disconnect the positive (+) battery cable from the positive (+) terminal of the generator. 5. Disconnect the other end of the positive (+) battery cable from the positive (+) terminal of the battery. 6. Reconnect the vehicle ground battery cable to the negative (-) terminal of the battery.

  • WARNING: Gasoline is highly flammable and explosive. Burns or severe personal injury may result from handling fuel.
  • Stop the engine and keep heat, sparks, and flames away.
  • Refuel only outdoors.
  • Wipe up spills immediately. Refuel in a well-ventilated area with the engine stopped. Allow the engine to cool first if it has been running. Refuel carefully to avoid spilling fuel. Do not fill above the upper limit mark. Never refuel the engine inside a building where gasoline fumes may reach flames or sparks. Keep gasoline away from appliance pilot lights, barbecues, electric appliances, power tools, etc. Spilled fuel is a fire hazard and causes environmental damage. Be sure to wipe up spills immediately.

High Altitude Operation At high altitudes, the standard carburetor air-fuel mixture will be too rich, and will cause performance to decrease and fuel consumption to increase. A very rich mixture will also foul the spark plug and cause hard starting. Operation for extended periods of time at an altitude that differs from the altitude at which this engine was certified may increase emissions. Engine horsepower decreases about 3.5% for every 1,000-foot (300-meter) increase in altitude, even with carburetor modification. If no carburetor modification is

Page 11 of the Makita EG5550A user manual — MAINTENANCE
Seite 11 · Zum Vergrößern klicken
Seite 11

Recommended Fuels This engine is certified to operate on regular unleaded gasoline with a pump octane rating of 86 or higher. Never use stale or contaminated gasoline or an oil- gasoline mixture. Avoid getting dirt or water in the fuel tank. Regular unleaded gasoline containing no more than 10% ethanol (E10) or 5% methanol by volume can be used. In addition, the methanol must contain cosolvents and corrosion inhibitors. If fuels containing levels of ethanol or methanol greater than those shown above are used, starting and/or performance problems may occur. The metal, rubber, and plastic parts of the fuel system may also be damaged. Engine damage or performance problems resulting from the use of fuel with percentages of ethanol or methanol greater than the values shown above are not covered by the warranty.

  • NOTICE:
  • The motor can be damaged if the starter motor is operated for more than 5 seconds. If the engine fails to start, release the switch and wait 10 seconds before operating the starter again.
  • If the speed of the starter motor drops after a period of time, it is an indication that the battery should be recharged. When the engine starts, allow the engine switch to return to the “I (ON)” position. If the choke was manually closed, push it to the “OPEN” position as the engine warms up.

Stopping the Engine

In an emergency: To stop the engine in an emergency, move the engine switch to the “O (OFF)” position.

In normal use: 1. Turn the AC circuit breaker to the “O (OFF)” position. Disconnect the DC battery charging cables. 2. Turn the engine switch to the “O (OFF)” position. 3. Turn the fuel valve lever to the “O (OFF)” position.

STARTING/STOPPING THE ENGINE

Starting the Engine For safety reasons, do not operate the generator in an enclosed area such as a garage. The generator’s exhaust contains poisonous carbon monoxide gas that can collect rapidly in an enclosed area and cause illness or death.

MAINTENANCE

The Importance of Maintenance Good maintenance is vital to the safe, economical, and trouble free operation of the generator. It will also help reduce air pollution.

WARNING: Exhaust from the generator contains poisonous carbon monoxide gas that can build up to dangerous levels in closed areas. Inhaling carbon monoxide can cause unconsciousness or death. Never run the generator in a closed or partially closed area where people may be present. To prevent fires, keep the generator at least 3 feet (1 meter) away from buildings and other structures during operation. Keep flammable objects away from the engine.

WARNING: Improper maintenance, or failure to correct a problem before operation, can cause a malfunction which can result in severe personal injury or loss of life. Always follow the inspection and maintenance recommendations and schedules in this instruction manual. The following pages include a maintenance schedule, routine inspection procedures, and simple maintenance procedures using basic hand tools required for properly caring for the generator. Other service tasks that are more complicated or require special tools are best handled by professionals and are normally performed by a Makita technician or other qualified mechanic. The maintenance schedule included in this manual is based on normal operating conditions. If the generator is operated under severe conditions, such as sustained high-load or high-temperature operation, or it is used in unusually wet or dusty conditions, consult your servicing dealer for recommendations applicable to your specific needs and use. Maintenance, replacement, or repair of the emission control devices and systems may be performed by any nonroad engine repair establishment or individual, using parts that are ‘‘certified’’ to EPA standards.

