

Reversible Air-to-Water Heat Pump for Indoor Installation
Pompe à chaleur air-eau réversible pour installation intérieure
Bestell-Nr. / Order no. / No de commande : 452160.66.16 FD 8611


1.3 Energy-Efficient Use of the Heat Pump
With the purchase of this heat pump you are helping to protect the environment. A prerequisite for energy-efficient operation is the correct design of the heat source system and heating (radia- tors and circulation pump) or cooling system.
It is particularly important for the efficient heating operation of a heat pump to keep the temperature difference between the heating water and the heat source as small as possible. For this reason, it is advisable to design the heat source and heating sys- tem very carefully. A temperature difference of approx. one Kelvin increases the power consumption by around 2.5%. When designing the heating system, it should be borne in mind that special consumers such as e.g. domestic hot water prepara- tion should also be taken into consideration and dimensioned for low temperatures. Underfloor heating systems (panel heat- ing) are optimally suited for heat pump use on account of the low flow temperatures (30 °C to 40 °C).
It is important to ensure that the heat exchangers are not con- taminated during operation because this increases the tempera- ture difference, in turn reducing the COP.
Correct adjustment of the heat pump controller is also important for energy-efficient use of the heat pump. Further information can be found in the heat pump controller's operating instructions.
The air-to-water heat pump is designed for use in existing or newly built heating systems.
It is designed exclusively for heating and cooling heating water!
In heating operation, the heat pump is suitable for mono energy and bivalent operation down to an external temperature of - 20 °C.
Proper defrosting of the evaporator is guaranteed by maintaining a heating water return flow temperature of more than 18 °C dur- ing continuous operation.
The heat pump is not designed for the increased heat consump- tion required when a building is being dried out. The additional heat consumption should be met using special devices provided by the customer. If a building is to be dried out in autumn or win- ter, we recommend installing an additional heating element (available as an accessory).
The construction and design of the heat pump complies with all relevant EU directives, DIN/VDE regulations (see CE declaration of conformity).
When connecting the heat pump to the power supply, the rele- vant VDE, EN and IEC standards are to be fulfilled. Any further connection requirements stipulated by local utility companies must also be observed.
In cooling operation, the heat pump is suitable for temperatures ranging from +15 °C to +40 °C.
It can be used for silent and dynamic cooling. Minimum water temperature +7 °C.
When connecting the heating and/or cooling system, all applica- ble regulations must be adhered to.
Persons, especially children, who are not capable of operating the device safely due to their physical, sensory or mental abilities or their inexperience or lack of knowledge, must not operate this device without supervision or instruction by the person in charge.
Children must be supervised to ensure that they do not play with the device.

2.2 Operating Principle
3.1 Basic Device
Surrounding air is drawn in by the ventilator and fed via the evap- orator (heat exchanger). The evaporator cools the air, i.e. it ex- tracts heat from it. This extracted heat is then transferred to the working medium (refrigerant) in the evaporator.
The heat pump is of compact design and is supplied complete with the components listed below.
R404A is used as the refrigerant.
The heat is “pumped” to a higher temperature level by increasing its pressure with the aid of an electrically driven compressor. It is then transferred to the heating water using the liquifier (heat ex- changer).

Domestic water can be prepared simultaneously, or separately, via the desuperheater connected in series.
Electrical energy is used to raise the temperature of the heat in the environment to a higher level. Because the energy extracted from the air is transferred to the heating water, this type of device is called an air-to-water heat pump.
The air-to-water heat pump consists of the main components evaporator, ventilator and expansion valve, as well as the low- noise compressor, desuperheater, liquifier and electrical control system.
At low ambient temperatures, humidity accumulates on the evap- orator in the form of frost reducing the transfer of heat. The evap- orator is defrosted automatically by the heat pump as required. Steam may be emitted from the air outlet depending on the at- mospheric conditions.
The functions of the evaporator and the liquifier are reversed in the “Cooling” operating mode.
The heating water transfers its heat to the refrigerant via the liq- uifier which is now functioning as an evaporator. The refrigerant is pumped to a higher temperature level using the compressor. Heat is passed on to the surrounding air via the liquifier (function- ing as an evaporator in heating operation).
The waste heat can also be used for hot water consumers, such as domestic hot water, swimming pool or bathroom heating, via the additional heat exchanger.

3.2 Switch Box
The switch box is located in the heat pump. It can be swung out after removing the lower front cover and loosening the fastening screw located in the upper right-hand corner.
The switch box contains the supply connection terminals, as well the power contactors, the soft starter unit and the heat pump manager.
Use a wooden pallet for transporting the heat pump to the final in- stallation location. The basic device can be transported with a lift truck, hand truck or by means of 3/4" pipes fed through the holes in the base plate or frame.

