Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without not ice and without inc urring obligations. Catalog No . 04-533000 54-01 Printed in U .S.A. Fo rm 30MP-1SI Pg 1 910 1-10 Replaces: Ne w Installation Instr uctions CONTENTS Page GENERAL .
2 INST ALLA TION Location — Do not store units in an area exposed to weath- er because of sensitive contro l mechanisms and electronic devices. Locate unit indoors. See Fig. 4 and 5 for unit dimen- sional details. When considering location, consult National Electrical Code (NEC) and local code requirements.
3 52.30 1328 [] STD UNIT 55.00 1397 [] OPTIONAL SOUND ENCLOSURE 57.00 [1448] 29.13 740 [] STD UNIT 32.00 813 [] 62.50 1588 [] OPTIONAL SOUND ENCLOSURE 32.12 [816] MOBILITY KIT (WHEEL) OPTIONAL 3.85 98 [] E D F OPTIONAL SOUND ENCLOSURE 48.42 [1230] OPTIONAL SOUND ENCLOSURE 65.
4 Fig. 5 — Dimensions — 30MPW015-045 Units NO TES: 1. Operating weight includes w eight of water and refrigerant. 2. Denotes center of gravity . 3. Dimensions are shown in inc hes. Dimensions in [ ] are in millimeters . 4. Allow 36-in. (914 mm) clear ance on control panel end, opposite control panel end and a b ov e the unit.
5 Table 1A — 30MPA Air-Cooled and 30MPW Liquid-Cooled Unit s — English * With optional hot gas b ypass. NO TES: 1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers. 2. 30MPW units are shipped with full operating charge.
6 T abl e 1B — 30MPA Air-Cooled a nd 30MPW Liquid-Cooled Units — SI * With optional hot gas b ypass. NO TES: 1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers. 2. 30MPW units are shipped with full operating charge.
7 Step 3 — Place the Unit NOTE: These units ar e not suitable for unpr otected outdoor use . Carrier recommends that these units be located in the base- ment or on the ground floor . However , if it is necessary to lo- cate the unit on an upper floor , be sure the structure has been designed to support the unit weight.
8 NO TES: 1. Chiller must b e installed le v el to maintain proper compressor oil return. 2. Wiring and pip ing shown are general points-of- connection guides only and are not intended for a spe- cific installation. Wiring and piping shown are f or a q uick ov erview of system and are not in accordance with recognized standards.
9 NO TES: 1. Chiller must b e installed lev el to maintain proper compr essor oil return. 2. Wir ing and piping show n are general poi nts-of-connection guides only and ar e not intended for a specific installa tion. Wiring and pip- ing shown are f or a q uic k ov erview of system and are no t in accor- dance with recognize d standards .
10 3. Install the inside coupling half over the gasket and then install the outer half. Connect with nuts and bolts. T ighten the nuts equally on both sides. Ensure there is no gap be- tween the two halves of the coupling. 4. Alternately tighten the nuts with a wrench to draw the coupling halves together uniformly .
11 120 1 100 80 e Drop (kPa) 40 60 Water Pressur e 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Liters/second 12 3 5 4 40 30 35 1 5 4 3 2 25 30 Drop () 15 20 Water Pressure 5 10 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 GPM Fig.
12 120 3 100 1 80 e Drop (kPa) 40 60 Water Pressur e 20 0 0123456789 1 0 1 1 1 2 1 3 Liters/second 1 2 3 4 5 0 5 10 15 20 25 30 35 40 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 Water Pressure Drop () GPM 15 4 3 2 Fig.
13 Step 6 — Fill the Chilled W ater Loop W A TER SYSTEM CLEANING — P r o pe r wa t e r sy s t em cleaning is of vital importance. Excessive particulates in the water system can cause excessive pump seal wear , reduce or stop flow , and cause damage of other com ponents.
14 Ensure the following when filling the system: 1. Remove temporary bypass piping and cleaning/flushing equipment. 2. Check to make sure all drain plugs are installed. 3. Open the blow-down valve to flush the strainer . Normally , a closed system needs to be filled only once.
15 EXAMPLE: Supply voltage is 240-3-60. AB = 243 v BC = 236 v AC = 238 v A verage V oltage = 243 + 236 + 238 3 = 239 v Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v Maximum deviation is 4 v .
Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53300054-0 1 Printed in U .S.A. Form 30MP-1SI Pg 16 910 1-10 Replaces: Ne w Copy right 2010 Carrier Cor poration Fig.
Ein wichtiger Punkt beim Kauf des Geräts Carrier AQUASNAP 30MPA (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier AQUASNAP 30MPA noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier AQUASNAP 30MPA - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier AQUASNAP 30MPA reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier AQUASNAP 30MPA erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier AQUASNAP 30MPA besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier AQUASNAP 30MPA verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier AQUASNAP 30MPA. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier AQUASNAP 30MPA gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.