NOTICE: Do not operate this generator less than 3 feet (1 meter) from a building or other obstruction. Doing so can cause overheating and/or damage the generator. In order to maintain proper cooling, allow at least 3 feet (1 meter) of empty space above and around the generator. Refer to the “AC OPERATION” or “DC OPERATION” of this manual for how to connect loads to the generator. 1. Perform the PRE-OPERATION CHECKS. 2. Make sure that the AC circuit breaker is in the “O (OFF)” position. It may be difficult to start the generator if a load is connected. 3. Turn the fuel valve lever to the “I (ON)” position. 4. Turn the engine switch to the “I (ON)” position. 5. Pull the starter grip slowly until resistance is felt, then pull swiftly.

Maintenance Safety The following are some of the most important safety precautions. However, we cannot cover every conceivable hazard that can arise in performing maintenance, so please remember that only you can decide whether or not you should perform a given task.

Page 12 of the Makita EG5550A user manual — REGULAR SERVICE PERIOD *3
Seite 12 · Zum Vergrößern klicken
Seite 12
  • - Injury from moving parts. Do not run the engine unless instructed to do so.
  • Read the instructions before you operate the generator, and make sure you understand the instructions and have the tools and skills required.
  • To reduce the possibility of fire or explosion, be careful when working around gasoline. Use only a nonflammable solvent, not gasoline, to clean parts. Keep cigarettes, sparks, and flames away from all fuelrelated parts. Remember that your servicing dealer knows your generator best and is fully equipped to maintain and repair it. To ensure the best quality and reliability, use only new, genuine Makita parts or their equivalents for repair or replacement.

Safety Precautions • Make sure the engine is off before beginning any maintenance or repairs. This will eliminate several potential hazards:

- Carbon monoxide poisoning from engine exhaust. Operate outside away from open windows or doors. - Burns from hot parts. Let the engine and exhaust system cool before touching.

Maintenance Schedule

REGULAR SERVICE PERIOD *3

MAINTENANCE ITEMS Perform at every indicated month or operating hour interval, whichever comes first.

Every 3 months or

Every 6 months or

Each use First month

Every year or 300 hrs.

or 20 hrs.

50 hrs.

100 hrs.

Engine oil Check level c

Air Cleaner Check c

Sediment cup Clean c

Spark plug Check-adjust c

Spark arrester Clean c c*2

Valve clearance Check-adjust c*2

Clean After every 500 hrs. *2

Fuel tank and filter

Fuel tube Check Every 2 years (Replace if necessary) *2

*1: Service more frequently when using the generator in dusty, dirty or severe environments. *2: Unless the owner has the proper tools and is mechanically proficient, this item should be serviced by an authorized Makita generator dealer. Refer to the Makita Shop Manual. *3: For commercial use, hours of operation should be logged to determine proper maintenance intervals. Failure to follow this maintenance schedule may result in non-warrantable malfunctions.

Engine Oil Change (Fig. 15) Drain the oil while the engine is warm to assure quick and complete draining. 1. Place a suitable container below the engine to catch the oil. 2. Drain the oil by removing the oil drain plug, the sealing washer, and the oil filler cap/dipstick. 3. Reinstall the oil drain plug and a new sealing washer and firmly tighten the plug. 4. Refill with the recommended oil and check the oil level. Wash your hands with soap and water after handling used oil.

NOTICE: Improper disposal of used engine oil can be hazardous to the environment. Before changing the oil, check for a suitable way to dispose of the used oil. Do not discard it in a trash bin, pour it down a drain, or dump it on the ground. Your local zoning or environmental regulations will give you more detailed instructions on proper disposal.

Air Cleaner Service (Fig. 16 & Fig. 17) A dirty air cleaner will restrict air flow to the carburetor. To prevent carburetor malfunction, clean the air cleaner regularly. Clean more frequently when operating the generator in extremely dusty areas.

