Montageund GebrauchsanweisungDeutsch Installation and Operating InstructionsEnglish Instructions d’installation et d’utilisationFrançais
Dimplex SI 75ZSR — SI 75ZSR diagram (page 1)
Abb. 1
Dimplex SI 75ZSR — SI 75ZSR diagram (page 1)
Abb. 2
Dimplex SI 75ZSR — SI 75ZSR diagram (page 1)
Abb. 3

Sole/WasserWärmepumpe für Innenaufstellung

Brine-to-Water Heat Pump for Indoor Installation

Pompe à chaleur eau glycolée-eau pour installation intérieure

Bestell-Nr. / Order no. / No de commande : 452234.66.09 FD 8708

Page 3 of the Dimplex SI 75ZSR user manual — 1.3 Energy-Efficient Use of the Heat Pump
Seite 3 · Zum Vergrößern klicken
Seite 3

1 Read immediately

1.2 Legal Provisions and Guidelines

1.1 Important Information

This heat pump conforms to all relevant DIN/VDE regulations and EU directives. For details refer to the EC Declaration of Con- formity in the appendix.

The electrical connection of the heat pump must be performed according to and conforming with all relevant VDE, EN and IEC standards. Beyond that, the connection requirements of the local utility companies have to be observed.

The heat pump is to be connected to the heat source system and the heating or cooling system in accordance with all applicable regulations.

1.3 Energy-Efficient Use of the Heat Pump

By operating this heat pump you contribute to the protection of our environment. The heating or cooling system and the heat source must be properly designed and dimensioned to ensure ef- ficient operation. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers con- nected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Low-temperature heat- ing systems with flow temperatures between 30 °C and 50 °C are optimally suited for energy-efficient operation.

Page 4 of the Dimplex SI 75ZSR user manual — Cooling
Seite 4 · Zum Vergrößern klicken
Seite 4

2 Purpose of the heat pump

3 Baseline Unit

The baseline unit consists of a heat pump, ready for connection, for indoor installation, complete with sheet metal cabinet, control box and integrated controller. The refrigeration cycle contains the refrigerant R404A. Refrigerant R404A is CFC-free, non-ozone depleting and non-combustible.

2.1 Application

The brine-to-water heat pump is designed for use in existing or newly built heating systems. Brine is used as the heat carrier in the heat source system. Ground coils, ground collectors or simi- lar systems can be used as the heat source.

All components required for the operation of the heat pump are located in the control box. A sensor for the external wall temper- ature including mounting hardware as well as a strainer are sup- plied with the heat pump. The voltage supply for the load and control current must be provided by the customer.

2.2 Principle of Operation

The control wire of the brine pump (to be provided by the cus- tomer) is to be connected to the control box. When so doing, a motor protecting device is to be installed, if required.

Heating

The heat generated by the sun, wind and rain is stored in the ground. This heat stored in the ground is collected at low temper- ature by the brine circulating in the ground collector, ground coil or similar device.

The collector including the brine manifold must be provided by the customer.

A circulating pump then conveys the warmed brine to the evapo- rator of the heat pump. There, the heat is given off to the refrig- erant in the refrigeration cycle. When so doing, the brine cools so that it can again take up heat energy in the brine circuit.

Dimplex SI 75ZSR — Heating diagram (page 4)
Abb. 4 · Heating

The refrigerant is drawn in by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost in this process, but most of the generated heat is transferred to the re- frigerant.

Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water. Based on the thermostat setting, the heating water is thus heated to up to 60 °C.

Cooling

The functions of the evaporator and the liquifier are reversed in the “Cooling” operating mode.

The heating water gives up its heat to the refrigerant via the liqui- fier which is now functioning as an evaporator. The refrigerant is pumped to a higher temperature level using the compressor. Heat passes into the brine via the liquifier (evaporator in heating operation) and consequently into the ground.

1. Control
2. Evaporator
3. Condenser
4. Compressor
5. Transport securing devices
6. Filter drier

· ·

Page 5 of the Dimplex SI 75ZSR user manual — 5HPRYHVFUHZLQ WUDQVSRUWORFN
Seite 5 · Zum Vergrößern klicken
Seite 5

4 Accessories

6 Installation

4.1 Connecting Flanges

6.1 General Information

The use of flat-sealing connecting flanges allows the unit, as an option, to be connected by means of flanges.

As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should make full contact with the surface in order to ensure adequate sound insu- lation. Failing this, additional sound insulation measures may be- come necessary.

