Install ation & O perating M anual C 6501073(0) S i n g l e s t a g e o p er a ti o n oil burners RETROFIT APPLICATIONS ONLY If this burn er is being instal led in a packaged un it (ie.
3398 GB INSTALLLATION PRECAUTIONS AIR FOR COMBUSTION Do not instal l burner in room with insuffic ient air for combust ion. Be sure there is an adequate air suppl y for combustion if the boil er room is enclosed. It may be nec es sary to create a window t o permit sufficient air to enter the boile r room.
3398 GB TABLE OF CONTENTS PACKAGE CONTENTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SERIAL NUMBER IDEN TIFICATION . . . . . . . . . . . . . . . .
3398 1 GB PACKAGE CONTENTS LIST Your Riel lo 40 BF b urner shoul d include the follow ing parts. Pl ease che ck to make s ure all pa rts are pre sent before be - ginnin g the in stallati on.
3398 2 GB TEC HNI CAL DA TA SPECIFICATIONS BU R N E R AND MOUNTING FLANGE D IM E N S IO N S BURNER COMPONENTS IDENTIFICATION Fuel No. 2 Fuel O il BF3 Firing rate - Effective Output 0.50 to 0. 95 US GPH - 70,0 00 to 133, 000 BTU/h BF5 Firing rate - Effective Output 0.
3398 3 GB MOUNTING THE BURNER TO THE BOILER - Positi on the MOUNT ING G ASKE T (2) be - tween the flat sur face of the UNIVERS AL MOUNTING FLAN GE (1) install ed on the burner and the appli ance.
3398 4 GB APPLICATION FIELD WIRING Oi l V a l v e Cap a c i t o r GR EEN BLU E BLAC K BLACK WH I T E BLUE M BR OW N AL 100 9- 1 B ur ner F an- Of f Ti m e r 6 12 8 N 1 11 9 3 2 7 Co nt r o l B o x 530.
3398 5 GB INSTALLATION/REMOVAL OF DRAWER ASSEMBLY Removal: A) Remove th e air press ure switch support (6) fro m the fron t shield by the two ret ain- ing screws (7) B) Loosen o ff oil delivery tube n ut from pump. C) Loosen SCREW ( 3), and th en unplug CONT ROL BO X (1) by carefu lly pu lling it back a nd then up.
3398 6 GB OIL LINE CONNECTIONS This burne r is s hipped wit h the oil p ump set to operate o n a single line sy stem. To ope rate on a two-line sy stem the by -pass pl ug must be inst alled. NOTE: Pump pressure must be set at time of b urner start- up.
3398 7 GB NPTF - NPT pipe adapter The B F bu rner you ha ve pu rchas ed is s hipped with an NP TF to NPT fi tting. This fitting is the connec tion point for the oil line from the oil tank or the in-line oil filter. In some locations, fit- tings wi th the NPT F male thread are difficul t to obtain.
3398 8 GB PUMP PURGE NOTE: To protect the pump gear s, it is advisabl e to lubricate the pump prior to purging a lift system. Apply oil through the VACUUM PORT (C). A) SIN GLE LINE (GRA VITY FE ED SYSTE M) I. Loosen the bleeder valve (A) until oil flows out.
3398 9 GB COMBUST ION CHAMBER PRESSURE CHA RT BURNER OUTPUT VS CHA MBER PRESSURE CHA RT D7525 (GPH) BURNER OUTPUT CHAM BER P RESSUR E (INCHES WC) 0 .0 0.
3398 10 GB BURNER START-UP CYC LE Normal Lock- out, due to l ight-failu re Thermo stat Motor Igniti on transf ormer Va l v e Flame Lock-o ut lamp ~ 12 se c.
3398 11 GB TROUBLE SHOOTING CHART • Faulty CAD cell or seeing light before trial for ignition. • Coil wire on terminals #1 & 2 or #1 & 8 reversed. • Open coil circuit, terminals #2 & 8. • Open coil circuit, terminal #1 (530 SE only).
3398 12 GB A TYPICAL LA YOUT FOR BF BURNER INT AKE AIR A) Use an approve d air in take kit. B) Al ways keep i ntake air run to the m inimum. C) Max imum intake air run of 4 ( inch) diam eter , flex ible or rigid type of venting = 100í D) Reduc e intake air l ength by 10’ for ever y 90° el bow used.
13 3398 EXPLODED SPARE PARTS LIST.
14 3398 SPARE PARTS LIS T No. CODE DESCRIPTION No. CODE DESCRIPTION 1 3008019 • BURN ER BAC K COVER 1 C8111015 • B URNER BA CK COVER 2 3007077 • • CRUSHABLE MET AL WASHER 3/8” ID 3 3007568 .
3398 15 GB BURNER START- UP FORM * 35 Pond P ark Rd. Hingham, MA 02043 Phone: 78 1-749-8 292 T oll Free: 800-992 -7637 Fax: 78 1-740-2069 2165 Meado wpine Blv d. Mississau ga,On L5H 3R2 Phone: 9 05-542- 0303 T oll Free: 800-387-38 98 Fax: 9 05-542-152 5 Burner S/N.
T echnical Supp ort Hotline 1-80 0-4- RIELLO 1-800-474 -3556 35 Pond Park Ro ad Hingham, MA 020 43 Phone 781-7 49-8292 T oll Free 800-992-76 37 Fax 781-7 40-2069 www .riello u sa. com 2165 Meado wpine Blv d Mississ auga, ON L 5N 6H6 Phone 905-5 42-0303 T o ll Free 80 0-387-3898 Fax 905-5 42-1525 www .
Ein wichtiger Punkt beim Kauf des Geräts Weil-McLain 800060000-Brn-PO Rie BF5 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Weil-McLain 800060000-Brn-PO Rie BF5 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Weil-McLain 800060000-Brn-PO Rie BF5 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Weil-McLain 800060000-Brn-PO Rie BF5 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Weil-McLain 800060000-Brn-PO Rie BF5 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Weil-McLain 800060000-Brn-PO Rie BF5 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Weil-McLain 800060000-Brn-PO Rie BF5 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Weil-McLain 800060000-Brn-PO Rie BF5. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Weil-McLain 800060000-Brn-PO Rie BF5 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.