Zur Seite of 16
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificat ions or des igns without notice an d withou t inc urring obligations.
2 Table 1A — P hysical Da ta — 50/60 Hz (English) LEGE ND NEMA — National Electrical M anuf acturing Assoc iation *Unit is factory supplied w ith holding charge only . †Storage capacity of condenser coil with coil 8 0% full of liquid R-22 at 124 F .
3 Table 1B — P hysical D ata — 50/6 0 Hz (SI) LEGE ND NEMA — National Electrical M anuf acturing Assoc iation *Unit is factory supplied w ith holding charge only . †Storage capacity of condens er coil with coil 8 0% full of liquid R-2 2 at 51 C.
4 CONSIDER SYSTEM REQUIR EMENTS • Consult local bu ilding codes and NEC for s pecial instal- lation requirem ents. • Allow sufficient space for airflow clearan ce, wiring, refriger ant pipi ng, and u nit ser vicing . See Fig. 2. • Locate unit so that co ndenser airflow is unrestricted o n all sides and abov e.
5 UNIT 38 DIM. A DIM. B DIM. C DIM. D DIM . E DIM. F AK007 1 ′ -6 1 / 2 ″ [470.0] 1 ′ -2 3 / 4 ″ [375.0] — — 1 ′ -2 1 / 4 ″ [362 ] 1 ′ -4 5 / 16 ″ [415 ] 2 ′ -9 5 / 16 ″ [846.5] AK008 1 ′ -8 ″ [508.0] 1 ′ -6 1 / 2 ″ [470.
6 FIL TER DRIER AND MOIS TURE INDICA TOR — The fil- ter drier is factory installed. M oisture indicator is field-supplied and should be installed just after liquid line shutof f valve. Do not use a r eceiver; there is none provided with unit and one should not be used.
7 Table 5 — E lectrical Data LEGEND NO TES: 1. In compliance with NEC requirem ents f or multimotor and combi- nation load equipment (ref er to NEC Ar ticles 430 and 440) , the ov erc urrent protective de vice f or the unit shall be fuse or HACR breaker .
8 FI E L D CO N T R O L WI R I NG — Install a Carri er-approved accessor y thermostat a ssembly ac cording to install ation instructi ons included with t he access ory . L ocate the rmostat assembly on a solid wall i n the conditioned spa ce to sense ave r- age temperatur e in accorda nce with therm ostat ins tallation instructions.
9 ST ART -UP Preliminary Chec ks 1. Field electrical power source must agree with unit name- plate rating. 2. Check that all internal wiring conne ctions are tight and that all barriers, covers, and pane ls are in place. Ensure no electrical wir es are in contact wit h refrigerant tubing.
10 Compressor Overload — This overload interrupts power to t he compress or when either the current or internal motor winding temperature be comes excessive, and automati- cally res ets when t he inte rnal tem perature drops t o a safe l evel. This overload may require up to 60 minutes (or longer) to reset.
11 Oil Char g e (T ables 1A and 1 B) 38 A KS U NI T S — Allow unit to run for about 20 minutes. Stop unit and che ck compressor oil level . Add oil only if neces- sary to bring oil into view in sight glass. Use on ly Ca rr ier- appr oved compr ess or oil.
12 Capacity Contr ol — Unit 38AKS012 Onl y — A suction pressure-actuated unl oader controls 2 cylinders and provides capacity control. Unloaders are fac tory set (see T able 1A or 1B), but may be field adjusted as follows: CONTROL SET POINT (cylinder l oad point) is adjustabl e from 0 to 85 psig (586 kPa).
13 TROUBLESHOO TING GUIDE NO TE: See Fig. 15 f or component arrangements. SYMPTOM CA U SE REME D Y Compressor does not run — Contactor open P ower off . Restore power . Fuses blo wn. Replace with correct fuses after finding cause and correcting. T ransformer open/shor t ed.
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations.
ST ART -UP CHECKLIST I. Preliminary Inf ormation OUTDOOR: MO DEL NO . _________ ______________ ________ SERIAL NO . _____________ ______________ _________ INDOOR: AIR HANDLER MANUF ACTURER ________ _____________________ ______________ ______________ _________ MODEL NO .
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations.
Ein wichtiger Punkt beim Kauf des Geräts Carrier 38AK007 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier 38AK007 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier 38AK007 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier 38AK007 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier 38AK007 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier 38AK007 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier 38AK007 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier 38AK007. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier 38AK007 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.