Dimplex SmartRad Fan Convector SRX 080M, SRX 120M, SRX 140M & SRX 180M

EN RU DK

FR NO DE FI NL PL

The product complies with the European Safety Standards EN60335-1 and the European Standard Electromagnetic Compatibility (EMC) EN55014, EN60555-2

and EN60555-3. These cover the essential requirements of EEC Directives 2006/95/EC and 2004/108/EC

srx_ba 01/11/C

Page 2 of the Dimplex SRX 180M user manual — EN RU DK
Seite 2 · Zum Vergrößern klicken
Seite 2
Dimplex SRX 180M — EN RU DK diagram (page 2)
Abb. 3
Dimplex SRX 180M — EN RU DK diagram (page 2)
Abb. 4

590 MIN 535 150 MIN 150 MIN 235 MIN

Dimplex SRX 180M — EN RU DK diagram (page 2)
Abb. 5
ABCD SRX 080503324396386 SRX 120670492564564 SRX 140740562634624 SRX 180911732804794
Dimplex SRX 180M — EN RU DK diagram (page 2)
Abb. 6
Page 3 of the Dimplex SRX 180M user manual — EN RU DK
Seite 3 · Zum Vergrößern klicken
Seite 3
Dimplex SRX 180M — EN RU DK diagram (page 3)
Abb. 7
Dimplex SRX 180M — EN RU DK diagram (page 3)
Abb. 8
Page 4 of the Dimplex SRX 180M user manual — EN RU DK
Seite 4 · Zum Vergrößern klicken
Seite 4
35°C45°C55°C65°C SRX18031631273438444959 21079180325303260 1641106914991929 SRX14031299217730613951 2838140319682536 149382311541484 SRX12031120187826413408 2719120116862172 14156939711249 SRX803759127317902050 247980111241448 1251419588756 Q = 450 l/h
35°C45°C55°C65°C SRX18031480250235204546 21020171324063102 1625104414641885 SRX14031199202428503682 2802134618922439 148480811331459 SRX12031044176024793202 2691116016292100 14086839571231 SRX803719121017052203 246578010951412 1249416582749 Q = 300 l/h
35°C45°C55°C65°C SRX18031059183226483498 2820140820212655 155894813461750 SRX1403900155822562984 2671115116512167 144274910631378 SRX1203806139420162668 2591101014471894 13796419071174 SRX803587101214601926 241370410051309 1237399564728 Q = 150 l/h
35°C45°C55°C65°C SRX1803852143120202559 2695116716472109 150684811751542 SRX1403752126917982263 259199513551793 14116919551251 SRX1203689116415572070 253089412151606 13575998281083 SRX80353090211901580 23876558841163 1231387534694 Q = 100 l/h
35°C45°C55°C65°C SRX180355191812841649 248781211361460 13946579201183 SRX140351185211931535 243672810201313 13385647911019 SRX120348080211241446 24026729431215 1302504707912 3 392 655 921 1191 SRX80 2 312 522 734 950 1 207 345 486 62733926559211191 2312522734950
35/30°C45/40°C55/47°C65/50°C SRX18031495285639254628 2893176024242879 1522100813951636 SRX14031078217229823492 2631132918282154 134475210391176 SRX1203870182625062924 2561111915411770 13316218561017 3 573 1165 1595 1777 SRX80 2 358 695 956 1137 1 201 375 516 6073573116515951777 23586959561137

Power Output

Page 5 of the Dimplex SRX 180M user manual — EN
Seite 5 · Zum Vergrößern klicken
Seite 5
Dimplex SmartRad fan convector ModelsSRX 080M, SRX 120M, SRX 140M & SRX 180M

EN

PLEASE STORE THESE INSTRUCTIONS IN A SAFE PLACE.

Important safety information The air inlet and outlet guards must not be covered or blocked. Before performing maintenance work on the device, discon- nect it from the power supply. THE DEVICE MUST BE GROUNDED. The heater must not be installed directly below a permanently installed socket. Combustible materials or liquids and other highly flammable furnishings must be kept away from the heater. For the necessary minimum distances (in mm), see fig. 4. Install the device such that it is not possible for someone in the bath or shower to touch the control elements. The heater must not be operated in very dusty areas. This device is not suitable for children or persons who cannot use the device safely as a result of physical or mental disability or reduced perception without the assistance or supervision of another person. Children should be supervised to ensure they do not play with the device.

