505309-UIM-D-0511 EFFICIENCY RATING CERTIFIED ISO 9001 Certified Quality Management System RESIDENTIAL GAS FURNACE MODELS: TM9T*MP (96% AFUE T wo St age Multi-position) INSTALLATION MANUAL LIST OF SECTIONS SAFETY . . . . . . . . . . . . . . . . . . . .
505309-UIM-D-0511 2 Johnson Controls Unitary Products These high efficiency , compact units employ induced combustion, reli- able hot surface ignition and high hea t transfer aluminized tubular heat exchangers. The units are factory shipped for installation in upflow or horizontal applications and may be converted for downflow applica- tions.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 3 • This furnace is not approved for installation in trailers or recre- ational vehicles. • Furnaces for installation on co mbustible flooring shall not be installed directly on carpeting, t ile or other combustible material other than wood flooring.
505309-UIM-D-0511 4 Johnson Controls Unitary Products INSPECTION As soon as a unit is r eceived, it should be inspected for possible dam- age during transit. If damage is evident, th e extent of the damage should be noted on the carrier ’s freight bill.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 5 SECTION II: DUCTWORK DUCTWORK GENERAL INFORMA TION The duct system’s design and installation must: 1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.
505309-UIM-D-0511 6 Johnson Controls Unitary Products COIL INST ALLA TION COIL/FURNA CE ASSEMBL Y - MC/FC/PC SERIES COILS FURNACE ASSEMBL Y - MC & FC SERI ES COILS These coils are factory shipped for installation in either upflow or down- flow applications with no conversion.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 7 Dimension “C” should be at least 2/3 of dimension “D”. See Figure 6 CRITICAL COIL PROJECTION The coil assembly must be located in the duct such that a minimum dis- tance is maintained between the top of the coil and the top of the duct.
505309-UIM-D-0511 8 Johnson Controls Unitary Products HORIZONT AL APPLICA TION A TTIC INST ALLA TION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 9 SECTION III: FIL TERS FIL TER INST ALLA TION All applications require the use of a field installed filter . All filters and mounting provision must be field supplied. Filters must be installed external to the furnace cabinet.
505309-UIM-D-0511 10 Johnson Controls Unitary Products HORIZONT AL APPLICA TION Horizontal Filters Any branch duct (rectangular or r ound duct) attached to the plenum must attach to the vertical plenum before the filter . The use of straps and/or supports is required to support the weight of the external filter box.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 11 GAS ORIFICE CONVERSION FOR PR OP ANE (LP) This furnace is constructed at the facto ry for natural gas-fired operation, but may be converted to operate on propane (LP) gas by using a factory-supplied LP conversion kit.
505309-UIM-D-0511 12 Johnson Controls Unitary Products Annual Fuel Utilizat ion Efficiency ( A FUE) numbers are determined in accordan ce with DOE T est procedures. Wire size and over current protection must comply with the National Electri cal Code (NFP A-70-latest edition) and all local code s.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 13 For additional connection diagrams for all J ohnson Controls Unitary Products’ equipment refer to “Low V oltage System Wiring” do cument available on-line at www .upgnet.com in the Product Catalog Section.
505309-UIM-D-0511 14 Johnson Controls Unitary Products FIGURE 19: Thermostat Chart - T wo Stage HP with T wo Stage PSC Furnace HP 22A O Reversing Va lve Energized in Cool C 24 – Vo lt Com mon R 24 .
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 15 ACCESSOR Y CONNECTIONS The furnace control will allow power-switching control of various accessories. ELECTRONIC AIR CLEANER CONNECTIO N T wo 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board.
505309-UIM-D-0511 16 Johnson Controls Unitary Products T w inning Instructions Connect the control wiring as shown in Figure 21. 1. Connect the low voltage wiring fr om the wall thermostat to the termi- nal strip on the control board of Furnace #1. 2.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 17 The condensate will flo w to the dr ain better if an open stand pipe is installed in the drain line. See Figure 22. If evaporator coil or humidifier drains are combined with the furnace drain, then the open stand pipe could be raised higher , above the 5” minimum.
505309-UIM-D-0511 18 Johnson Controls Unitary Products FIGURE 24: Upflow Configuration INDUCER ROT A TED FOR LEFT SIDE VENTING UPFLOW AS RECEIVED INDUCER ROT A TED FOR RIGHT SIDE VENTING When drain hose routing changes are required, be sure to cap all un-used openings.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 19 FIGURE 25: Downflow Configuration AIRFLOW AIRFLOW Move rain gutter hose to this position. DOWNFLOW - INDUCER ROT A TED FOR LEFT SIDE VENTING DOWNFLOW - INDUCER ROT A TED FOR RIGHT SIDE VENTING Move pressure switch hose to this position.
