Benutzeranleitung / Produktwartung 38AKS013-024 des Produzenten Carrier
Zur Seite of 24
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ............................. 1-12 Step 1 — Complete Pre-Installation Checks ....................................1 Step 2 — Rig and Mount the Unit .
NOTE: Service areas — Allow 3 ft (914 mm) on both sides and 2 ft (610 mm) on both ends of unit for servicing. Fig. 1 — Dimensions 2.
13 2 4567 8 12 9 10 11 LEGEND 1— No. 1 Fan 5— No. 2 Fan 9— Compressor 2— High-Pressure Switch 6— T erminal Block 1 (Unit Power) 1 0— Low-Pressure Switch 3— Circuit Breaker — Control Circuit 7— T erminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 3 ⁄ 8 -in.
T able 1A — Physical Data (English, 60 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (lb) With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040 REFRIGERANT* R-22 Shipping Charge (lb) 2.
T able 1B — Physical Data (SI, 60 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (kg) With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472 REFRIGERANT* R-22 Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, T ypical (kg)† 10.
T able 1C — Physical Data (English, 50 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (lb) With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040 REFRIGERANT* R-22 Shipping Charge (lb) 2.
T able 1D — Physical Data (SI, 50 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (kg) With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472 REFRIGERANT* R-22 Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, T ypical (kg)† 10.
Step 2 — Rig and Mount the Unit Be sure unit panels are securely in place prior to rigging. RIGGING — These units are designed for overhead rigging only . For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks.
T able 4A — Refrigerant Piping Sizes — 60 Hz Units UNIT 38AKS LENGTH OF INTERCONNECTING PIPING, FT (M) 0-15 (0-4.5) 15-25 (4.5-7.5) 25-50 (7.5-15) 50-75 (15-23) 75-100 (23-30) Line Size (in.
INST ALL FIL TER DRIER(S) AND MOISTURE INDICA- TOR(S) — Every unit should have a filter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses.
T able 6A — Electrical Data (3 Ph/60 Hz) UNIT 38AKS UNIT COMPR F AN MOT ORS (Single Phase) Model V olts MCA ICF MOCP (Fuse Only) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 501 208-230 187 253 62.5 178 100 43.6 170 2 4.
T able 6B — Electrical Data (3 Ph/50 Hz) UNIT 38AKS UNIT COMPR F AN MOT ORS 230 v (Single Phase) Model V olts MCA ICF MOCP (Fuse Only) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 803 230 198 264 47.5 134 75 32.9 128 2 2.
ST ART -UP Compressor crankcase heater must be on for 24 hours before start-up. After the heater has been on for 24 hours, the unit can be started. If no time has elapsed since the pre- liminary charge step has been completed, it is unnecessary to wait the 24-hour period.
Fig. 10 — 38AKS013 and 38AKS024 Charging Chart 14.
Fig. 1 1 — 38AKS014 Charging Chart 15.
Fig. 12 — 38AKS016 Charging Chart 16.
OPERA TING SEQUENCE Cooling — When the first stage (TC1) of the cooling ther- mostat closes, the timer starts. After approximately 3 seconds, the timer expires, energizing the compressor and fan motor no. 1. When the liquid pressure builds to approxi- mately 257 psig (1772 kPa), fan motor no.
Winter Start Control (If Required) — Install Ac- cessory Package 38AE900021. Crankcase Heater — The heater prevents refrigerant migration and compressor oil dilution during shutdown when- ever compressor is not operating. It is wired to cycle with the compressor; the heater is of f when compressor is run- ning, and on when compressor is of f.
Fig. 15 — Outdoor Fan Fig. 16 — Pivot and Support T op Cover Fig. 17 — Coil Cleaning (T ypical) 19.
TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power . 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power . 3. Check control circuit breaker; reset if tripped or replace if defective.
TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty . 2. Clean coil fins. 3. Air filters dirty . 3. Clean or replace filters. 4. Dampers closed.
Copyright 1998 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Ta b 3 a 2 a PC 1 1 1 Catalog No. 563-701 Printed in U.S.A.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK INDOOR UNIT F AN SPEED AND RECORD. CHECK OUTDOOR UNIT F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE.
Ein wichtiger Punkt beim Kauf des Geräts Carrier 38AKS013-024 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier 38AKS013-024 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier 38AKS013-024 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier 38AKS013-024 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier 38AKS013-024 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier 38AKS013-024 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier 38AKS013-024 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier 38AKS013-024. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier 38AKS013-024 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.