SRX 080MSRX 120MSRX 140MSRX 180M Heat output (kW) at flow temperature of 45°C20.701.101.401.80 Temperature range of flow temperature (°C)25 – 85 Maximum permissible flow temperature (°C)85 Permissible operating overpressure (MPa)1 Pressure drop (kPa)11.313.113.715.8 Air volume flow (m³/h)3228345410540 2125190225300 160100120160 Sound pressure level at 1 m (dB(A))347 238 127 Nominal voltage~ 230 V, 50 Hz Power consumption of fan (W)326435650 219293633 116202423 Standby energy consumption (W)< 1 Protection categoryIP 20 Volume of heat exchanger (ml)310430480600 Dimensions W x H x D (mm)503 x 530 x 145670 x 530 x 145740 x 530 x 145911 x 530 x 145 Weight (kg)121517.522
Dimplex SRX 180M — EN diagram (page 5)
Abb. 9

A warning symbol is attached to the heater. This in- dicates that the device must not be covered. The operating instructions belong to the device and must be stored in a safe place. In case of the owner changes, the operating instructions should be passed on to the new owner. IMPORTANT – If the mains cable of the device is damaged, it must be replaced by the manufacturer, a customer service representative or a similarly qualified person. Always ensure proper operation. Device description

Remove packaging material. Unscrew the four fixing screws from underside of device (see fig. 2) to remove casing cover. Store the casing cover such that it cannot be damaged during installation. Fixing to the wall

The SmartRad model is a fan convector for heating living spaces. The fan convector is intended for connection to a central heat- ing system. The fan convector is suitable for use in heat pump systems, but it can also be operated in conjunction with other heating systems, e.g. with oil or gas fires. The device draws in air from the underside. This is heated up in the heat exchanger and discharged at the top.

For drywalls, use suitable fixing material (not supplied)! Draw and drill four holes on a sturdy wall as shown in fig. 4. All dimensions are in mm. Insert dowels and pre-fit the two top screws (don't completely screw in yet). Hang device on the two top screws. Insert and tighten the two bottom screws, then tighten the two top screws. Hydraulic connection

Fig. 1: (a) Casing cover (b) Control panel (c) Air outlet guard (d) 1 m connection cable

To ensure a sufficient heating water flow rate through the fan convectors, observe the following points:

Fan convectors may only be used in central heating systems with a closed control circuit. The heating system must be operated as a dual-pipe system. The devices must be of a sufficient rating such that they can compensate for heat losses in the room.

- The devices are not suitable for installation in single-pipe

systems. - The nominal width of the connection pipe must have a

minimum diameter of 15 mm. - If the devices are installed in a heating system with various

heat distribution systems (e.g. underfloor heating), a sepa- rate circuit is required to guarantee a sufficient water flow rate. - For optimum operation (heat output) of the fan convectors,

Technical data

Page 6 of the Dimplex SRX 180M user manual — EN
Seite 6 · Zum Vergrößern klicken
Seite 6

a hydraulic balance is required on the heating system.

external voltage (via a timer contact or pilot device with pro- gramming cassette). Final installation

Fig. 5 shows the various hydraulic connection options on the device. The recommended flow and return connections are shown in fig. 5 and fig. 4 (below). The heating pipes can be laid in the floor or in the wall. The device is supplied with two cop- per pipes with a diameter of 15 mm that are fitted on the heat exchanger at the factory. Before and during filling of the heating system, all pipe connec- tions must be checked for leaks. During filling, the bleeder valve (see fig. 4) must be open such that air can escape from the de- vice. If necessary, bleed again following commissioning (circulat- ing pump running). Electrical connection

Fit casing cover following completion of installation work. To do this, screw in the four fixing screws on the underside of the de- vice, see fig. 2. Operation

The control panel is shown in fig. 3. The individual elements have the following meaning: A – Operating mode button B – On/off indicator C – Manual mode indicator D – Automatic mode indicator E – Fan level button F – Low fan level indicator G – Medium fan level indicator H – High fan level indicator J – Thermostat setting wheel K – Cover for programming cassette slot Manual operation

WARNING: The device must be grounded. WARNING – phase conductor (brown) and neutral conductor (blue) must not be swapped as this may cause malfunctions. The electrical connection should have a supply voltage of ~230- 240V, 50 Hz. The device must be installed by a qualified electrician in compli- ance with the existing standards and local installation guide- lines. Before performing installation, ensure that the power supply is switched off. The device is equipped with a flexible 1 m connection cable (4 x 0.75 mm²), which can be used to connect the heater directly to the power supply via a suitable wall socket. In the electrical supply line, fit a circuit breaker for each pole with a contact opening width of at least 3 mm. Automatic fuses are also permitted as separators. Automatic fuses should have a delayed tripping characteristic.

