Benutzeranleitung / Produktwartung Extended-Run des Produzenten Tripp Lite
Zur Seite of 16
Copyright © 2008 Tripp Lite. All tr ademarks are the sole property of their respective owners. Owner’s Manual Extended-Run 3-Phase Battery Cabinet C US Not suitable for mobile applications.
[ 2 ] 1 – Introduction Tripp Lite’s Extended-Run 3-Phase Battery Cabinets co nnect to SmartOnline 3-Phase UPS Systems to provide long-lasting battery backup for data centers, telecommunications, n.
[ 3 ] 2 – Important Safety Instructions Installation and Location Warnings • Install the battery cabinet in a controlled indo or environment, away from moisture, temperat ure extremes, fl amm able liquids and gasses, cond uctive conta minants, dust and direct su nlight.
[ 4 ] 2 – Important Safety Instructions (continued) Battery Warnings • The battery ca binet does not require rout ine mainte nance by the user. There are no user-servicea ble parts insi de. Only qualified, knowledgeable service personne l fam iliar with all requir ed precautions should open t he access panels for a ny reason.
[ 5 ] 3 – Battery Cabinet Installation Read Section 2 – Important Safety Instructions Before Installation 3-1 Preparation • At your site, prepare to off-load the battery cabin et from the delivery truck and tran sport it to the final installation locati on.
[ 6 ] 3 – Battery Cabinet Installation (continued) 3-4 Internal Wiring (Typical) • Battery cabinets use multiple 6 VDC or 12 VDC batteries connected in series to provide nominal DC voltages ranging from 240 VDC t o 480 VDC. • Internal cabl ing is sized for specific a pplication load currents.
[ 7 ] 3 – Battery Cabinet Installation (continued) 3-7 Electrical Connection • The battery ca binet shoul d be connecte d to the loa d through a DC disconnect s witch or a DC ci rcuit breaker . This allows t he battery to be disconnecte d from the load and charge r for mainte nance and/or repair.
[ 8 ] 4 – Operation and Charging 4-1 Determine Charging Voltages To determine the appropriate equalization (freshening) charg e voltage and float charge voltage , multiply the number of batterie s connected in series in the battery cabi net by the recomm ended charging voltage per unit .
[ 9 ] 5 – Maintenance The battery cabinet c ontains valve-re gulated recom binant lead- acid (VRLA) batteries, which are maintenance-free relative to the electrolyte. You cannot add water to these batteries or sample the electroly te specifi c gra vity.
[ 10 ] 6 – Diagrams 6-1 Battery Cabinet Diagram (4 Shelves) Note : All dimensions are in inches. Conduit Knockouts Conduit Knockouts Breaker Mounting Plate 79 4.
[ 11 ] 6 – Diagrams (continued) 6-2 Battery Cabinet Diagram (3 Shelves) Note : All dimensions are inches. 58 Front of Cabinet Front of Ca binet Breaker Mounting Plate Conduit Knockouts Conduit Knockouts 15.75 2.25 Side View Side View Side View Side View Bottom View Top View Front View 3.
[ 12 ] 6 – Diagrams (continued) 6-3 Battery and Breaker Diagrams (240 VDC) Notes : • All internal wiring is UL-listed, MTW, 125C Hi-Flex cable. • Terminal block is UL-recogn ized and rated for 600 VD C. • Breaker is UL-listed a nd rated fo r 150 A, 600 VDC, 25 KAIC.
[ 13 ] 6 – Diagrams (continued) 6-4 Battery and Breaker Diagrams (+/- 240 VDC) Notes : • All internal wiring is UL-listed, MTW, 125C Hi-Flex cable. • Terminal block is UL-recogn ized and rated for 600 VD C. • Breaker is UL-listed a nd rated fo r 250 A, 600 VDC, 25 KAIC.
[ 14 ] 6 – Diagrams (continued) 6-5 Integrated Battery Charger (Select Models) Notes : • All dim ensions are inches . • AC input is selectabl e 120/208/ 240 VAC, 60 Hz. • Constant voltage out put. • Electronic current lim iting and hi gh voltage shutdown.
[ 15 ] 7 – Specifications 7-1 Dimensions and Floor Loading Battery Cabinet Model Shelves Dimensions (Width x Depth x Height) Weight Floor Loading BP240V99 3 32 x 30 x 58 inches (81.3 x 76.2 x 147.3 cm) 1760 lb (800 kg) 264 lb/ft 2 (1292 kg/m 2 ) BP240V120 3 32 x 30 x 58 inches (81.
[ 16 ] 8 – Storage and Service Storage The battery ca binet must be st ored in a clean, sec ure environm en t with a temperature less than 40° C (104° F) and a relative hu midity less than 90% (non-conden sing). Store the ba ttery cabinet in its original shipping co ntaine r if possible.
Ein wichtiger Punkt beim Kauf des Geräts Tripp Lite Extended-Run (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Tripp Lite Extended-Run noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Tripp Lite Extended-Run - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Tripp Lite Extended-Run reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Tripp Lite Extended-Run erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Tripp Lite Extended-Run besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Tripp Lite Extended-Run verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Tripp Lite Extended-Run. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Tripp Lite Extended-Run gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.