Show 6 more labels / short text on this page
Change c c · Clean c*1 · Replace c · Idle speed Check-adjust · Combustion chamber · Clean c*2
Page 13 of the Makita EG5550A user manual — Fuel
Seite 13 · Zum Vergrößern klicken
Seite 13

NOTICE: Operating the engine without an air filter, with a damaged air filter, or with an improperly installed air filter will allow dirt to enter the engine, causing rapid engine wear. This type of damage is not covered by the Distributor’s Limited Warranty. 1. Remove the knob, unhook the two air cleaner cover clips, and then remove the air cleaner cover and the element. 2. Wash the air cleaner element with a solution of household detergent and warm water, then rinse thoroughly, or wash with a nonflammable or high flashpoint solvent. Then, allow the air cleaner element to dry thoroughly. 3. Soak the air cleaner element in clean engine oil and squeeze out the excess oil. If too much oil is left in the air cleaner element, the engine will smoke during initial startup. 4. Reinstall the air cleaner element and the cover.

Spark Arrester Maintenance (country specific) (Fig. 20) If the generator has been running, the muffler will be very hot. Allow it to cool before cleaning the spark arrester. In order to keep the spark arrester functioning as designed, it must be serviced every 100 hours. Clean the spark arrester as follows: 1. Loosen the screw by the exhaust port of the muffler and remove the spark arrester. 2. Use a brush to remove carbon deposits from the spark arrester screen. The spark arrester must be free of breaks or tears. Inspect it and replace it if damaged. 3. Install the spark arrester in the reverse order of removal.

Fuel Sediment Cup Cleaning The sediment cup prevents any dirt or water that may be in the fuel tank from entering the carburetor. Be sure to clean the sediment cup if the engine has not been run for a long period of time. 1. Turn the fuel valve lever to the “O (OFF)” position. Remove the sediment cup, O-ring, and filter. 2. Clean the sediment cup and filter with a nonflammable or high flash point solvent. 3. Reinstall the filter, new O-ring, and sediment cup. 4. Turn the fuel valve lever to the “I (ON)” position and check for leaks.

STORAGE

Storage Preparation Proper storage preparation is vital to keep the generator trouble-free and looking good. The following steps will help to keep rust and corrosion from impairing the generator’s performance and appearance, and will make the engine easier to start when you use the generator again.

Spark Plug Service (Fig. 18 & Fig. 19) A spark plug wrench (commercially available) is required to service the spark plug. Recommended spark plugs: RN9YC (Champion), BPR5ES (NGK), W16EPR-U (DENSO) In order for the engine to operate properly, the spark plug must be properly gapped and free of deposits.

Cleaning Wipe down the generator with a moist cloth and let it dry completely. Touch up any damaged paint and coat other areas that may rust with a light film of oil.

Fuel

NOTICE: Fuel formulations may deteriorate and oxidize rapidly, depending on the region where the equipment is operated. Fuel deterioration and oxidation can occur in as little as 30 days and may cause damage to the carburetor and/or fuel system. Check with your servicing dealer for local storage recommendations. Gasoline will oxidize and deteriorate in storage. Old gasoline will cause hard starting, and it leaves gum deposits that clog the fuel system. If the gasoline in the generator deteriorates during storage, the carburetor and other fuel system components may need to be serviced or replaced. The length of time that gasoline can be left in the fuel tank and carburetor without causing functional problems will vary with factors such as gasoline blend, your storage temperatures, and whether the fuel tank is partially or completely filled. The air in a partially filled fuel tank promotes fuel deterioration. Very warm storage temperatures accelerate fuel deterioration. Fuel deterioration problems may occur within a few months, or even less if the gasoline was not fresh when you filled the fuel tank.

NOTICE: Using an incorrect spark plug can damage the engine. Let the engine cool before servicing the spark plug, if the engine has been running. 1. Remove the spark plug cap. 2. Clean any dirt from around the spark plug base. 3. Use a spark plug wrench to remove the spark plug. 4. Visually inspect the spark plug. Discard it if the insulator is cracked, chipped, or fouled. 5. Measure the spark plug electrode gap with a wire-type feeler gauge. If necessary, correct the gap by carefully bending the side electrode. The gap should be: 0.7 - 0.8 mm 6. Check that the spark plug sealing washer is in good condition, and then thread the spark plug in by hand to prevent cross-threading. 7. After the spark plug is seated, tighten with a spark plug wrench to compress the washer.

