Inhaltsverzeichnis 32 Abschnitte Table of contents · 1 Please Read Immediately · 1.1 Important Information · 1.2 Legal Regulations and Directives · … AnzeigenAusblenden
Page 1 of the Dimplex LA 17PS user manual — Luft/WasserWärmepumpe für Außenaufstellung
Seite 1 · Zum Vergrößern klicken
Seite 1

LA 17PS LA 22PS LA 26PS

Montageund GebrauchsanweisungDeutsch Installation and Operating InstructionsEnglish Instructions d’installation et d’utilisationFrançais
Dimplex LA 17PS — LA 17PS LA 22PS LA 26PS diagram (page 1)
Abb. 1
Dimplex LA 17PS — LA 17PS LA 22PS LA 26PS diagram (page 1)
Abb. 2
Dimplex LA 17PS — LA 17PS LA 22PS LA 26PS diagram (page 1)
Abb. 3
Dimplex LA 17PS — LA 17PS LA 22PS LA 26PS diagram (page 1)
Abb. 4

Luft/WasserWärmepumpe für Außenaufstellung

Air-to-Water Heat Pump for Outdoor Installation

Pompe à chaleur air-eau pour installation extérieure

Bestell-Nr. / Order no. / No de commande : 452159.66.04 FD 8703

Page 3 of the Dimplex LA 17PS user manual — 1.3 Energy-Efficient Use of the Heat Pump
Seite 3 · Zum Vergrößern klicken
Seite 3

1 Please Read Immediately

1.2 Legal Regulations and Directives

The construction and design of the heat pump complies with all relevant EU directives, DIN/VDE regulations (see CE declaration of conformity).

1.1 Important Information

The relevant VDE, EN and IEC standards must be adhered to when connecting the heat pump to the power supply or carrying out maintenance work. Any further connection requirements stip- ulated by local utility companies must also be observed.

When connecting the heating system, all applicable regulations must also be adhered to.

Persons, especially children, who are not capable of operating the device safely due to their physical, sensory or mental abilities or their inexperience or lack of knowledge, must not operate this device without supervision or instruction by the person in charge.

Children must be supervised to ensure that they do not play with the device.

1.3 Energy-Efficient Use of the Heat Pump

With the purchase of this heat pump you are helping to protect the environment. A prerequisite for energy-efficient operation is the correct design of the heat source system and heating system (radiators and circulation pump).

It is particularly important for the efficiency of a heat pump to keep the temperature difference between heating water and heat source as small as possible. For this reason, it is advisable to de- sign the heat source and heating system very carefully. A tem- perature difference of approx. one Kelvin increases the power consumption by around 2.5%. When designing the heating system, it should be borne in mind that special consum- ers such as e.g. domestic hot water preparation should also be taken into consideration and dimensioned for low temperatures. Underfloor heating systems (panel heating) are optimally suited for heat pump use on account of the low flow temperatures (30 °C to 40 °C).

It is important to ensure that the heat exchangers are not con- taminated during operation because this increases the tempera- ture difference, in turn reducing the COP.

Correct adjustment of the heat pump controller is also important for energy-efficient use of the heat pump. Further information can be found in the heat pump controller’s operating instructions.

Page 4 of the Dimplex LA 17PS user manual —
Seite 4 · Zum Vergrößern klicken
Seite 4

2 Purpose of the Heat Pump

3 Scope of Delivery

3.1 Basic Device

2.1 Application

The heat pump is of compact design and is supplied complete with the components listed below.

The air-to-water heat pump is designed for use in existing or newly built heating systems.

R290 (propane) is used as refrigerant.

It is designed exclusively for heating domestic hot water and heating water!

The heat pump is suitable for mono energy and bivalent opera- tion down to an external temperature of -20 °C.

Dimplex LA 17PS —   diagram (page 4)
Abb. 5

Proper defrosting of the evaporator is guaranteed by maintaining a heating water return flow temperature of more than 13 °C dur- ing continuous operation.

The heat pump is not designed for the increased heat consump- tion required when a building is being dried out. The additional heat consumption should be met using special devices provided by the customer. If a building is to be dried out in autumn or win- ter, we recommend installing an additional heating element (available as an accessory).

