Battery Inst allation MGE™ Galaxy™ 3 00 10-40 kV A 380/400/415 V 10-40 kVA.
.
Content s MGE™ Galaxy ™ 300 10-40 kVA 3: 3 - 380/400 /415 V, 10-30 kVA 3:1 - 380/4 00/415 V Installatio n i Overview . ............. ......... ............. ...... ...... ......... ............. .... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS .
MGE™ Ga laxy™ 300 1 0-40 kVA 3:3 - 380 /400/415 V , 10-30 kVA 3:1 - 3 80/400/415 V Insta llation ii Checklist.... ............. ...... ......... ............. ......... ............. ...... 15 Appendi x .......... ............ ...... ....... .....
1 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Overview IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS W arning: ALL safety i nstructions in t he Safety S heet (990-3620 ) must be r ead, understo od and followed when ins t alli ng the UPS and XR Battery e nclsour e(s).
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 2 Product Overview Battery shelves Battery circuit breaker Ground cable conn ect ion (from the UP S) B.
3 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Cables and Batteries Note: The batter y enclosure mu st be inst alled on a non-i nflammable, level and solid floor . Prep are for Cab les 1. Open the fr ont door . 2.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 4 Battery enclos ure with p re-inst alled batteries W arning: Remove al l card board used to pr otect the batter ies during transport. Make sur e that cables and coppe r bars are se parated.
5 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation 2. Connect th e batteries to the batt ery breaker by running t he cables from the ba ttery br eaker to each shel ve. Note! Make sure to run th e cab les in this order .
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 6 Note: A maximum of t wo batter y enclosures can be connect ed to the UPS (one XR Bat tery enclos ure with a circ uit breake r plus one en closure wi thout a circuit b r eaker ) by a batch cable betwe en the UPS an d the circuit br eaker in th e batter y enclosure.
7 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Connect Co mmunicatio n Cables between the UPS and Ba ttery En closure External battery tempera ture (A TIZ) and externa l battery breaker signal Note: The A TIZ c able is f or external bat tery tempe rature detect ion si gnal (cab le is pre- instal led).
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 8 Connect the Battery Cable s between th e UPS and Battery Enclosure W arning: This pr ocedure de scribes how to connect t he initi al battery ca bles between the UPS and XR befor e star t-up.
9 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation 5. Connect th e battery cable s to the batter y terminal s in the UPS. See the UPS inst allation manual for info rmation on how to remove the I/ O sheet metal c over .
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 10 Connect an XR Battery Enclosure to a r unning UPS W arning: Befor e connecting an XR bat tery encl osure , ALL safety instructi ons in the Safety S heet (990-3620) must be r ead, understood and followed.
11 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Electrica l Hazard: Check the DC volta ges with a DC volt age multimeter versus the bat t ery voltage before continui ng. 7. T urn the XR batter y breaker (QFB) to the ON ( closed) posit i on.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 12 Replace t he Batteries W arning: Befo re battery replace ment, A LL sa fety ins truc tions in the S afety S heet ( 990- 3620) must be r ead, understood and followed. Fa ilur e to do so could r esult in equ ipment damage, ser i ous i njury , or death.
13 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation S pecifications Battery Output Recommended Cable Sizes Caution: All wirin g must co mply with all appl icable nationa l and/or e lectrical co des.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 14 Recommended Bolt and Lug Size T orque sp ecifications Battery T erminal Bolt size T orque CSB 910-0631 c lip 910-0633 M6 5.4 NM (max 8.2 NM) YUASA 912-0001 M5 2.5 NM (max 6 NM) 910-0632 M6 4.
15 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Checklist Make sure th at all cardb oard and st rappings h ave been r emoved. Check that the power wiring is torqued as described in the torque specification table above.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 16 Appe ndix One-li ne diagrams Note: Use the bel ow table as a hel p to find t he diagram that f its your system. Note: - marked cables are a ssembled by the manufacturer .
17 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling YUASA 15 kV A 60 min. No. Item Description Part no.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 18 Battery cabling YUASA 20/30 kV A 60 min. No. Item Description Part no.
19 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling YUASA 40 kV A 60 min. No. Item Description Part no.
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 20 Battery cabling CSB 15 kV A 60 min. No. Item Description Part no. Qty .
21 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling CSB 30 kV A 60 min. No. Item Description Part no. Qty .
MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 22 Battery cabling CSB 40 kV A 60 min. No. Item Description Part no. Qty .
.
6/2010 990-3617-001 *990-3617-001* APC W orldwide Customer Support Customer s upport for this or any other AP C product is avai lable at no char ge in any of the foll owing ways: • V isit th e APC W eb site to acce ss docu ments in t he APC Knowledge Base a nd to subm it custo m er support requests.
Ein wichtiger Punkt beim Kauf des Geräts APC 300 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie APC 300 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für APC 300 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von APC 300 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über APC 300 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon APC 300 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von APC 300 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit APC 300. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei APC 300 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.