- If installing a new spark plug, tighten 1/2 turn after the spark plug seats to compress the washer. If reinstalling a used spark plug, tighten 1/8 to 1/4 turns after the spark plug seats to compress the washer.

Page 14 of the Makita EG5550A user manual — TRANSPORTING (Fig. 23)
Seite 14 · Zum Vergrößern klicken
Seite 14

Fuel system damage or engine performance problems resulting from neglected storage preparation is not covered by the Distributor’s Limited Warranty. Fuel storage life can be extended by adding a gasoline stabilizer that is formulated for that purpose. Or, drain the

carburetor, sediment cup (if applicable) and/ or fuel tank to avoid fuel deterioration problems. Service according to the table below:

LENGTH OF STORAGE RECOMMENDED SERVICE PROCEDURES TO PREVENT HARD STARTING

Less than 1 month No preparation required.

1 to 2 months Fill with fresh gasoline and add gasoline stabilizer*.

2 months to 1 year Fill with fresh gasoline and add gasoline stabilizer*. Drain the carburetor float bowl and the fuel sediment cup.

Fill with fresh gasoline and add gasoline stabilizer*. Drain the carburetor float bowl and the fuel sediment cup. Remove the spark plug and put a teaspoon of engine oil into the cylinder. Turn the engine slowly with the recoil starter to distribute the oil. Then, reinstall the spark plug. Change the engine oil. After removing the generator from storage, drain the stored gasoline into a suitable container, and fill with fresh gasoline before starting.

1 year or more

*Use gasoline stabilizers that are formulated to extend storage life. Follow the manufacturer’s instructions for use. Contact our authorized Makita generator dealer for stabilizer recommendations.

Draining the Fuel Tank and Carburetor (Fig. 21)

Select a well ventilated storage area away from furnaces, water heaters, or clothes dryer, or any other appliance that operates with a flame. Also avoid areas with a spark- producing electric motor, or where power tools are operated. Since high humidity promotes rust and corrosion, avoid storage areas with high humidity when possible. Unless all of the fuel has been drained from the fuel tank, leave the fuel valve in the “O (OFF)” position to reduce the possibility of leakage. Place the generator on a stable and level surface. Tilting can cause the fuel or oil to leak. Once the engine and exhaust system are cool, cover the generator to keep out dust. A hot engine and exhaust system can ignite or melt certain materials. Do not use sheet plastic as a dust cover. A nonporous cover will trap moisture around the generator, promoting rust and corrosion.

  • WARNING: Gasoline is highly flammable and explosive. Burns or severe personal injury may result from handling fuel.
  • Stop the engine and keep heat, sparks, and flames away.
  • Handle fuel only outdoors.
  • Wipe up spills immediately. 1. Loosen the drain screw and drain the carburetor. Drain the gasoline into a suitable container. 2. Place a suitable gasoline container below the sediment cup, and use a funnel to avoid spilling gasoline. 3. Remove the sediment cup, and then turn the fuel valve lever to the “I (ON)” position. 4. Allow the gasoline to drain completely, and then reinstall the sediment cup.

Removal from Storage Check the generator as described in the “PRE- OPERATION CHECKS” chapter of this manual. Fill the fuel tank with fresh gasoline if the fuel was drained during storage preparation. If gasoline for refueling is kept in a container, be sure that it contains only fresh gasoline. Gasoline oxidizes and deteriorates over time, and using oxidized and/or deteriorated oil will cause hard starting. Note that if the cylinder was coated with oil during storage preparation, it is normal for the engine to smoke briefly at startup.

Engine Oil (Fig. 22) 1. Change the engine oil. 2. Remove the spark plug. 3. Pour a teaspoon (5 - 10 cc) of clean engine oil into the cylinder. 4. Pull the starter grip several times to distribute the oil in the cylinder. 5. Reinstall the spark plug. 6. Pull the starter grip slowly until resistance is felt. The piston is coming up on its compression stroke at this point, and both the intake and exhaust valves are closed. Storing the engine in this position will help to protect it from internal corrosion. Return the starter grip back gently to its original position.

TRANSPORTING (Fig. 23)

When transporting the generator, turn off the engine switch and the fuel valve. Keep the generator stable and level to prevent fuel from spilling. Fuel vapor or spilled fuel may ignite.

Storage Precautions If the generator is to be stored with gasoline in the fuel tank and carburetor, it is important to reduce the hazard of gasoline vapor ignition.