5 Transport

The heat pump should be installed to allow easy maintenance/ service access. This is ensured if a clearance of approx. 1 m in front of the heat pump is maintained.

For the transport by means of a hand truck or boiler trolley, po- sition the latter under the front end of the unit below the transport security device.

For transport on a level surface, the unit can be lifted from the rear or from the front by means of a lift truck or forklift. In this case, the transport securing device is not imperative.

P

Dimplex SI 75ZSR — P diagram (page 5)
Abb. 5
Dimplex SI 75ZSR — P diagram (page 5)
Abb. 6

P

6.2 Sound Emissions

Dimplex SI 75ZSR — 6.2 Sound Emissions diagram (page 5)
Abb. 7 · 6.2 Sound Emissions

The heat pump offers silent operation due to efficient sound insu- lation. Any vibration transmission to the foundation or the heating system can be largely prevented by internal sound decoupling measures.

7 Mounting

5HPRYHVFUHZLQ WUDQVSRUWORFN

7.1 General Information

The following connections need to be estab-lished on the heat pump:

After the transport, the transport securing device is to be re- moved on either side at the bottom of the unit.

„ supply/return flow of the brine system

„ supply/return flow of the heating system

To remove the panelling, open the individual covers by unscrew- ing the respective turn-lock fasteners and then gently tilting the covers away from the device. Then lift them up out of the mount- ings.

ƒ · ƒ · „ power supply

Page 6 of the Dimplex SI 75ZSR user manual — 7.3 Connection on Heat Source Side
Seite 6 · Zum Vergrößern klicken
Seite 6

7.2 Connection on Heating Side

7.4 Electrical Connection

The following electrical connections must be established on the heat pump:

„ Connection of the control wire to terminals X1: L/N/PE in the

control box of the heat pump.

Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to re- move any impurities that may be present, as well as residues of sealing material, and the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.

„ Connection of the load wire to terminals X5: L1/L2/L3/PE in

the control box of the heat pump.

„ Connection of the brine pump (to be supplied by the cus-

tomer) to terminal PE and pump contactor K5: 2/4/6 on the control panel of the HP.

All electrical components required for the operation of the heat pump are located in the control box.

For more detailed instructions concerning the connection and functioning of the heat pump controller (e.g. the supplied external wall sensor) please refer to the enclosed operating manual of the controller.

Once the installation on the heating side has been completed, the heating system must be filled, de-aerated and pressure- tested.

An automatic circuit-breaker with simultaneous tripping of all ex- ternal conductors is to be provided in the load power supply. The circuit-breaker must be an all-pole disconnect device with a con- tact gap of at least 3 mm. The same applies to any additional dis- able contactors that may be required, e.g. during shut-off periods imposed by the utility company. The required cross-sectional area of the conductors is to be selected according to the power consumption of the heat pump, the technical connection require- ments of the relevant utility company and all applicable regula- tions. Power consumption data of the heat pump is provided in the product literature and on the nameplate. The terminals are designed for a max. conductor cross-section of 35 mm².

Heating water minimum flow rate

The heating water minimum flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing a differential pressure-free manifold or an overflow valve. The procedure for setting an overflow valve is described in the Chapter Commis- sioning.

Frost protection for installations prone to frost

Provided the controller and heating circulating pumps are ready for operation, the frost protection feature of the controller is ac- tive. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump instal- lations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.

7.3 Connection on Heat Source Side

Dimplex SI 75ZSR — 7.3 Connection on Heat Source Side diagram (page 6)
Abb. 8 · 7.3 Connection on Heat Source Side

The following procedure must be observed when making the connection:

Connect the brine line to the flow and return pipe of the heat pump.

The hydraulic plumbing diagram must be observed here.

In addition, a microbubble deaerator must be installed in the heat source system.

The power cable must be run through the guide tubes, inserted into the side of the control box and secured by means of the strain relief.

The brine liquid must be produced prior to charging the system. The brine concentration must be at least 25 %. Freeze protection down to -14°C can thus be ensured.

Only antifreeze products on the basis of mono-ethylene glycol or propylene glycol may be used.

The heat source system must be vented (de-aerated) and checked for leaks.

Page 7 of the Dimplex SI 75ZSR user manual — 8.2 Preparatory Steps
Seite 7 · Zum Vergrößern klicken
Seite 7

8 Commissioning

8.3 Commissioning Procedure

The start-up of the heat pump is effected via the heat pump con- troller.

