A utomation and Drive s - SCE T I A Training Document Page 1 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Training Document for Comprehensive Automa.
A utomation and Drive s - SCE T I A Training Document Page 2 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET This document has been written by Siemens AG for tr aining purposes for the project entitled "Siemens Automation Cooperates with Education (SCE)".
A utomation and Drive s - SCE T I A Training Document Page 3 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET PAGE 1. pref ace ............................................................................
A utomation and Drive s - SCE T I A Training Document Page 4 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET 6.3 Generating the Data Blo ck for the R equest Me ssage ....................................
A utomation and Drive s - SCE T I A Training Document Page 5 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET The follow ing symbols are prov ided as a .
A utomation and Drive s - SCE T I A Training Document Page 6 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 1.
A utomation and Drive s - SCE T I A Training Document Page 7 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example Hardw are and Softw are Required 1.
A utomation and Drive s - SCE T I A Training Document Page 8 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startu.
A utomation and Drive s - SCE T I A Training Document Page 9 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Prefacet Notes Startup with PROFIBUS Startup with PROFINET Program Example 2. NOTES ON USING THE CPU 315F-2 PN/DP The CPU 315F-2 PN/DP is a CPU that is shipped with two integrated interfaces.
A utomation and Drive s - SCE T I A Training Document Page 10 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 11 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 12 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 13 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example Modularity SINAMICS G120 is a modular converter system that consists of di fferent functional units.
A utomation and Drive s - SCE T I A Training Document Page 14 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 15 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 16 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 17 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example The description below explains how a drive is conf igured by using Sizer.
A utomation and Drive s - SCE T I A Training Document Page 18 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 19 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 5.
A utomation and Drive s - SCE T I A Training Document Page 20 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 7. After selecting ’Environmental conditions’ , we now click on ' ’ to select the motor.
A utomation and Drive s - SCE T I A Training Document Page 21 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 9.
A utomation and Drive s - SCE T I A Training Document Page 22 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 11. Now we specify whether a ’Brake’ , a ’Motor encoder’ or ’additional motor protection’ is desired.
A utomation and Drive s - SCE T I A Training Document Page 23 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 13. All data pertaining to the moto r is now represented in Workflow.
A utomation and Drive s - SCE T I A Training Document Page 24 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 15.
A utomation and Drive s - SCE T I A Training Document Page 25 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 17. The ’Axis components’ such as ’Output reactor’ and ’Encoder evaluation’ are deselected here.
A utomation and Drive s - SCE T I A Training Document Page 26 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 19.
A utomation and Drive s - SCE T I A Training Document Page 27 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 21.
A utomation and Drive s - SCE T I A Training Document Page 28 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 29 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 30 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 31 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 32 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.4 Connecting the Frequency Conv erter SINAMICS G120 3.
A utomation and Drive s - SCE T I A Training Document Page 33 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 34 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example Below, the block diagram for the CU240S PN is shown.
A utomation and Drive s - SCE T I A Training Document Page 35 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example Terminal Number w ith Name and Function: 1 +10V OUT Output without isolation, +10V, max.
A utomation and Drive s - SCE T I A Training Document Page 36 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 37 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 38 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 39 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 40 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 41 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.5.1.1 Function Keys of the Basic Operator Panel (BOP) The following keys are available on the BOP.
A utomation and Drive s - SCE T I A Training Document Page 42 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 43 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 44 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 45 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 46 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 47 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 48 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 49 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 50 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 51 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 52 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 53 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 2. Along with the STARTER, the project wizard is started.
A utomation and Drive s - SCE T I A Training Document Page 54 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 4. Now, we are changing and testing the PG/PC interface.
A utomation and Drive s - SCE T I A Training Document Page 55 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.
A utomation and Drive s - SCE T I A Training Document Page 56 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 8. Under the tab ’RS 485’ , select the ’Automatic Mode’ .
A utomation and Drive s - SCE T I A Training Document Page 57 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 10. We are accepting the interface ’PC COM-Port (USS)’ that is now set with ’Continue’ .
A utomation and Drive s - SCE T I A Training Document Page 58 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 12. Under ’Summary’ (Item 4), we once more see all project settings.
A utomation and Drive s - SCE T I A Training Document Page 59 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 14. Now, first select your control unit (CU240S PN) on the basis of the order number.
A utomation and Drive s - SCE T I A Training Document Page 60 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 16. After you have checked your se lection, choose the option: ’Start the Startup w izard’ .
A utomation and Drive s - SCE T I A Training Document Page 61 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 18.
A utomation and Drive s - SCE T I A Training Document Page 62 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 20. Now, the ’Motor type’ is selected.
A utomation and Drive s - SCE T I A Training Document Page 63 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 22. If you connected an encoder, select it now, or select ’Sw itched off (0)’ .
A utomation and Drive s - SCE T I A Training Document Page 64 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 24. Now, important parameters can be set such as ’Motor overload factor’ , ’Min.
A utomation and Drive s - SCE T I A Training Document Page 65 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 26.