Dimplex LA 17PS —   diagram (page 4)
Abb. 6

2.2 Operating Principle

Surrounding air is drawn in by the ventilator and fed via the evap- orator (heat exchanger). The evaporator cools the air, i.e. it ex- tracts heat from it. This extracted heat is then transferred to the working medium (refrigerant) in the evaporator.

The heat is “pumped” to a higher temperature level by increasing its pressure with the aid of the electrically driven compressors. It is then transferred to the heating water using the liquifier (heat exchanger).

1. Evaporator

Electrical energy is used to raise the temperature of the heat in the environment to a higher level. Because the energy extracted from the air is transferred to the heating water, this type of device is called an air-to-water heat pump.

2. Ventilator
3. Switch box
4. Compressor

The air-to-water heat pump consists of the main components evaporator, ventilator and expansion valve, as well as the low- noise compressors, liquifier and electrical control system.

5. Liquifier
6. Expansion valve

At low ambient temperatures, humidity accumulates on the evap- orator in the form of frost reducing the transfer of heat. The evap- orator is defrosted automatically by the heat pump as required. Steam may be emitted from the air outlet depending on the at- mospheric conditions.

Page 5 of the Dimplex LA 17PS user manual — 3.3 Heat Pump Controller
Seite 5 · Zum Vergrößern klicken
Seite 5

4 Transport

3.2 Switch Box

The switch box is located in the heat pump. All electrical compo- nents are accessible after the front cover and the switch box cover have been removed.

The switch box contains the supply connection terminals, the plug connector for the control line, as well as the power contac- tors and the soft starter unit.

3.3 Heat Pump Controller

Use a wooden pallet for transporting the heat pump to the final in- stallation location. The basic device can be transported with a lift truck, hand truck or by means of 3/4" pipes fed through the holes in the base plate or frame.

Use the heat pump controller included in the scope of supply to operate the air-to-water heat pump.

The heat pump controller is a convenient electronic regulation and control device. It controls and monitors the entire heating system on the basis of the external temperature, including do- mestic hot water preparation and safety systems.

Dimplex LA 17PS — 3.3 Heat Pump Controller diagram (page 5)
Abb. 7 · 3.3 Heat Pump Controller

The customer must install the return temperature sensor and the external temperature sensor, which are supplied with the heat pump controller / with these instructions together with the neces- sary fixing accessories.

The enclosed operating instructions describe the function and use of the heat pump controller.

Before using the transport holes in the frame, it is necessary to remove the lower side panel assemblies. This is done by loosen- ing each of the two screws at the base and then withdrawing the panels by unhooking them from above. Rehang the panels by gently pushing them in an upwards direction.

Be careful not to damage any components when inserting the pipes through the frame.

Dimplex LA 17PS — 3.3 Heat Pump Controller diagram (page 5)
Abb. 8 · 3.3 Heat Pump Controller

Opening the cover Closing the cover

Show 5 more labels / short text on this page
· · · ·
Page 6 of the Dimplex LA 17PS user manual — Antifreeze
Seite 6 · Zum Vergrößern klicken
Seite 6

5 Set-up

6 Installation

5.1 General Information

6.1 General Information

The heat pump is suited for outdoor installation. The device should always be installed on a permanently smooth, even and horizontal surface and must be aligned vertically. The entire frame should lie directly on the ground to ensure a good sound- proof seal and to prevent the water-bearing components from be- coming too cold. If this is not the case, additional insulation measures may be necessary. It must be possible to carry out maintenance work without hindrance. This can be ensured by maintaining a clearance of 1.2 m to any fixed walls.

The following connections need to be established on the heat pump:

„ Flow and return flow of the heating system

„ Control line to the heat pump controller

6.2 Heating System Connection

The heating system connections on the heat pump have a 1 1/4" external thread.

P

Route the connection hoses out of the device in a downwards di- rection. Use a spanner to firmly grip the transitions when con- necting the heat pump. After the heat pump has been installed, the ductwork must be sealed so that the connection is gastight.

