Installation, Operating, and Maintenance Instructions For Use With Positive Pressure Chillers SAFETY CONSIDERA TIONS Positive pressure storage systems are designed to pro- vide safe and reliable service when operated within de- sign specifications.
CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INTRODUCTION ..............................2 INST ALLA TION ............................. 2-10 Complete Pre-Installation Checks .............2 • IDENTIFY UNIT • INSPECT SHIPMENT Mount the Pumpout Unit .
T able 1 — Positive Pressure System Assembly Numbers POSITIVE PRESSURE SYSTEM ASSEMBL Y NUMBER PUMPOUT UNIT ASSEMBL Y NO. REFRIGERANT COMPRESSOR MOTOR (V -Ph-Hz) MAXIMUM RLA LRA STORAGE T ANK 19XB04280205 19EA42-748 R-22 208-3-60 13.2 63.5 28 cu ft 19XB04280206 19EA44-748 R-22 230-3-60 1 1.
CONDENSER W A TER CONNECTIONS (FIELD PIPING) REFRIGERANT INLET V AL VE VENT V AL VE CONTROL BOX (WIRING BY CONTRACTOR) COMPRESSOR VA LV E S VA LV E S 19EA PUMPOUT UNIT 19EA CONTROL BOX (INTERIOR) 19EA PUMPOUT UNITS Fig.
* 3 ⁄ 8 -16 bolts × 1-in. lg; 4 required. Fig. 2 — 19EA Pumpout Unit: T ypical Chiller Mount Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE Q.
T able 2 — Physical Data 19EA Pumpout Unit ENGLISH (SI) Pumpout Unit Weight* lb (kg) 210 (95) Pumpout Condenser W ater Flow Rate gpm (L/s) 5 to 7 (.32 to .
T able 3 — 19XB Storage T ank Rated Dry Weight and Refrigerant Capacity English SIZE CODE T ANK OD (in.) DR Y WEIGHT* (lb) MAXIMUM REFRIGERANT CAP ACITY (lb) ASHRAE/ANSI 15 UL 1963 R-22 R-134a R-22 R-134a 0428 24.00 2380 1842 1860 1704 1716 0452 27.
DIMENSIONS ENGLISH (ft-in.) T ANK SIZE A B CDE F G H J K LM NP R S T 0428 10- 5 9-10 4-9 2-4 3 ⁄ 4 1-2 3 ⁄ 8 3-1 3 ⁄ 16 4-1 1 3-8 1 ⁄ 8 3- 8 2-9 7 ⁄ 16 3-2 0-3 1 ⁄ 2 4-8 3 ⁄ 4 1-7 7 ⁄ .
GENERAL PIPING CONNECTION SIZES CONNECTION SIZE (in.) Refrigerant T ransfer Connections 1 ⁄ 2 ODS (female) Condenser W ater Cooling Connectors 1 ⁄ 2 NPT (female) Safety Relief Head Pumpdown Conden.
T able 4 — Relief Devices STORAGE T ANK SIZE RELIEF V AL VE OUTLET SIZE QUANTITY REQUIRED F ACTOR lb air min Kg air min 28 1 in. NPT Female Connector 2 31.4 14.2 52 1 in. NPT Female Connector 2 52.3 23.7 LEGEND Ground Field Wiring Factory Wiring Contactor T erm.
CONTROLS AND COMPONENTS Figure 1 shows the major components of the PPS system. Pumpout Unit — The pumpout unit consists of a spring- mounted direct motor-driven reciprocating compressor , a water- cooled refrigerant condenser , an oil separator , suction and discharge valves to control refrigerant flow , and prewired safety and control devices.
NOTE: During this operation, maintain water circulation through the chiller cooler and condenser vessels to prevent tube freeze-up. DISTILLING THE REFRIGERANT — Refrigerant vapor is transferred from.
e. Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. Open refrigerant charg- ing valve 7 and storage tank charging valve 10 to let liquid refrigerant drain into the chiller .
3. Remove any remaining refrigerant. a. T urn on chiller water pumps. b. T urn on pumpout condenser water . c. Place valves in the following positions: V A L V E 1 a 1 b23 4567 81 0 1 1 CONDITION C C C C C d.
d. Close valve 1a. e. T urn of f pumpout compressor . f. Close valves 1b, 3, and 4. V A L V E 1 a 1 b 23458 1 1 CONDITION C C CCCCC C g. T urn of f pumpout condenser water . h. T urn of f chiller water pumps and lock out chiller compressor . T ransfer All Refrigerant to Chiller Cooler V essel: 1.
PUMPOUT COMPRESSOR OIL CHARGE — Use oil con- forming to Carrier specifications for reciprocating compres- sor use. Oil requirements are listed in T able 6. T able 6 — Pumpout Compressor Oil Requirements REFRIGERANT ISO VISCOSITY CARRIER SPECIFICA TION NO.
Ein wichtiger Punkt beim Kauf des Geräts Carrier 19XB (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier 19XB noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier 19XB - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier 19XB reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier 19XB erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier 19XB besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier 19XB verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier 19XB. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier 19XB gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.