A utomation and Drive s - SCE T I A Training Document Page 66 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 28.
A utomation and Drive s - SCE T I A Training Document Page 67 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 30. Now, click on' ’, and the configuration is loaded to the SINAMICS G120.
A utomation and Drive s - SCE T I A Training Document Page 68 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 31.
A utomation and Drive s - SCE T I A Training Document Page 69 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 32. With the ’Control board’ , the SINAMICS G120 can be controlled directly from the STARTER for test purposes.
A utomation and Drive s - SCE T I A Training Document Page 70 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 34. With a checkmark, the ’Enables’ required for operation can be set without further ado.
A utomation and Drive s - SCE T I A Training Document Page 71 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 36. Ultimately, the ’master control’ has to be ’returned’ .
A utomation and Drive s - SCE T I A Training Document Page 72 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.5.3 Startup w ith the Micro Memory Card (MMC) 3.
A utomation and Drive s - SCE T I A Training Document Page 73 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 74 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 75 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 4.
A utomation and Drive s - SCE T I A Training Document Page 76 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3. The project is now assigned the ’Name’ ’Elevator_SINAMICS_DP’ ( → Aufzug_SINAMICS_DP → OK) 4.
A utomation and Drive s - SCE T I A Training Document Page 77 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 5. Then, a ’SIMATIC 300-Station’ is inserted.
A utomation and Drive s - SCE T I A Training Document Page 78 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 7. Open the hardware catalog by clicking on ' ’.
A utomation and Drive s - SCE T I A Training Document Page 79 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 8.
A utomation and Drive s - SCE T I A Training Document Page 80 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 9. Next, we drag the ’CPU 315F-2 PN/DP’ to the second slot.
A utomation and Drive s - SCE T I A Training Document Page 81 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 82 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 11. Drag the digital input module with 16 inputs to Slot 4.
A utomation and Drive s - SCE T I A Training Document Page 83 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 13. By default, the RS485 interface of the CPU is set to the MPI.
A utomation and Drive s - SCE T I A Training Document Page 84 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 15. Now, select an ’Address’ and click on the ’PROFIBUS(1)’ network.
A utomation and Drive s - SCE T I A Training Document Page 85 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 17. With ’Brow se’ , select the path on your PC where you stored the GSD files.
A utomation and Drive s - SCE T I A Training Document Page 86 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 20.
A utomation and Drive s - SCE T I A Training Document Page 87 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 22. By clicking on ' ’, the configuration tabl e is saved and compiled.
A utomation and Drive s - SCE T I A Training Document Page 88 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 23.
A utomation and Drive s - SCE T I A Training Document Page 89 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 25. Confirm the change of the access path to CP5611[Auto] with ’OK’.
A utomation and Drive s - SCE T I A Training Document Page 90 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 27. Confirm the CPU 315F-2 PN/DP as destination module for loading the configuration table.
A utomation and Drive s - SCE T I A Training Document Page 91 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 29. Then, the MPI address of the CPU in the network is selected.
A utomation and Drive s - SCE T I A Training Document Page 92 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 31. After the hardware conf iguration is created, the ’SIMATIC 300 Station’ is located in the SIMATIC Manager.
A utomation and Drive s - SCE T I A Training Document Page 93 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 33. To configure the SINAMICS G 120, the parameter assignment tool ’STARTER’ is opened with ’Open object’ .
A utomation and Drive s - SCE T I A Training Document Page 94 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 35. Now, first select your control unit based on the order number (Control Unit CU240S DP).
A utomation and Drive s - SCE T I A Training Document Page 95 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 37. After you have checked your selection, select the option: ’Now start the startup w izard’ .
A utomation and Drive s - SCE T I A Training Document Page 96 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 39.
A utomation and Drive s - SCE T I A Training Document Page 97 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 41. Now, select the ’Motor type’ .
A utomation and Drive s - SCE T I A Training Document Page 98 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 43. If you connected an encoder, you have to select it now, or select ’Disabled(0)’ .
A utomation and Drive s - SCE T I A Training Document Page 99 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 45. Now, important parameters can be set such as ’Motor overload factor’ , ’Min.
A utomation and Drive s - SCE T I A Training Document Page 100 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 47.
A utomation and Drive s - SCE T I A Training Document Page 101 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 49. By clicking on ' ’, the configuration is saved and compiled ( → → OK) 50.
A utomation and Drive s - SCE T I A Training Document Page 102 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 51.
A utomation and Drive s - SCE T I A Training Document Page 103 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 53. By clicking on ' ’, the configuration can now be loaded to the SINAMICS G120.
A utomation and Drive s - SCE T I A Training Document Page 104 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 54.
A utomation and Drive s - SCE T I A Training Document Page 105 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 5.
A utomation and Drive s - SCE T I A Training Document Page 106 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 3.
A utomation and Drive s - SCE T I A Training Document Page 107 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 5. Then, a ’SIMATIC 300 Station’ is inserted.
A utomation and Drive s - SCE T I A Training Document Page 108 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 7. Open the hardware catalog by clicking on ' ’.