P P

Before connecting the heating water system to the heat pump, the heating system must be flushed to remove any impurities, residue from sealants, etc., and to prevent any accumulation of deposits in the liquifier. A contaminated liquifier may cause the heat pump to completely break down. For systems in which the heating water flow can be shut off via the radiator or thermostat valves, an overflow valve must be installed in a heating bypass downstream from the heat pump by the customer. This ensures a minimum heating water flow rate through the heat pump and helps to avoid faults.

P

Once the heating system has been installed, it must be filled, de- aerated and pressure-tested (in the heat pump the air-relief cock is located at or in the water pipes at the condenser).

5.2 Condensed Water Pipe

Dimplex LA 17PS — 5.2 Condensed Water Pipe diagram (page 6)
Abb. 9 · 5.2 Condensed Water Pipe

Condensed water that forms during operation must be drained off frost-free. The heat pump must be mounted on a level plane to guarantee proper drainage. The condensed water pipe must have a minimum diameter of 50 mm and should be fed frost-free into a sewer. Condensate should not be discharged directly into clearing tanks and cesspits because the aggressive vapours could destroy the evaporator.

$LUUHOLHIFRFN

&RQGHQVHU

Minimum heating water flow rate

The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing either a manifold without differential pressure or an overflow valve. The procedure for adjusting an overflow valve is described in the Chapter Start-up.

Antifreeze

Manual drainage should be provided for heat pumps which are exposed to frost. The antifreeze function of the heat pump con- troller is active whenever the controller and the heat circulating pump are ready for operation. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained, and if required, blown out, at three locations (see illus- tration). The heating circuit should be operated with a suitable antifreeze if heat pump systems are implemented in buildings where a power failure can not be detected (holiday home).

„ Condensate outflow · „ Power supply

Page 7 of the Dimplex LA 17PS user manual — 7.3 Procedure
Seite 7 · Zum Vergrößern klicken
Seite 7

7 Start-up

Dimplex LA 17PS — 7 Start-up diagram (page 7)
Abb. 10 · 7 Start-up

7.1 General Information

To ensure that start-up is performed correctly, it should only be carried out by an after-sales service technician authorised by the manufacturer. This may be a condition for extending the guaran- tee (see Warranty Service).

7.2 Preparation

The following items need to be checked prior to start-up:

„ The heat pump must be fully connected, as described in

Chapter 6.

„ All valves that could impair the proper flow of the heating

6.3 Electrical Connection

water in the heating circuit must be open.

„ The air intake and air outlet paths must be clear.

A standard four-core cable is used for connecting the heat pump to the power supply.

„ The ventilator must turn in the direction indicated by the ar-

row.

The power supply and the control line are normally installed in the ground (in ductwork with a suitable size and resistance) and routed from the heat pump to the building. This ductwork must extend into the heat pump by approx. 22 mm and be installed with a continuous downward slope in order to comply with Sec- tion 42 of the VDE 0100 regulations. Instead of 90° bends, two 45° bends must be used as pipe bends. The control line and the cable for the power supply are drawn into this ductwork.

„ The settings of the heat pump controller must be adapted to

the heating system in accordance with the controller’s oper- ating instructions.

„ Ensure the condensate outflow functions.

7.3 Procedure

The heat pump is started up via the heat pump controller. Adjust- ments should be made in compliance with the instructions.

The cable (power supply) must be provided by the customer. The conductor cross section is selected in accordance with the power consumption of the heat pump (see Appendix Device Informa- tion) and the applicable VDE (EN) and VNB regulations.

If an overflow valve is fitted to maintain the minimum heating water flow rate, the valve must be adapted to the requirements of the heating system. Incorrect adjustment can lead to faulty oper- ation and increased energy consumption. We recommend carry- ing out the following procedure to correctly adjust the overflow valve:

The power supply line on the heat pump must be fed through the provided cable feedthrough into the switch box. The line must be firmly screwed to its feedthrough (vapour sealed pipe union).

An all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility blocking contactor or power contactor) as well as a 3-pole circuit breaker with common tripping for all external con- ductors must be installed in the power supply (tripping current in compliance with the Device Information). Ensure that the incom- ing supply has a clockwise rotating field when connecting mul- tiphase devices.