Page 15 of the Makita EG5550A user manual — Å Æ
Seite 15 · Zum Vergrößern klicken
Seite 15

WARNING: Contact with a hot engine or exhaust system can result in serious burns or fire. Allow the engine cool before transporting or storing the generator. When transporting the generator, take care not to drop or strike the generator. Do not place heavy objects on the generator. When transporting the generator on a vehicle, secure to the generator frame as shown.

TECHNICAL INFORMATION

Emission Control System Information

Source of Emissions Carbon monoxide, oxides of nitrogen, and hydrocarbons are produced in the combustion process. Controlling the emission of hydrocarbons and oxides of nitrogen is extremely important because, under certain conditions, they react to form photochemical smog when subjected to sunlight. Although carbon monoxide does not react in the same way, it is toxic. Makita utilizes the appropriate air-fuel ratios and other emissions control systems in order to reduce the emissions of carbon monoxide, oxides of nitrogen, and hydrocarbons. Furthermore, Makita fuel systems utilize components and control technologies in order to reduce evaporative emissions.

TROUBLESHOOTING

When the engine fails to start:

Check if fuel is in the tank. Å Æ If empty, refill the fuel tank.

Check the fuel level. Å Æ If low, add the recommended oil.

If in bad condition, readjust the gap and dry the spark plug. Replace if necessary.

Check the condition of the spark plug.

  • Tampering and Altering The level of emissions may increase beyond the legal limit, if the emission control system is tampered with or altered. Acts that constitute tampering include:
  • Removal or alteration of any part of the intake, fuel, or exhaust systems.
  • Altering or defeating the governor linkage or speedadjusting mechanism to cause the engine to operate outside its design parameters.

Å Æ

Check if fuel is reaching the carburetor.

Å Æ If not, clean the fuel sediment cup.

If the engine still fails to start, take the generator to an authorized Makita generator dealer.

When no electricity is generated at the AC receptacles:

  • Problems That May Affect Emissions If you become aware of any of the following symptoms, have the engine inspected and repaired by your servicing dealer.
  • Hard starting or stalling after starting.
  • Rough idle.
  • Misfiring or backfiring under load.
  • Afterburning (backfiring).
  • Black exhaust smoke or high fuel consumption.

Check that the AC circuit breaker is in the “I (ON)” position.

Å Æ If not, turn on the AC circuit breaker.

If there are no defects, take the generator to an authorized Makita generator dealer. If there are defects: - Replace the electrical appliance or equipment. - Take the electrical appliance or equipment to an electrical shop to be repaired.

Replacement Parts The emission control systems on your Makita engine were designed, built, and certified to conform to applicable emission regulations. Therefore, it is recommended that genuine Makita parts be used whenever you have maintenance done. Since these original-design replacement parts are manufactured to the same standards as the original parts, their performance is reliable. Using replacement parts that are not of the original design and quality may decrease the effectiveness of the emission control system. Note that manufacturers producing aftermarket parts assume the responsibility that the part will not adversely affect emission performance. The manufacturer or rebuilder of the part must certify that the engine will still comply with emission regulations even with the use of the part.

Check if the electrical appliance or equipment has any defects.

Å Æ

Maintenance Follow the Maintenance Schedule. Remember that this schedule is based on the assumption that the machine will be used for the purpose it is designed. The machine will require more frequent service for continuous high-load or high-temperature operation, or use in unusually wet or dusty conditions.

Page 16 of the Makita EG5550A user manual — WIRING DIAGRAM
Seite 16 · Zum Vergrößern klicken
Seite 16

WIRING DIAGRAM

Makita EG5550A — WIRING DIAGRAM diagram (page 16)
Abb. 30

9.6/12.5A Overcurrent Protective Device Class 1 Mutual Inductor

Class 2 Mutual Inductor

8A Overcurrent Protective Device

Engine Engine Oil Level Switch

Show 11 more labels / short text on this page
Electric Generator · Panel · Stud · Main Coil · Drive Coil · Oil Level · Flameout · Rotor Coil · Direct- current Winding · Spark Plug · Ignition Coil
Page 17 of the Makita EG5550A user manual — WIRING DIAGRAM
Seite 17 · Zum Vergrößern klicken
Seite 17
Makita EG5550A — WIRING DIAGRAM diagram (page 17)
Abb. 31