Press the button once or several times until the yellow indicator lights up. Press the button once or several times to select the de- sired fan level (fan speed). The set fan level is indicated by the red indicator (1, 2, 3). Set the desired room tempera- ture with the knob. The set fan level is switched on and off depending on the room temperature. The temperature re- duction is forwarded to any downstream devices via the control conductor. Automatic mode (eco)

Conductor configuration of the connection cable: Brown: 'L' – supply voltage phase conductor Blue: 'N' – supply voltage neutral conductor Green/yellow: 'PE' grounding conductor Black: control conductor (temperature reduction; on/off)

Press the button once or several times until the red eco indicator lights up. Set the desired room temperature with the knob. Depend- ing on the current room temperature and the target tem- perature set on the thermostat, the electronics calculate which of the three fan levels (fan speeds) to use. The elec- tronics select the required fan level depending on the dif- ference between the current room temperature and the de- sired target temperature. If necessary, the number of possible fan levels can be reduced. For instance, to limit the fan levels to a maximum of 2, press the button once or several times until the red 2 indicator lights up. Operation with a programming cassette or a timer can only take place in automatic mode (eco). If there is a control signal, the green eco indicator lights up. Fault indication

For circuit diagram, see fig. 6. Control conductor

The black control conductor has the following functions:

Lowering temperature using an external timer or switch By activating the control conductor, see fig. 6 on the left, the set target temperature on the device is lowered. The temperature reduction is forwarded to any downstream devices via the control conductor.

Operation with programming cassette The control signals of the programming cassette, which is plugged into the pilot device, are forwarded to any downstream devices via the control conductor, see fig. 6 on the right. The control conductor does not have to be in phase with the supply connection. If the control conductor is not used, it must be properly insulated. WARNING – if you switch over to controlled operation, the mains voltage is on this conductor! WARNING – do not ground the control conductor. When taking out of service, e.g. for maintenance work, ensure that both the mains supply and the control conductor are dis- connected from the power supply, because this may result in

If the water temperature is too low, operation of the device is interrupted and the red indicator flashes. In this case, check that the heating system and circulating pump are operating cor- rectly. For more information, please refer to the "Troubleshoot- ing" chapter.

Page 7 of the Dimplex SRX 180M user manual — EN
Seite 7 · Zum Vergrößern klicken
Seite 7

Operation with air/water heat pumps

When operating with an air/water heat pump, particularly when temperatures are low outside, the heat pump's buffer tank must be at a temperature of at least 14°C to ensure that the heat pump evaporator can defrost. You should therefore en- sure that thawing has taken place if necessary before opening the valves to the heating circuit. Troubleshooting

The heater must be switched off and cooled for cleaning. The surfaces of the heater can be cleaned by wiping with a soft, damp cloth and then dried. Do not use abrasive powder or fur- niture polish to clean as these may damage the surface. Maintenance – to be performed by a specialist

Dust or lint that collects inside the heater must be removed at regular intervals. To do this, disconnect the device from the power supply, loosen the 4 fixing screws on the underside of the casing and carefully remove the casing cover. Remove dirt with a soft brush or a vacuum cleaner. Build-up of air in the heat exchanger can be remedied by open- ing the bleeder valve (fig. 4). Warranty

The following causes can result in the fan convector producing insufficient heat:

  • Red indicator flashes: See "Fault indication" section
  • Air trapped in heat exchanger: Disconnect device from power supply, remove casing and bleed heat exchanger. For position of bleeder screw, see fig. 4.
  • Water temperature too low: Set flow temperature higher on heating system.
  • Insufficient water flow rate through device: Adjust flow rate (hydraulic balance). To do this, close thermostat valves on the other heaters.
  • Dirt on heat exchanger: Clean heat exchanger, see "Maintenance" section.

We offer a two-year warranty for this device in accordance with our warranty conditions.

Glen Dimplex Deutschland GmbH Phone +49 9221 709564 Am Goldenen Feld 18 Fax +49 9221 709589 D-95326 Kulmbach www.glendimplex.de Subject to modifications EN 01/11/C

Cleaning outer surfaces

Quellen

Referenzen & Links

In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.

Frage zu Dimplex SRX 180M stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Dimplex SRX 180M

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Dimplex SRX 180M PDF-Anleitung

32 Seiten·973 KB·Konvektor·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…