Close all of the heating circuits that may also be closed during operation (depending on the type of heat pump usage) so that the most unfavourable operating state - with respect to the water flow rate - is achieved. This normally means the heating circuits of the rooms on the south and west sides of the building. At least one heating circuit must remain open (e.g. bathroom).

The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re- turn flow listed in the following table for the current heat source temperature. The temperature spread should be measured as close as possible to the heat pump. The heating element of mono energy systems should be disconnected.

Phase sequence: L1, L2, L3.

The control voltage is supplied via the heat pump controller.

Dimplex LA 17PS — 7.3 Procedure diagram (page 7)
Abb. 11 · 7.3 Procedure
Heat source temperatureMax. temperature spread between heating flow and return flow FromTo -20 °C-15 °C4 K -14 °C-10 °C5 K -9 °C-5 °C6 K -4 °C0 °C7 K 1 °C5 °C8 K 6 °C10 °C9 K 11 °C15 °C10 K 16 °C20 °C11 K 21 °C25 °C12 K 26 °C30 °C13 K 31 °C35 °C14 K

The heat pump controller has a 230 V AC-50 Hz power supply. Connect the controller in compliance with its own operating in- structions (16 A fuse).

The control line (not included in scope of supply) is connected to the heat pump controller using the two rectangular plug connec- tors. Use the plug connector located on the base of the heat pump adjacent to the cable gland in the base plate. More de- tailed information can be found in the operating instructions of the heat pump controller.

For detailed information, see Circuit Diagrams in the Appendix.

Page 8 of the Dimplex LA 17PS user manual — 8.2 Cleaning the Heating System
Seite 8 · Zum Vergrößern klicken
Seite 8

8 Maintenance / Cleaning

Any faults occurring during operation are also displayed on the heat pump controller and can be corrected as described in the operating instructions of the heat pump controller.

8.1 Maintenance

For external temperatures below 10 °C and heating water tem- peratures below 16 °C, the buffer tank should be heated up with the second heat generator to at least 25 °C.

To protect the paintwork, avoid leaning anything against the de- vice or putting objects on the device. External heat pump parts can be wiped with a damp cloth and domestic cleaner.

Observe the following procedure to implement a smooth start-up:

1. Close all of the heating circuits.
2. Fully open the overflow valve.
3. Use the controller to select the automatic operating mode.
4. Wait until the buffer tank has reached a temperature of at least 25 °C.

To prevent faults due to sediment in the heat exchanger of the heat pump, ensure that the heat exchanger in the heating system can not be contaminated. In the event that operating malfunc- tions due to contamination still occur, the system should be cleaned as described below. The device may only be cleaned ac- cording to the following instructions from the manufacturer.

5. Now slowly reopen the heating circuit valves in succession so that the heating water throughput is constantly raised by slightly opening the respective heating circuit. The heating water temperature in the buffer tank must not be allowed to drop below 20 °C during this process. This ensures that the heat pump can be defrosted at any time.
6. Set the minimum volume flow quantity on the overflow valve and heat circulating pump when all heating circuits are fully open and a heating water temperature in the buffer tank of approx. 20 °C is maintained.

8.2 Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust), particularly if steel components are used. These products enter the heating system via the valves, the circulating pumps and/or plastic pipes. It is therefore essential - in particular with respect to the piping of un- derfloor heating systems - that only diffusion-proof materials are used.

7. New buildings have an increased heat consumption on account of the energy required to dry them out. This increased heat consumption means that marginally dimensioned heating systems can not always achieve the desired room temperature. In such cases, we recommend keeping a second heat generator on standby during the first heating period. The limit temperature on the heat pump controller should also be turned up to 15 °C.

Residue from lubricants and sealants may also contaminate the heating water.

In the case of severe contamination leading to a reduction in the performance of the liquifier in the heat pump, the system must be cleaned by a heating technician.

According to today’s state of knowledge, we recommend using a 5 % phosphoric acid solution for cleaning purposes. However, if cleaning needs to be performed more frequently, a 5 % formic acid solution should be used.

In either case, the cleaning fluid should be at room temperature. We recommend flushing the heat exchanger in the direction op- posite to the normal flow direction.