8.1 General Information

To ensure proper commissioning it should be carried out by a customer service authorised by the manufacturer. This will lead, under certain circumstances, to an extension of the warranty pe- riod (cf. Warranty). Start-up should be carried out in heating op- eration.

Where an overflow valve is fitted to assure the minimum heating water flow rate, the valve must be set in accordance with the re- quirements of the heating installation. An incorrect setting may result in various error symptoms and an increased elec-tric power consumption. To correctly set the overflow valve, the fol- lowing procedure is recommended:

8.2 Preparatory Steps

Prior to commissioning, the following items need to be checked:

„ All connections of the heat pump must have been made as

Close all of the heating circuits which may also be closed during operation (depending on the type of heat pump usage) so that the least favourable operating state - with respect to the water flow rate - is achieved. Normally, these heating circuits are those of the rooms located on the south and west sides of buildings. At least one heating circuit must remain open (e.g. bathroom).

described in Chapter 7.

„ The heat source system and the heating circuit must have

been filled and checked.

„ The strainer must have been fitted in the sole inlet of the

heat pump.

„ In the brine and heating circuits all valves that might impair

The overflow valve is to be opened to such an extent that based on the current heat source temperature the maximum tempera- ture difference between heating supply and return flow tempera- ture is obtained, as indicated in the table below. The tempera- ture difference should be measured as closely to the heat pump as possible. In mono-energetic systems, the electric heating ele- ment is to be deactivated.

the proper flow must be open.

„ The settings of the heat pump controller must be adapted to

the heating installation in accordance with the instructions contained in the controller's operating manual.

Heat source temperaturemax. difference between heating supply and return temperature fromto -5° C0° C10 K 1° C5° C11 K 6° C9° C12 K 10° C14° C13 K 15° C20° C14 K 21° C25° C15 K

Any malfunctions occurring during operation are displayed on the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.

Page 8 of the Dimplex SI 75ZSR user manual — 11 Decommissioning / Disposal
Seite 8 · Zum Vergrößern klicken
Seite 8

9 Care/Cleaning

9.3 Cleaning of Heat Source Side

9.1 Care

The heat pump is maintenance-free. To prevent malfunctions due to sediments in the heat exchangers, care must be taken that no im-purities can enter the heat source system and the heating installation. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.

The filter screen of the strainer should be cleaned one day after commissioning, thereafter every week. If no more contamination can be noticed any more, the strainer filter can be removed in order to reduce pressure losses.

9.2 Cleaning og Heating Side

10 Malfunctions / Troubleshooting

ATTENTION! Hier Satz „Im Heizwassereintritt der Wärmepumpe ... Verunreinigungen zu schützen.“ einfügen!!!

This heat pump is a quality product and designed for trouble- and maintenance-free operation. In the event that a malfunction oc- curs nevertheless, it will be indicated on the display of the heat pump controller. Simply consult the Malfunctions and Trouble- shooting table contained in the in-stallation and operating man- ual of the heat pump controller (manager).

The ingress of oxygen into the heating water circuit, in particular if it contains steel components, may result in the formation of ox- idation products (rust). These can enter the heating system via valves, circulating pumps or plastic tubing. It is therefore impor- tant - in particular with respect to the piping of underfloor heating systems - that the installation be executed in a diffusion-proof manner.

If you cannot correct the malfunction yourself, please contact the after-sales service agent in charge.

In the case of severe contamination leading to a reduction in the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.

Based on current knowledge, we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution.

11 Decommissioning / Disposal

In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger be cleaned in the di- rection opposite to the normal flow direction.

Before removing the heat pump, disconnect the unit from the power source and close all valves.

To prevent acidic cleaning agents from entering the circuit of the heating installation we recommend that the flushing device be fit- ted directly to the supply and return lines of the condenser of the heat pump.

Environment-relevant requirements regarding the recovery, re- cycling and disposal of service fuels and components in accord- ance with all relevant standards must be adhered to. Particular attention must hereby be paid to the proper disposal of refriger- ants and refrigeration oils.

Thereafter the system must be thoroughly flushed using appro- priate neutralising agents in order to prevent any damage caused by cleaning agent residues that may still be present in the sys- tem.

All acids must be used with great care, all relevant regulations of the employers' liability insurance associations must be adhered to.

If in doubt, contact the manufacturer of the chemicals!

