Air-to-Water Heat Pump for Outdoor Installation
Pompe à chaleur air-eau pour installation extérieure
Bestell-Nr. / Order no. / No de commande : 452149.66.19 FD 8703


1.2 Legal Regulations and Directives
The construction and design of the heat pump complies with all relevant EU directives, DIN/VDE regulations (see CE declaration of conformity).
The relevant VDE, EN and IEC standards must be adhered to when connecting the heat pump to the power supply or carrying out maintenance work. Any further connection requirements stip- ulated by local utility companies must also be observed.
When connecting the heating system, all applicable regulations must also be adhered to.
Persons, especially children, who are not capable of operating the device safely due to their physical, sensory or mental abilities or their inexperience or lack of knowledge, must not operate this device without supervision or instruction by the person in charge.
Children must be supervised to ensure that they do not play with the device.
With the purchase of this heat pump you are helping to protect the environment. A prerequisite for energy-efficient operation is the correct design of the heat source system and heating system (radiators and circulation pump).
To maintain heat pump efficiency, it is particularly important to keep the temperature difference between the heating water and heat source to a minimum. For this reason, it is advisable to de- sign the heat source and heating system very carefully. A tem- perature difference of approx. one Kelvin increases the power consumption by around 2.5%. When designing the heating system, it should be borne in mind that special consum- ers such as e.g. DHW preparation should also be taken into con- sideration and dimensioned for low temperatures. Underfloor heating systems (panel heating) are optimally suited for heat pump use on account of the low flow temperatures (30 °C to 40 °C).
It is important to ensure that the heat exchangers are not con- taminated during operation because this increases the tempera- ture difference, in turn reducing the COP.
Correct adjustment of the heat pump controller is also important for energy-efficient use of the heat pump. Further information can be found in the operating instructions of the heat pump controller.

3 Scope of Delivery
3.1 Basic Device
2.1 Application
The heat pump is of compact design and is supplied complete with the components listed below.
The air-to-water heat pump is designed for use in existing or newly built heating systems.
R290 (propane) is used as refrigerant.
It is designed exclusively for heating domestic hot water and heating water!
The heat pump is suitable for mono energy and bivalent opera- tion down to an external temperature of -20 °C.
Proper defrosting of the evaporator is guaranteed by maintaining a heating water return flow temperature of more than 13 °C dur- ing continuous operation.

The heat pump is not designed for the increased heat consump- tion required when a building is being dried out. The additional heat consumption should be met using special devices provided by the customer. If a building is to be dried out in autumn or win- ter, we recommend installing an additional heating element (available as an accessory).
Surrounding air is drawn in by the ventilator and fed via the evap- orator (heat exchanger). The evaporator cools the air, i.e. it ex- tracts heat from it. This extracted heat is then transferred to the working medium (refrigerant) in the evaporator.
The heat is “pumped” to a higher temperature level by increasing its pressure with the aid of electrically driven compressors. It is then transferred to the heating water via the liquifier (heat ex- changer).
Electrical energy is used to raise the temperature of the heat in the environment to a higher level. Because the energy extracted from the air is transferred to the heating water, this type of device is called an air-to-water heat pump.
The air-to-water heat pump consists of the main components evaporator, ventilator and expansion valve, as well as the low- noise compressors, the liquifier and the electrical control system.
At low ambient temperatures, humidity accumulates on the evap- orator in the form of frost reducing the transfer of heat. The evap- orator is defrosted automatically by the heat pump as required. Steam may be emitted from the air outlet depending on the at- mospheric conditions.

3.2 Switch Box
The switch box is located in the heat pump. All electrical compo- nents are accessible after the front cover and the switch box cover have been removed.
The switch box contains the supply connection terminals, the plug connector for the control line, as well as the power contac- tors and the soft starter unit.
The heat pump should be transported to its final installation loca- tion packaged and using the wooden pallet. The device can be transported to its final location e.g. with a lift truck or one or two hand trucks.
Use the heat pump controller included in the scope of supply to operate the air-to-water heat pump.
The heat pump controller is a convenient electronic regulation and control device. It controls and monitors the entire heating system on the basis of the external temperature, including do- mestic hot water preparation and safety systems.

The customer must install the return temperature sensor and the external temperature sensor, which are supplied with the heat pump controller / with these instructions together with the neces- sary fixing accessories.
The operating instructions included in the scope of supply of the heat pump controller describe its function and use.
The devices LA 12PS and LA 18PS are packaged with transport pipes on the wooden pallets. These pipes can be inserted using the boreholes of the heat pump base frame (they are sealed with cover caps, which can easily be removed), and can be used for manual transport by securing them on both sides using the spring cotters to keep them from slipping out of place.


