Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................1 GENERAL ..................................1 INST ALLA TION ............................ 1-12 Step 1 − Complete Pre-Installation Checks ..1 Step 2 − Rig and Place Unit .
Fig. 1 — 09BY Unit (008-014 Shown) 2.
LEGEND Refrigerant Connection Field-Supplied Refrigerant Piping *Field-Supplied Floor Stand (Height to Match W all Opening). Fig. 2 — Mounting Applications 09BY DISCHARGE DUCT INLET DUCT TO OUTSIDE .
09BY DIMENSIONS (English) DIMENSION 006 (Ft-in.) 008 (Ft-in.) 012 (Ft-in.) 014 (Ft-in.) 016,024 (Ft-in.) A 2-1 1 1 ⁄ 2 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 5- 0 B 1- 7 11 ⁄ 16 1-1 1 5 ⁄ .
NOTES: 1. Operational clearances are 0 in. on all sides of the unit. 2. Service clearances are 0 in. (minimum) on the top, rear , and front of the unit. A minimum of 3 ft service clearance is required on the unit right side, an da3f t clearance is recommended on the left side (2 ft is the minimum).
T able 1 — Condenser Unit Application UNIT 50BZ 09BY 006 008 012 014 016 024 006 S 008 S 012 OS 014 OS 016 OS 024 OS LEGEND S— Standard O— Optional NOTE: Contact your local representative for use with reciprocating air-cooled chillers and other compressor-bearing unit combinations.
Step 2 — Rig and Place Unit RIGGING — The 09BY units are mounted on skids. Leave the unit on the skid until it is in the final position. While on the skid, the unit can be rolled, dragged or forklifted; do not apply for ce to the unit.
Step 3 — Install Accessory Low-Ambient Kit or Inlet Filter Kit (If Required) — If the unit will be op- erated with inlet air to the condenser below 50 F , a low- ambient damper may be required. The low-ambient kit con- trols head pressure by discharge dampers on the condenser fan.
LIQUID LIFT — Amount of liquid lift available before re- frigerant flashing occurs depends on amount of liquid sub- cooling in the system. All 09BY condensers have positive subcooling when ap- plied with optimum charge.
CHECK V AL VE — When the 09BY condenser is installed with the condenser located above the compressor evapora- tor , it is recommended that a field-supplied check valve be installed on the hot gas discharge line. This prevents refrig- erant which condenses in the discharge line during the of f cycle from draining back into the compressor .
3. A high-density fiberglass (2 lb minimum density) or semi- rigid foamed insulation such as Styrofoam™ will be re- quired inside the ducts to prevent air erosion. The insu- lation must be firmly secured in the discharge duct near the blower discharge to withstand the high air velocity .
Determine maximum deviation from average voltage: (AB) 243 – 23 9=4v (BC) 239 – 23 6=3v (AC) 239 – 23 8=1v Maximum deviation is then 4 v . T o determine the percentage of voltage imbalance: 4 % V oltage Imbalance = 100 x 239 = 1.7% This amount of phase imbalance is satisfactory since it is below the allowable maximum of 2%.
ST ART -UP To prevent personal injury, be sure wire fan guards are secured in place over each fan discharge (or that fans are ducted) before starting the unit.
T able 5 — Condenser Fan Performance UNIT 09BY AIRFLOW (Cfm) EXTERNAL ST A TIC PRESSURE (in. wg) 0.0 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 006 2000 676 0.26 905 0.51 1085 0.80 1230 1.08 1348 1.34 1449 1.60 2500 845 0.51 1039 0.
TO CHANGE F AN WHEEL — If a fan wheel should fail, it may be replaced as follows: 1. Remove belts from fan pulley . 2. Loosen locking collars on the fan bearings and set screws on the fan wheels. 3. Remove the shaft through the access panel on either side of the unit.
TROUBLESHOOTING See T able 6 for problems and possible solutions. T a b l e6—T roubleshooting PROBLEM POTENTIAL CAUSE SOLUTION Unit is tripping on high-pressure switch or high discharge pressure is noted. 1. Fan belts are slipping or broken. 2. Fan is not delivering adequate air for condenser .
.
Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 4 Ta b 4 a 4 a PC 1 1 1 Catalog No. 530-969 Printed in U.S.A.
ST ART -UP CHECKLIST A. Preliminary Information COMPRESSOR BEARING UNIT : MODEL NO. SERIAL NO. 09BY UNIT : MODEL NO. SERIAL NO. FIELD-INST ALLED ACCESSORIES B. Pre-Start-Up CONDENSING UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
CHECK VOL T AGE IMBALANCE IS CONDENSER MOTOR WIRED FOR CORRECT VOL T AGE? (Y/N) LINE-TO-LINE VOL TS: AB VA C VB C V (AB + AC + BC)/3 = A VERAGE VOL T AGE = V MAXIMUM DEVIA TION FROM A VERAGE VOL T AGE.
Ein wichtiger Punkt beim Kauf des Geräts Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier AIR-COOLED CONDENSER UNITS 09BY006-024. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.