The heat pump manager is a convenient electronic regulation and control device. It controls and monitors the entire heating or cooling system on the basis of the external temperature, includ- ing hot water preparation and safety systems.
The customer must install the external temperature sensor, which is included in the scope of supply of the heat pump man- ager together with the necessary fixing accessories.
The enclosed operating instructions describe the function and use of the heat pump manager.
Before using the transport holes in the frame, it is necessary to remove the lower side panel assemblies. This is done by loosen- ing each of the two screws at the base and then withdrawing the panels by unhooking them from above. Rehang the panels by gently pushing them in an upwards direction.
Be careful not to damage any components when inserting the pipes through the frame.

Opening the cover Closing the cover

6 Installation
5.1 General Information
6.1 General Information
The unit must be installed indoors on a level, smooth and hori- zontal surface. The entire base of the frame should lie directly on the floor to ensure a good soundproof seal. If this is not the case, additional sound insulation measures may be necessary. If the device is installed on top of a built-under buffer tank, a surface that fully supports the base is required. The heat pump must be installed so that maintenance work can be carried out without hindrance. This can be ensured by maintaining a clearance of 1 m in front and to the left and right of the heat pump.
The following connections need to be established on the heat pump:
Fresh and exhaust air
Flow and return flow of the heating system
Flow and return flow of the hot water circuit
P
The glass fibre reinforced concrete air ducts offered as accesso- ries are moisture-resistant and diffusion-free.
The sealing collar is used to seal the air ducts on the heat pump. The air ducts are not screwed directly onto the heat pump. Only the rubber seal comes into direct contact with the heat pump when the system is installed correctly. This guarantees easy as- sembly and disassembly of the heat pump and also ensures that solid-borne sound is well insulated.
Never install the device in rooms subject to high humidity. Con- densation can form on the heat pump and air circuit if the humid- ity exceeds 50% and the external temperature is below O °C.
If the heat pump is installed on an upper storey, the load-bearing capacity of the ceiling should be checked. On account of the acoustics, measures for isolating possible vibrations should also be very carefully planned in advance as well. Installation on a wooden floor is not recommended.
Condensed water that forms during operation must be drained off frost-free. The heat pump must be mounted on a level plane to guarantee proper drainage. The condensed water pipe must have a minimum diameter of 50 mm and should be fed frost-free into a sewer. Condensate should not be discharged directly into clearing tanks and cesspits because the aggressive vapours could destroy the evaporator.
If another type of air duct is used, observe the external and inter- nal dimensions as specified in the figure. Also ensure that the vi- bration and duct insulation are adequate.
If flange-mounted air ducts are used, connecting stubs are se- cured on the air inlet and air outlet sides of the evaporator with 4 M8 x 16 hexagon bolts in the threaded holes provided. When doing this, ensure that both air duct stubs only touch the insula- tion. There should be no contact with the external sheeting.
To prevent solid-borne sound from being transmitted to the heat- ing system, we recommend connecting the heat pump to the heating system using a flexible hose. Connect the domestic water circuit using the same type of connection.
Installed air ducts should be sound-isolated from the heat pump to prevent the transmission of solid-borne sound to the ducts.
Condensate outflow · Power supply


A method of manual drainage (see illustration) should be pro- vided for heat pumps which are exposed to frost. The antifreeze function of the heat pump controller is active whenever the con- troller and the heat circulating pump are ready for operation. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. The heating circuit should be operated with a suitable antifreeze if heat pump systems are implemented in buildings where a power failure can not be de- tected (holiday home).

The values in parentheses are valid for the LI 16TER+
6.3 Heating and Hot Water Connection
The power supply and control voltage are supplied using stand- ard cables (load: 4-core, control: 3-core).
An all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility blocking contactor or power contactor) as well as a 3-pole circuit breaker with common tripping for all external conductors must be installed in the power supply (tripping current in compliance with the Device Information).
The heating system connections on the heat pump have a 1" ex- ternal thread. Use a spanner to firmly grip the transitions when connecting the heat pump.
Before connecting the heating water system to the heat pump, the heating system must be flushed to remove any impurities, residue from sealants, etc. Any accumulation of deposits in the liquifier could cause the heat pump to completely break down. For systems in which the heating water flow can be shut off via the radiator or thermostat valves, an overflow valve must be in- stalled by the customer in a heating bypass downstream from the heat pump. This ensures a minimum heating water flow rate through the heat pump and helps to avoid faults.
Ensure that the incoming supply has a clockwise rotating field when connecting multiphase devices L1; L2; L3.
The control voltage must be protected by a 10 A fuse.
For detailed information, see Circuit Diagrams in the Appendix.
Once the heating system has been installed, it must be filled, de- aerated and pressure-tested.
The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing either a manifold without differential pressure or an overflow valve. The procedure for adjusting an overflow valve is described in the Chapter Start-up.