6 Installation
5.1 General Information
6.1 General Information
The heat pump is suited for outdoor installation. The device should always be installed on a permanently smooth, even and horizontal surface and must be aligned vertically. The entire frame should lie directly on the ground to ensure a good sound- proof seal and to prevent the water-bearing components from be- coming too cold. If this is not the case, additional insulation measures may be necessary. It must be possible to carry out maintenance work without hindrance. This can be ensured by maintaining a clearance of 1.2 m to any fixed walls.
The following connections need to be established on the heat pump:
Flow and return flow of the heating system
Control line to the heat pump controller
The heating system connections on the heat pump have a 1" ex- ternal thread.
Route the connection hoses out of the device in a downwards di- rection. Use a spanner to firmly grip the transitions when con- necting the heat pump. After the heat pump has been installed, the ductwork must be sealed so that the connection is gastight.
Before connecting the heating water system to the heat pump, the heating system must be flushed to remove any impurities, residue from sealants, etc., and to prevent any accumulation of deposits in the liquifier. A contaminated liquifier may cause the heat pump to completely break down. Systems in which the heat- ing water flow can be shut off via the radiator or thermostat valves must be fitted with an overflow valve downstream from the heat pump in a heating bypass (to be installed by the customer). This ensures a minimum heating water flow rate through the heat pump and helps to avoid faults.
P
Once the heating system has been installed, it must be filled, de- aerated and pressure-tested (in the heat pump the air-relief cock is located at or in the water pipes at the condenser).

5.2 Condensed Water Pipe
Condensed water that forms during operation must be drained off frost-free. The heat pump must be mounted on a level plane to guarantee proper drainage. The condensed water pipe must have a minimum diameter of 50 mm and should be fed frost-free into a sewer. Condensate should not be discharged directly into clearing tanks and cesspits because the aggressive vapours could destroy the evaporator.
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing either a manifold without differential pressure or an overflow valve. The procedure for adjusting an overflow valve is described in the Chapter Start-up.
Condensate outflow · Power supply

The control line (not included in scope of supply) is connected to the heat pump controller using the two rectangular plug connec- tors and the single-core wire. The plug connector is located on the bottom side of the switch box inside the heat pump. More de- tailed information can be found in the operating instructions of the heat pump controller.
Manual drainage should be provided for heat pumps which are exposed to frost. The antifreeze function of the heat pump con- troller is active whenever the controller and the heat circulating pump are ready for operation. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained, and if required, blown out, at three locations (see illus- tration). The heating circuit should be operated with a suitable antifreeze if heat pump systems are implemented in buildings where a power failure can not be detected (holiday home).
For detailed information, see Circuit Diagrams in the Appendix.

To ensure that start-up is performed correctly, it should only be carried out by an after-sales service technician authorised by the manufacturer. This may be a condition for extending the guaran- tee (see Warranty).
The following items need to be checked prior to start-up:
The heat pump must be fully connected, as described in
Chapter 6.
All valves that could impair the proper flow of the heating
water in the heating circuit must be open.
The air intake and air outlet paths must be clear.
The ventilator must turn in the direction indicated by the ar-
row.
A standard four-core cable is used for connecting the heat pump to the power supply.
The settings of the heat pump controller must be adapted to
the heating system in accordance with the controller’s oper- ating instructions.
The power supply and the control line are normally installed in the ground (in ductwork with a suitable size and resistance) and routed from the heat pump to the building. This ductwork must extend into the heat pump by approx. 22 mm and be installed with a continuous downward slope in order to comply with Sec- tion 42 of the VDE 0100 regulations. Instead of 90° bends, two 45° bends must be used as pipe bends. The control line and the cable for the power supply are drawn into this ductwork.
Ensure the condensate outflow functions properly.
The heat pump is started up via the heat pump controller. Adjust- ments should be made in compliance with the instructions.
The cable (power supply) must be provided by the customer. The conductor cross section is selected in accordance with the power consumption of the heat pump (see Appendix Device Informa- tion) and the applicable VDE (EN) and VNB regulations.
If an overflow valve is fitted to assure the minimum heating water flow rate, the valve must be set in accordance with the require- ments of the respective heating system. Incorrect adjustment can lead to faulty operation and increased energy consumption. We recommend carrying out the following procedure to correctly adjust the overflow valve:
The power supply line on the heat pump must be fed through the provided cable feedthrough into the switch box. The line must be firmly screwed to its feedthrough (vapour sealed pipe union).
Close all of the heating circuits that may also be closed during operation (depending on the type of heat pump usage) so that the most unfavourable operating state - with respect to the water flow rate - is achieved. This normally means the heating circuits of the rooms on the south and west sides of the building. At least one heating circuit must remain open (e.g. bathroom).
An all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility blocking contactor or power contactor) as well as a 3-pole circuit breaker with common tripping for all external conductors must be installed in the power supply (tripping current in compliance with the Device Information). Ensure that the in- coming supply has a clockwise rotating field when connecting multiphase devices.
The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re- turn flow listed in the following table for the current heat source temperature. The temperature spread should be measured as close as possible to the heat pump. The heating element of mono energy systems should be disconnected.
Phase sequence: L1, L2, L3.
The control voltage is supplied via the heat pump controller.
The heat pump controller has a 230 V AC-50 Hz power supply. Connect the controller in compliance with its own operating in- structions (16 A fuse).