19.5/24/26A Overcurrent Protective Device Class 1 Mutual Inductor

Class 2 Mutual Inductor 16A Overcurrent Protective Device

16A Overcurrent Protective Device

8A Overcurrent Protective Device

Ignition Coil Carburetor Oil Cut-off Valve

Engine Engine Oil Level Switch

Battery Starting Motor & Relay

Show 11 more labels / short text on this page
Panel Electric Generator · Main Coil · Drive Coil · Oil Level · Rotor Coil · Flameout · Fuel Cut · Direct- current Winding · Charging Coil Startup · Spark Plug · Charging Coil
Page 18 of the Makita EG5550A user manual — ASSEMBLY
Seite 18 · Zum Vergrößern klicken
Seite 18

SPECIFICATIONS

MODEL EG2250A EG2850A EG4550A EG5550A EG6050A

Type Brush, 2-poles, single phase

Voltage regulating system AVR type

AC Output 230 - 50 Rated voltage-Frequency V-Hz

Rated current A 8.7 11.3 17.4 21.7 24

Rated output VA (W) 2,000 2,600 4,000 5,000 5,500

Maximum output VA (W) 2,200 2,800 4,500 5,500 6,000

Rated power factor 1.0

Safety device type Circuit breaker

DC Output 12 Rated voltage V

Rated current A 8.3

Safety device type Circuit breaker

Type OHV 4-stroke single cylinder

Displacement mL 210 420

Fuel Automotive Unleaded Gasoline

Fuel tank capacity (Full) L 15 25

Fuel tank capacity (regulated Fuel volume) L 10 20

Engine oil capacity L 0.6 1.1

Spark plug Champion RN9YC

Starting system Recoil starter Electric starter / Recoil

Length mm 600 680

Width mm 442 550

Height mm 450 550

Noise (according to 2000/14/EC)

Sound pressure level dB (A) 75 (Uncertainty K=3)

Sound power level dB (A) 95 (Uncertainty K=3)

Dry weight kg 42 45 80 83 85

kg 49.8 52.8 95.5 98.5 100.5

Gross weight Weight according to EPTA procedure 01/2003

ASSEMBLY

The Importance of Proper Assembly Proper assembly is vital to operator safety and the machine reliability. Any error or oversight made by the person assembling or servicing a unit can easily result in faulty operation, damage to the machine, or injury to the operator.

WARNING: Improper assembly can cause an unsafe condition that can lead to severe personal injury or loss of life. Follow the procedures and precautions in the assembly instructions carefully. Some of the most important safety precautions are given below. However, we cannot cover every conceivable hazard that can arise in performing this assembly, so please remember that only you can decide whether or not you should perform a given task.

- Before beginning work, read the instructions and be sure you have the tools and skills required to perform the tasks safely. • Make sure the engine is off before beginning any maintenance or repairs. This will help eliminate several potential hazards:

Show 4 more labels / short text on this page
Generator · Model 170F 190F · Engine · Dimension
Page 19 of the Makita EG5550A user manual — SPECIFICATIONS
Seite 19 · Zum Vergrößern klicken
Seite 19

- Carbon monoxide poisoning from engine exhaust. Operate outside away from open windows or doors. - Burns from hot parts. Let the engine and exhaust system cool before touching. - Injury from moving parts. Do not run the engine unless the instruction tells you to do so. Even then, keep your hands, fingers, and clothing away. When any protective guard or shield has been removed, do not run the engine.

  • To reduce the possibility of a fire or explosion, be careful when working around gasoline or batteries. Use only a non-flammable solvent, not gasoline, to clean parts. Keep all cigarettes, sparks, and flames away from all fuel-related parts.

Unpacking 1. Take out the generator and the loose parts box from the carton. 2. Check the loose parts against the contents list below. Tools required: 12-mm wrench (2), pliers

Loose Parts (Wheel Kit and Handle) and Front Support (Only for model EG4550A, EG5550A, EG6050A) Check all loose parts against the following list. Contact your dealer if any of the loose parts shown below are not included with the generator.