505309-UIM-D-0511 20 Johnson Controls Unitary Products FIGURE 26: Horizontal Left Configuration HORIZONT AL - LEFT INDUCER ROT A TED HORIZONT AL - LEFT INDUCER AS RECEIVED AIRFLOW AIRFLOW Move pressure switch hose to this position. NOTE: May require the longer hose that is provided with wider cabinets.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 21 FIGURE 27: Horizontal Right Configuration AIRFLOW HORIZONT AL - RIGHT INDUCER ROT A TED HORIZONT AL - RIGHT INDUCER AS RECEIVED Move rain gutter hose to this position. Move pressure switch hose to this position.
505309-UIM-D-0511 22 Johnson Controls Unitary Products SECTION VIII: COMB USTION AIR AND VENT SY STEM COMBUSTION AIR AND VENT SAFETY This Category IV , dual certified direct vent furnace is designed for resi- dential application.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 23 Dimensions are those requi red in Stand ard ASTM D-331 1. Example: An 80,000 BTUH furnace requires 3 2 feet of pipe and five 90º elbows.
505309-UIM-D-0511 24 Johnson Controls Unitary Products VENT CLEARANCES † A vent shall not terminate directly above a sidewalk or pa ved driveway that is located between t wo single family dwellings and serves both dwellings. †† 12” (30.5 cm) up from the botto m edge of the structur e for T wo- pipe (direct vent) applications per ANSI Z223.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 25 VENT SY STEM This furnace is certified to be installed with one of two possible vent configurations. 1. Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.
505309-UIM-D-0511 26 Johnson Controls Unitary Products DOWNWA RD VENTING In some applications, it may be neces sary to run the ven t pipe and air intake downwards.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 27 An unconfined space is not less than 50 cu.f t (1.42 m 3 ) per 1,000 Btu/ hr (0.293 kW/h) input rating for all of the appliances installed in that area.
505309-UIM-D-0511 28 Johnson Controls Unitary Products Combustion Air Source from Out doors 1. T wo permanent opening s, one within 12” (30.5 cm) of the top and one within 12” (30.5 cm) of bottom of the confined space, T wo per- manent openings, shall communicate directly or by means of ducts with the outdoors, crawl spaces or attic spaces.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 29 SECTION IX: ST ART -UP AND ADJUSTMENTS The initial start-up of the furnace requires the following addition al procedures: When the gas supply is initially connec ted to the furnace, the ga s piping may be full of air .
505309-UIM-D-0511 30 Johnson Controls Unitary Products T able 15: Gas Rate (CU FT/HR) at Full Inpu t Seconds For 1 Revolution Size of T est Dial Seconds For 1 Revolution Size of T est Dial 1 Cu Ft 2 C.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 31 ADJUSTMENT OF MANIFO LD GAS PRESSURE & INPUT RA TE Inlet and manifold gas pressure may be measured by connecting the “U” tube manometer to the gas valve with a piece of tubing. Follow the appropriate section in the instructions below.
505309-UIM-D-0511 32 Johnson Controls Unitary Products ADJUSTMENT OF TEMPERA TURE RISE After about 5 minutes of operation, determine the furnace temperature rise. T ake readings of both the return air and the heated air in the ducts, about six feet (1.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 33 NOTES: 1.Airflow expressed in st andard cubic feet per minute (CFM). 2.Return air is through side opposite mot or (lef t side). 3.Motor voltage at 1 15 V . 4.Airflow thro ugh across motor side ( right side) ma y be sli ghtly less than the data shown above.
505309-UIM-D-0511 34 Johnson Controls Unitary Products SECTION X: SAFETY CONTROLS CONTROL CIR CUIT FUSE A 3-amp fuse is provided on the control circuit board to protect the 24- volt transformer from overload caus ed by control circ uit wiring errors. This is an A TO 3, automotive type fuse and is located on the control board.
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 35 FURNA C E CONTROL DIA GNOSTICS The furnace has built-in, self-diagnos tic capability . A blinking LED light on the control board can flash red, green or amber to indicate various conditions. The control con tinuou sly monitors its own operation and the operation of the system.
505309-UIM-D-0511 36 Johnson Controls Unitary Products DIAGNOSTIC F A UL T CODE STORA GE AND RETRIEV AL The control in this furnace is equipped with memory that will store up to five error codes to allow a serv ice technician to diagnose problems more easily .
505309-UIM-D-0511 Johnson Controls Unitary Produ cts 37 SECTION XIII: WIRING DIAGRAM FIGURE 43: Wiring Diagram LEGEND DSDoorswitch MOTCirculatingmotor LS.
Subject to change without not ice. Published in U.S.A. 505309-UIM-D-0511 Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 505309-UIM-C-0910 Johnson Contro ls Unit ary Produ.
Ein wichtiger Punkt beim Kauf des Geräts Johnson Controls TM9T*MP (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Johnson Controls TM9T*MP noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Johnson Controls TM9T*MP - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Johnson Controls TM9T*MP reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Johnson Controls TM9T*MP erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Johnson Controls TM9T*MP besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Johnson Controls TM9T*MP verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Johnson Controls TM9T*MP. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Johnson Controls TM9T*MP gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.