Page 9 of the Dimplex SI 75ZSR user manual — 12 Device Information
Seite 9 · Zum Vergrößern klicken
Seite 9

12 Device Information

Device information for brine-to-water heat pumps (heating only) 1 Type and order codeSI 75ZSR 2 Design 2.1 ModelReversible 2.2 Degree of protection according to EN 60 529IP 21 2.3 Installation locationIndoors 3 Performance data 3.1 Operating temperature limits: Heating water flow °CUp to 55 Cooling, flow °C+7 to +20 Brine (heat source, heating) °C-5 to +25 Brine (heat sink, cooling) °C+5 to +30 AntifreezeMonoethylene glycol Minimum brine concentration (-13 °C freezing temperature)25% 3.2 Temperature spread of heating water (flow/return flow) at B0 / W35K5 3.3 Heat output / COP at B-5 / W55 1 kW / --- 254.9 / 2.0 kW / --- 327.3 / 2.1 at B0 / W50 1 kW / --- 262.3 / 2.5 kW / --- 331.3 / 2.5 at B0 / W35 1 kW / --- 265.3 / 3.5 kW / --- 335.1 / 3.8 3.4 Cooling capacity / COP at B20 / W8 kW / --- 282.1 / 5.0 kW / --- 344.9 / 6.4 at B20 / W18 kW / --- 2100.0 / 5.6 kW / --- 355.0 / 7.4 at B10 / W8 kW / --- 286.6 / 6.1 kW / --- 347.4 / 7.7 at B10 / W18 kW / --- 298.2 / 6.3 kW / --- 353.2 / 8.2 3.5 Sound power level dB(A)69 3.6 Sound pressure level at a distance of 1 m db(A)54 3.7 Heating water flow with an internal pressure differential of m³/h / Pa11.5 / 7300 3.8 Brine throughput with an internal pressure differential20.5 / 17800 3.9 Refrigerant; total filling weight type / kgR404A / 16.1 4 Dimensions, connections and weight 4.1 Device dimensions without connections 4 H x W x L mm1890 × 1350 × 750 4.2 Device connections to heating system InchG 2" internal/external 4.3 Device connections to heat source InchG 2 1/2" internal/external 4.4 Weight of the transportable unit(s) incl. packing kg607 5 Electrical Connection 5.1 Nominal voltage; fuse protection V / A400 / 63 5.2 Nominal power consumption 1 B0 W35 kW18.86 5.3 Starting current with soft starter A105 5.4 Nominal current B0 W35 / cos ϕ 2 A / ---34.03 / 0.8 6 Complies with the European safety regulations5 7 Additional model features 7.1 Water in device protected against freezing 6Yes 7.2 Performance levels2 7.3 Controller internal/externalInternal
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
2. Operation with 2 compressors
3. Operation with 1 compressor
4. Note that additional space is required for pipe connections, operation and maintenance.
5. See CE declaration of conformity
6. The heat circulating pump and the heat pump controller must always be ready for operation.
Page 10 of the Dimplex SI 75ZSR user manual — Anhang · Appendix · Annexes
Seite 10 · Zum Vergrößern klicken
Seite 10

Anhang / Appendix / Annexes

1 Maßbild / Dimension drawing / Schéma coté A-II

2 Diagramme / Schematics / Diagrammes ................................................................................... A-III

2.1 Heizbetrieb / Heating operation / Mode chauffage A-III 2.2 Kühlbetrieb / Cooling operation / Mode refroidissement A-IV

3 Stromlaufpläne / Wiring diagrams / Schémas électriques A-V

3.1 Steuerung Standardregler / Control via the standard controller / Commande régulateur standard A-V 3.2 Steuerung Kühlregler / Control via the cooling controller / Commande régulateur refroidissement A-VI 3.3 Last / Load / Charge A-VII 3.4 Anschlussplan Standardregler / Terminal diagram for standard controller / Schéma de branchement du régulateur standard A-VIII 3.5 Anschlussplan Kühlregler / Terminal diagram for cooling controller / Schéma de branchement du régulateur de refroidissement A-IX 3.6 Legende / Legend / Légende A-X

4 Hydraulisches Prinzipschema / Hydraulic block diagrams / Schéma hydraulique A-XII

4.1 Darstellung / Schematic view / Représentation schématique A-XII 4.2 Legende / Legend / Légende A-XIII

Anhang · Appendix · Annexes

5 Konformitätserklärung / Declaration of Conformity / Déclaration de conformité ...............A-XIV

www.dimplex.de A-I

Frage zu Dimplex SI 75ZSR stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.