A utomation and Drive s - SCE T I A Training Document Page 109 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 8.
A utomation and Drive s - SCE T I A Training Document Page 110 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 9. Next, we are dragging the ’CPU 315F-2 PN/DP’ to the second slot .
A utomation and Drive s - SCE T I A Training Document Page 111 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Start.
A utomation and Drive s - SCE T I A Training Document Page 112 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 10. Drag the digital input module with 16 inputs to Slot 4.
A utomation and Drive s - SCE T I A Training Document Page 113 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 12.
A utomation and Drive s - SCE T I A Training Document Page 114 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 13. Now, select the ’Device version’ and confirm with ’OK’ .
A utomation and Drive s - SCE T I A Training Document Page 115 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 15. To each IO device, a ’Device name’ has to be assigned that is unique within the PROFINET IO system.
A utomation and Drive s - SCE T I A Training Document Page 116 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 17.
A utomation and Drive s - SCE T I A Training Document Page 117 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 19. Confirm changing the access path to TCP/IP with ’OK’ ( → OK ) 20.
A utomation and Drive s - SCE T I A Training Document Page 118 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 21. Now, the frequency converter has to be selected in order to ’Assign name’ .
A utomation and Drive s - SCE T I A Training Document Page 119 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 22. By clicking on ' ’, the configuration table can now be loaded to the PLC.
A utomation and Drive s - SCE T I A Training Document Page 120 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 23. The CPU 315F-2 PN/DP is confirmed as the destination module for loading the configuration table.
A utomation and Drive s - SCE T I A Training Document Page 121 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 25. Then, the MAC address of the CPU on the Ethernet is selected.
A utomation and Drive s - SCE T I A Training Document Page 122 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 27.
A utomation and Drive s - SCE T I A Training Document Page 123 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 29. Now, first select your control unit by using the order number (CU240S PN).
A utomation and Drive s - SCE T I A Training Document Page 124 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 31. After you have checked your selection, select the option: ’Now start the commissioning wi z a r d ’ .
A utomation and Drive s - SCE T I A Training Document Page 125 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 33.
A utomation and Drive s - SCE T I A Training Document Page 126 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 35. Now, the ’Motor type’ is selected.
A utomation and Drive s - SCE T I A Training Document Page 127 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 37. If an encoder is connected, you eit her have to select it, or select ’Sw itchedOff(0)’ .
A utomation and Drive s - SCE T I A Training Document Page 128 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 39. Now, important parameters can be set such as ’Motor overload factor’ , ’Min.
A utomation and Drive s - SCE T I A Training Document Page 129 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 41.
A utomation and Drive s - SCE T I A Training Document Page 130 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 43. By clicking on ' ’, the configuration is saved and compiled ( → → OK) 44.
A utomation and Drive s - SCE T I A Training Document Page 131 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 45.
A utomation and Drive s - SCE T I A Training Document Page 132 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 47. By clicking on ' ’, you can now load the configur ation to the SINAMICS G120.
A utomation and Drive s - SCE T I A Training Document Page 133 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 48.
A utomation and Drive s - SCE T I A Training Document Page 134 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6. CONTROL PROGRAM 'BUCKET ELEVATOR’ ON THE PROFIBUS DP/PROFINET 6.
A utomation and Drive s - SCE T I A Training Document Page 135 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Star.
A utomation and Drive s - SCE T I A Training Document Page 136 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.1.2 The Status Word (ZSW) Bit No.
A utomation and Drive s - SCE T I A Training Document Page 137 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.
A utomation and Drive s - SCE T I A Training Document Page 138 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.
A utomation and Drive s - SCE T I A Training Document Page 139 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.
A utomation and Drive s - SCE T I A Training Document Page 140 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 2. Enter the following symbol table in your project.
A utomation and Drive s - SCE T I A Training Document Page 141 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.3 Generating the Data Block for the Request Message 4.
A utomation and Drive s - SCE T I A Training Document Page 142 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6. Enter DB20 and save it.
A utomation and Drive s - SCE T I A Training Document Page 143 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.4 Generating the Data Block for the Response Message 7.
A utomation and Drive s - SCE T I A Training Document Page 144 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.5 Generating Function FC10 to Control the Bucket Elevator 8.
A utomation and Drive s - SCE T I A Training Document Page 145 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Star.
A utomation and Drive s - SCE T I A Training Document Page 146 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.6 Generate Organization Block OB1 for Controlling the Bucket Elevator 9.
A utomation and Drive s - SCE T I A Training Document Page 147 of 147 Module H01 Issued: 02/2008 Frequency Converter SINAMI CS G120 on PROFIBUS DP and PROFINET Preface Notes Startup with PROFIBUS Startup with PROFINET Program Example 6.7 Load the blocks for controlling the bucket elevator to the CPU 315-2DP 10.
Ein wichtiger Punkt beim Kauf des Geräts Siemens G120 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Siemens G120 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Siemens G120 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Siemens G120 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Siemens G120 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Siemens G120 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Siemens G120 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Siemens G120. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Siemens G120 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.