To protect the paintwork, avoid leaning anything against the de- vice or putting objects on the device. External heat pump parts can be wiped with a damp cloth and domestic cleaner.
To prevent faults due to sediment in the heat exchanger of the heat pump, ensure that the heat exchanger in the heating system cannot be contaminated. In the event that operating malfunctions due to contamination still occur, the system should be cleaned as described below. The device may only be cleaned according to the following instructions from the manufacturer.
Any faults occurring during operation are also displayed on the heat pump controller and can be corrected as described in the operating instructions of the heat pump controller.
For external temperatures below 10 °C and heating water tem- peratures below 16 °C, the buffer tank should be heated up with the second heat generator to at least 25 °C.
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust), particularly if steel components are used. These products enter the heating system via the valves, the circulating pumps and/or plastic pipes. It is therefore essential - in particular with respect to the piping of un- derfloor heating systems - that only diffusion-proof materials are used.
Observe the following procedure to implement a smooth start-up:
Residue from lubricants and sealants may also contaminate the heating water.
In the case of severe contamination leading to a reduction in the performance of the liquifier in the heat pump, the system must be cleaned by a heating technician.
According to today’s state of knowledge, we recommend using a 5% phosphoric acid solution for cleaning purposes. However, if cleaning needs to be performed more frequently, a 5% formic acid solution should be used.
In either case, the cleaning fluid should be at room temperature. We recommend flushing the heat exchanger in the direction op- posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys- tem circuit, we recommend connecting the flushing device di- rectly to the flow and return flow of the liquifier of the heat pump.
It is important that the system be thoroughly flushed using appro- priate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of the employers’ liability insurance associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!

8.3 Cleaning the Air System
Evaporator, ventilator and condensate outflow should be cleaned of contamination (leaves, twigs, etc.) before each new heating period.
This heat pump is a quality product and is designed for trouble- free and maintenance-free operation. In the event that a fault should occur, it will be indicated on the heat pump manager dis- play. Simply consult the Faults and Trouble-shooting page in the operating instructions of the heat pump manager. If you cannot correct the fault yourself, please contact your after-sales service technician.
To prevent the evaporator and the condensate tray from being damaged, do not use hard or sharp objects for cleaning.
Inflammable refrigerant could leak out if the refrigerating circuit is damaged. Ignition sources and open flames must be avoided when carrying out any work on the device.
Anyone carrying out work on the refrigerating circuit must be cer- tified to safely handle inflammable refrigerants or be supervised by a person having such certification.
Under extreme weather conditions (e.g. snow drifts), ice may form on the air intake and exhaust air outlet grids. If this happens, the ice must be removed in the vicinity of the air intake and ex- haust air outlet grids to ensure that the minimum air flow rate is maintained.
Before removing the heat pump, disconnect it from the power source and close all valves. Observe all environmentally-relevant requirements regarding the recovery, recycling and disposal of materials and components in accordance with all applicable standards. Particular attention should be paid to the proper dis- posal of refrigerants and refrigeration oils.


1.1 Maßbild / Dimension Drawing / Schéma coté LA 9PS A-II 1.2 Maßbild / Dimension Drawing / Schéma coté LA 12PS A-III 1.3 Maßbild / Dimension Drawing / Schéma coté LA 18PS A-IV
2.1 Kennlinien / Characteristic Curves / Courbes caractéristiques LA 9PS A-V 2.2 Kennlinien / Characteristic Curves / Courbes caractéristiques LA 12PS A-VI 2.3 Kennlinien / Characteristic Curves / Courbes caractéristiques LA 18PS A-VII
3.1 Steuerung / Control / Commande LA 9PS A-VIII 3.2 Last / Load / Charge LA 9PS A-IX 3.3 Anschlussplan / Circuit Diagram / Schéma électrique LA 9PS A-X 3.4 Legende / Legend / Légende LA 9PS A-XI 3.5 Steuerung / Control / Commande LA 12PS A-XII 3.6 Last / Load / Charge LA 12PS A-XIII 3.7 Anschlussplan / Circuit Diagram / Schéma électrique LA 12PS A-XIV 3.8 Legende / Legend / Légende LA 12PS A-XV 3.9 Steuerung / Control / Commande LA 18PS A-XVI 3.10 Last / Load / Charge LA 18PS A-XVII 3.11 Anschlussplan / Circuit Diagram / Schéma électrique LA 18PS A-XVIII 3.12 Legende / Legend / Légende LA 18PS A-XIX
4 Hydraulische Prinzipschemen / Hydraulic Plumbing Diagram / Schéma hydraulique........A-XX
4.1 Monoenergetische Anlage / Mono Energy System / Installation monoénergétique A-XX 4.2 Monoenergetische Anlage und Warmwasserbereitung / Mono Energy System and Domestic Hot Water Preparation / Installation monoénergétique et production d’eau chaude A-XXI 4.3 Bivalente Anlage / Bivalent System / Installation bivalente A-XXII 4.4 Legende / Legend / Légende A-XXIII
Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.
Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.