To prevent acidic cleaning agents from entering the heating sys- tem circuit, we recommend connecting the flushing device di- rectly to the flow and return flow of the liquifier of the heat pump.

It is important that the system be thoroughly flushed using appro- priate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system.

Acids must be used with great care and all relevant regulations of the employers’ liability insurance associations must be adhered to.

If in doubt, contact the manufacturer of the chemicals!

Page 9 of the Dimplex LA 17PS user manual — 10 Decommissioning/ Disposal
Seite 9 · Zum Vergrößern klicken
Seite 9

9 Faults / TroubleShooting

8.3 Cleaning the Air System

Evaporator, ventilator and condensate outflow should be cleaned of contamination (leaves, twigs, etc.) before each new heating period.

This heat pump is a quality product and is designed for trouble- free and maintenance-free operation. In the event that a fault should occur, it will be indicated on the heat pump manager dis- play. Simply consult the Faults and Trouble-shooting page in the operating instructions of the heat pump manager. If you cannot correct the fault yourself, please contact your after-sales service technician.

Do this by opening the front of the heat pump. The bottom should be opened first followed by the top.

Remove and rehang the side panel assemblies as described in Chapter 4.

To prevent the evaporator and the condensate tray from being damaged, do not use hard or sharp objects for cleaning.

Anyone carrying out work on the refrigerating circuit must be cer- tified to safely handle inflammable refrigerants or be supervised by a person having such certification.

Inflammable refrigerant could leak out if the refrigerating circuit is damaged. Ignition sources and open flames must be avoided when carrying out any work on the device.

10 Decommissioning/ Disposal

Under extreme weather conditions (e.g. snow drifts), ice may form on the air intake and exhaust air outlet grids. If this happens, the ice must be removed in the vicinity of the air intake and ex- haust air outlet grids to ensure that the minimum air flow rate is maintained.

Before removing the heat pump, disconnect it from the power source and close all valves. Observe all environmentally-relevant requirements regarding the recovery, recycling and disposal of materials and components in accordance with all applicable standards. Particular attention should be paid to the proper dis- posal of refrigerants and refrigeration oils.

Page 10 of the Dimplex LA 17PS user manual — 11 Device Information
Seite 10 · Zum Vergrößern klicken
Seite 10