Makita EG5550A — SPECIFICATIONS diagram (page 19)
Abb. 32

No. Name Quantity

1 10-Inch Roller 2

2 Wheel Axle 2

3 Transport Handle Shaft 2

4 M8 x 100 Bolt 2

5 Transport Handle 2

6 Front Stand 2

7 Rubber Base 2

8 M8 Flange Nut 6

Page 20 of the Makita EG5550A user manual — WARRANTY SERVICE INFORMATION
Seite 20 · Zum Vergrößern klicken
Seite 20
  • Handle Installation (Fig. 24) 1. Remove the two lugs in the pushrod inserted into the rack, and line up the hole on the pushrod with the hole on the rack. Next, insert the pushrod into the rack from the outside and then screw in the M8 flange bolt on the inside and tighten down the bolt. TORQUE: 17 - 22 lbf
  • ft (24 - 29 N
  • m, 2.4 - 3.0 kgf
  • m)

questions you may have. If there is a problem that your dealer does not solve to your satisfaction, please discuss it with the Service Manager or General Manager of the dealership. Almost all problems are solved in this way. If you are dissatisfied with the decision made by the dealership’s management, contact the Makita Corporation.

For European countries only

  • Wheel Kit Installation (Fig. 25) 1. Line up the hole on the roller with the hole on the rack, insert the roller shaft into the rack from the outside, and then screw in the M8 flange bolt on the inside and tighten down the bolt. TORQUE: 17 - 22 lbf
  • ft (24 - 29 N
  • m, 2.4 - 3.0 kgf
  • m)

EC Declaration of Conformity We Makita Corporation as the responsible manufacturer declare that the following Makita machine(s):

Designation of Machine: Petrol Generator Model No./ Type: EG2250A, EG2850A, EG4550A, EG5550A, EG6050A Specifications: see "SPECIFICATIONS" table. are of series production and Conforms to the following European Directives:

Fit the front stand (Fig. 26) 1. Insert an M8×100 bolt into the holes on the rubber blanket, front stand, and rack mounting plate. 2. Screw the M8 flange bolt onto the M8×100 bolt from the mounting plate and then tighten down the bolt.

2000/14/EC, 2004/108/EC, 2006/42/EC, 2006/95/EC And are manufactured in accordance with the following standards or standardised documents:

Stopping the engine with remote control 1. Press the stop button. 2. Turn the engine switch on the generator to the “O (OFF)” position. 3. Turn the fuel valve lever on the generator to the “O (OFF)” position.

EN12601, EN55012, EN61000, EN60204-1 The technical documentation is kept by:

Makita International Europe Ltd. Technical Department, Michigan Drive, Tongwell, Milton Keynes, Bucks MK15 8JD, England

Battery Tray (Fig. 27)

NOTE: Battery is not included. Use a battery (rating: 12V-10Ah, L x W x H: maximum 160 mm x 90 mm x 160 mm) available in the market. 1. Connect the black power line (ground electrode) on the electric generator to the negative electrode on the battery and the red power line to the positive electrode on the battery. 2. Place the battery connected to the power lines into the battery box on the rack. 3. Hang each of the two card buckles on the rubber belt onto one of the two hangers on the battery box.

The conformity assessment procedure required by Directive 2000/14/EC was in Accordance with annex VI. Notified Body:

AV TECHNOLOGY LTD AVTECH House,Arkle Avenue Stanley Green Trading Estate Handforth,Cheshire SK9 3RW,United Kingdom Identification number 1067 Model EG2250A Measured Sound Power Level: 94 dB (A) Guaranteed Sound Power Level: 95 dB (A)

Model EG2850A, EG4550A, EG5550A, EG6050A Measured Sound Power Level: 95 dB (A) Guaranteed Sound Power Level: 96 dB (A)

Engine Oil (Fig. 13) The generator is shipped WITHOUT OIL in the engine. Place the generator on a stable and level surface. Add enough of the recommended oil to bring the oil level to the top of the oil filler neck. Use a 4-stroke motor oil that satisfies the requirements for API service category SJ or later (or equivalent). Do not overfill the engine with oil. If the engine is overfilled, the excess oil may get transferred to the air cleaner housing and air filter.

27.12.2013

Director Makita Corporation 3-11-8, Sumiyoshi-cho, Anjo, Aichi, 446-8502, JAPAN

WARRANTY SERVICE INFORMATION

CUSTOMER SERVICE INFORMATION The personnel at the servicing dealership are trained professionals. They should be able to answer most

Tomoyasu Kato

Frage zu Makita EG5550A stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Makita EG5550A

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Makita EG5550A PDF-Anleitung

112 Seiten·2.9 MB·Generator·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…