To ensure that start-up is performed correctly, it should only be carried out by an after-sales service technician authorised by the manufacturer. This may be a condition for extending the guaran- tee (see Warranty Service).
Start-up should be carried out in heating operation.
The following items need to be checked prior to start-up:
All of the heat pump connections must be established as de-
scribed in Chapter 6.
All valves that could impair the proper flow of the heating
Any faults occurring during operation are also displayed on the heat pump controller and can be corrected as described in the operating instructions of the heat pump controller.
water in the heating circuit must be open.
The air intake and air outlet paths must be clear.
The ventilator must turn in the direction indicated by the ar-
For external temperatures below 10 °C and heating water tem- peratures below 16 °C, the buffer tank should be heated up with the second heat generator to at least 25 °C.
row.
The settings of the heat pump controller must be adapted to
the heating system in accordance with the controller’s oper- ating instructions.
Observe the following procedure to implement a smooth start-up:
Ensure the condensate outflow functions.
The heat pump is started up via the heat pump controller. Adjust- ments should be made in compliance with the instructions.
If an overflow valve is fitted to maintain the minimum heating water flow rate, the valve must be adapted to the requirements of the heating system. Incorrect adjustment can lead to faulty oper- ation and increased energy consumption. We recommend carry- ing out the following procedure to correctly adjust the overflow valve:
Close all of the heating circuits that may also be closed during operation (depending on the type of heat pump usage) so that the most unfavourable operating state - with respect to the water flow rate - is achieved. This normally means the heating circuits of the rooms on the south and west sides of the building. At least one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re- turn flow listed in the following table for the current heat source temperature. The temperature spread should be measured as close as possible to the heat pump. The heating element of mono energy systems should be disconnected.

8.3 Cleaning the Air System
Air ducts, evaporator, ventilator and condensate outflow should be cleaned of contamination (leaves, twigs, etc.) before each new heating period. Do this by opening the front of the heat pump. The bottom should be opened first followed by the top.
To protect the paintwork, avoid leaning anything against the de- vice or putting objects on the device. External heat pump parts can be wiped with a damp cloth and domestic cleaner.
Remove and rehang the side panel assemblies as described in Chapter 4.
To prevent faults due to sediment in the heat exchanger of the heat pump, ensure that the heat exchanger in the heating system can not be contaminated. We recommend protecting the evapo- rator by installing a bird guard in the inlet duct. At least 80% of the cross section of the grating should be open. In the event that op- erating malfunctions due to contamination still occur, the system should be cleaned as described below.
To prevent the evaporator and the condensate tray from being damaged, do not use hard or sharp objects for cleaning.
8.2 Cleaning the Heating System
This heat pump is a quality product and is designed for trouble- free and maintenance-free operation. In the event that a fault should occur, it will be indicated on the heat pump manager dis- play. Simply consult the Faults and Trouble-shooting page in the operating instructions of the heat pump manager. If you cannot correct the fault yourself, please contact your after-sales service technician.
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust), particularly if steel components are used. These products enter the heating system via the valves, the circulating pumps and/or plastic pipes. It is therefore essential - in particular with respect to the piping of un- derfloor heating systems - that only diffusion-proof materials are used.
Residue from lubricants and sealants may also contaminate the heating water.
In the case of severe contamination leading to a reduction in the performance of the liquifier in the heat pump, the system must be cleaned by a heating technician.
Before removing the heat pump, disconnect it from the power source and close all valves. Observe all environmentally-relevant requirements regarding the recovery, recycling and disposal of materials and components in accordance with all applicable standards. Particular attention should be paid to the proper dis- posal of refrigerants and refrigeration oils.
According to today’s state of knowledge, we recommend using a 5 % phosphoric acid solution for cleaning purposes. However, if cleaning needs to be performed more frequently, a 5 % formic acid solution should be used.
In either case, the cleaning fluid should be at room temperature. We recommend flushing the heat exchanger in the direction op- posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys- tem circuit, we recommend connecting the flushing device di- rectly to the flow and return flow of the liquifier of the heat pump.
It is important that the system be thoroughly flushed using appro- priate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of the employers’ liability insurance associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!


1.1 Maßbild / Dimension Drawing / Schéma coté LI 11TER+ A-II 1.2 Maßbild / Dimension Drawing / Schéma coté LI 16TER+ A-III
2.1 Heizbetrieb / Heating Operation / Mode chauffage LI 11TER+ A-IV 2.2 Kühlbetrieb / Cooling Operation / Mode refroidissement LI 11TER+ A-V 2.3 Heizbetrieb / Heating Operation / Mode chauffage LI 16TER+ A-VI 2.4 Kühlbetrieb / Cooling Operation / Mode refroidissement LI 16TER+ A-VII
3.1 Steuerung Standardregler / Control of the standard controller / Commande régulateur standard A-VIII 3.2 Steuerung Kühlregler / Control of the cooling controller / Commande régulateur standard A-IX 3.3 Last / Load / Charge A-X 3.4 Anschlussplan Standardregler / Terminal diagram for the standard controller / Schéma électrique du régulateur standard A-XI 3.5 Anschlussplan Kühlregler / Terminal diagram for the cooling controller / Schéma électrique du régulateur refroidissement A-XII 3.6 Legende / Legend / Légende A-XIII
4 Hydraulisches Prinzipschema / Hydraulic Plumbing Diagram / Schéma hydraulique .......A-XIV
4.1 Darstellung / Schematic View / Représentation A-XIV 4.2 Legende / Legend / Légende A-XV
Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.
Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.