11 Device Information

1 Type and order codeLA 17PSLA 22PSLA 26PS 2 Design 2.1 Degree of protection according to EN 60 529 for compact devices and heating componentsIP 24IP 24IP 24 2.2 Installation LocationOutdoorsOutdoorsOutdoors 3 Performance data 3.1 Operating temperature limits: Heating water flow/return flow 1 °C / °CUp to 65 / above 18Up to 65 / above 18Up to 65 / above 18 Air °C-20 to +35-20 to +35-20 to +35 3.2 Temperature spread of heating water at A7 / W359.35.09.55.09.45.0 3.3 Heat output / COP at A-7 / W35 2 kW / --- 36.7 / 2.56.4 / 2.47.7 / 2.47.5 / 2.38.7 / 2.48.4 / 2.2 411.4 / 2.610.8 / 2.513.6 / 2.613.1 / 2.514.4 / 2.613.9 / 2.5 at A-7 / W45 2 kW / --- 36.0 / 2.27.0 / 2.27.8 / 2.3 410.3 / 2.212.5 / 2.313.3 / 2.3 at A2 / W35 2 kW / --- 38.7 / 3.28.3 / 3.010.6 / 3.110.5 / 3.011.7 / 3.111.5 / 3.0 414.5 / 3.114.3 / 3.016.7 / 3.116.5 / 3.018.8 / 3.118.6 / 3.0 at A7 / W35 2 kW / --- 310.1 / 3.69.6 / 3.412.6 / 3.812.0 / 3.613.7 / 3.613.3 / 3.5 417.3 / 3.516.6 / 3.422.0 / 3.821.1 / 3.524.0 / 3.722.9 / 3.5 at A7 / W45 2 kW / --- 39.3 / 2.911.3 / 3.012.5 / 2.9 416.1 / 2.920.5 / 3.021.6 / 3.0 at A10 / W35 2 kW / --- 311.8 / 4.111.4 / 4.113.7 / 4.213.5 / 4.115.0 / 4.114.7 / 4.0 419.6 / 3.819.2 / 3.823.4 / 4.023.2 / 3.926.2 / 4.025.9 / 4.0 3.4 Sound power level dB(A)646868 3.5 Sound pressure level at a distance of 10 m (air outlet side) dB(A)374141 3.6 Heating water flow with an internal pressure differential of m³/h / Pa1.6 / 29003.0 / 100002.0 / 45003.5 / 138002.2 / 31003.8 / 8900 3.7 Air flow rate m³/h550080008000 3.8 Refrigerant; total filling weight type / kgR290 / 1.8R290 / 2.2R290 / 2.5 4 Dimensions, connections and weight 4.1 Device dimensions H x W x L cm157 x 155 x 85171 x 168 x 100171 x 168 x 100 4.2 Device connections to heating system InchG 1 1/4'' externalG 1 1/4'' externalG 1 1/4'' external 4.3 Weight of the transportable unit(s) incl. packing kg330360371 5 Electrical connection 5.1 Nominal voltage; fuse protection V / A400 / 20 T400 / 20 T400 / 25 T 5.2 Nominal power consumption 2 A2 W35 kW4.744.765.45.56.16.2 5.3 Starting current with soft starter A232530 5.4 Nominal current A2 W35 / cos ϕ A / ---8.6 / 0.88.6 / 0.89.8 / 0.89.9 / 0.811.1 / 0.811.2 / 0.8 6 Complies with the European safety regulations555 7 Additional model features 7.1 DefrostingAutomaticAutomaticAutomatic Type of defrostingHot gasHot gasHot gas Defrosting tray includedYes (heated)Yes (heated)Yes (heated) 7.2 Heating water in device protected against icing 6YesYesYes 7.3 Performance levels222 7.4 Controller internal/externalExternalExternalExternal
1. See operating limits diagram
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: 2 °C external air temperature and 55 °C heating water flow temperature.
3. Operation with 1 compressors
4. Operation with 2 compressors
5. See CE declaration of conformity
6. The heat circulating pump and the heat pump controller must always be ready for operation.
Page 11 of the Dimplex LA 17PS user manual — Anhang · Appendix · Annexes
Seite 11 · Zum Vergrößern klicken
Seite 11

Anhang / Appendix / Annexes

1 Maßbild / Dimension Drawing / Schéma coté A-II

1.1 Maßbild / Dimension Drawing / Schéma coté LA 17PS A-II 1.2 Maßbild / Dimension Drawing / Schéma coté LA 22PS - LA 26PS A-III

2 Diagramme / Diagrams / Diagrammes A-IV

2.1 Kennlinien / Characteristic Curves / Courbes caractéristiques LA 17PS A-IV 2.2 Kennlinien / Characteristic Curves / Courbes caractéristiques LA 22PS A-V 2.3 Kennlinien / Characteristic Curves / Courbes caractéristiques LA 26PS A-VI

3 Stromlaufpläne / Circuit Diagrams / Schémas électriques A-VII

3.1 Steuerung / Control / Commande A-VII 3.2 Last / Load / Charge A-VIII 3.3 Anschlussplan / Circuit Diagram / Schéma électrique A-IX 3.4 Legende / Legend / Légende A-X

4 Hydraulische Prinzipschemen / Hydraulic Plumbing Diagram / Schémas hydrauliques A-XI

4.1 Monoenergetische Anlage / Mono Energy System / Installation monoénergétique A-XI 4.2 Monoenergetische Anlage und Warmwasserbereitung / Mono Energy System and Domestic Hot Water Preparation / Installation monoénergétique et production d’eau chaude A-XII 4.3 Bivalente Anlage / Bivalent System / Installation bivalente A-XIII 4.4 Legende / Legend / Légende A-XIV

Anhang · Appendix · Annexes

5 Konformitätserklärung / Declaration of Conformity / Déclaration de conformité ................A-XV

www.dimplex.de A-I

Frage zu Dimplex LA 17PS stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Dimplex LA 17PS

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Dimplex LA 17PS PDF-Anleitung

26 Seiten·1.5 MB·Wärmepumpe·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…