Page 1 of the Emerson Rosemount 975 Flame Detectors user manual — Safety Quick Start Guide 00825-0400-4975, Rev AA June 2021
Seite 1 · Zum Vergrößern klicken
Seite 1

Safety Quick Start Guide 00825-0400-4975, Rev AA June 2021

Rosemount

™ 975

Flame Detectors

Page 2 of the Emerson Rosemount 975 Flame Detectors user manual — Contents
Seite 2 · Zum Vergrößern klicken
Seite 2

Contents

Rosemount 975 series 3

Certified product identification of the device 4

Applied standards 5

Safety parameters 6

Guidelines for configuring, installing, operating, and service 8

Conditions for safe operating 9

Page 3 of the Emerson Rosemount 975 Flame Detectors user manual — 1 Rosemount 975 series
Seite 3 · Zum Vergrößern klicken
Seite 3

1 Rosemount 975 series

The flame detectors series Rosemount 975 fulfills the requirements of the IEC 61508 for a Safety Integrity Level (SIL) 2 in a one-channel configuration or up to SIL 3 of IEC 61508 in a redundant configuration.

Page 4 of the Emerson Rosemount 975 Flame Detectors user manual — 2 Certified product identification of the device
Seite 4 · Zum Vergrößern klicken
Seite 4

2 Certified product identification of the device

Kind of productInfrared and ultraviolet flame detector series
Type designationRosemount 975HR4U, 975MR4U, 975UF4U, 975UR4U
Spectral response:Infrared and ultraviolet bands Supply voltage:18-32 Vdc Max. power consumption:300 mA Max. current:9.6 W Output:0-20 mA Fault relay Alarm relay 0-5 V
Page 5 of the Emerson Rosemount 975 Flame Detectors user manual — N2 EN 54-10:2002 and EN 54-10/A1:2005
Seite 5 · Zum Vergrößern klicken
Seite 5

3 Applied standards

N1 IEC 61508 Part 1 - 7:2010

Functional safety of electrical/electronic/programmable electronic safety-related systems

N2 EN 54-10:2002 and EN 54-10/A1:2005

Fire detection and fire alarm systems

Part 10Flame detectors - Point detectors
Page 6 of the Emerson Rosemount 975 Flame Detectors user manual — 4.3 Safety relevant parameters
Seite 6 · Zum Vergrößern klicken
Seite 6

4 Safety parameters

4.1 Safety function

The safety function of the Rosemount 975 flame detector series is to detect flames in which carbon dioxide (CO2) is produced in the combustion process and announce this over the 4-20 mA interface, analog output interface, and/or by opening the alarm-relay-contact.

4.2 Characteristics as per IEC 61508

Emerson Rosemount 975 Flame Detectors — 4.2 Characteristics as per IEC 61508 diagram (page 6)
Abb. 1 · 4.2 Characteristics as per IEC 61508
Safety Integrity Level (SIL)2 (one-channel configuration) and 3 (redundant configuration) HFT (intern)0 Device typeB Mode of operationLow demand mode and high demand or continues mode Average ambient temperaturemax. 55 °C Main time to repair0 h Proof-test interval365 days

4.3 Safety relevant parameters

Emerson Rosemount 975 Flame Detectors — 4.3 Safety relevant parameters diagram (page 6)
Abb. 2 · 4.3 Safety relevant parameters
Rosemount 975HR4U, 975MR4U (IR)Rosemount 975UF4U, 975UR4U (UV/IR) MAORYORYO2FDOMAORYORYO2FDO λ (fit) S9881290129083592312261226770 λ (fit) D9881285128583592312211221770 λ (fit) DU10410710710279828277 λ (fit) DD8841179117973284411391139693 SFF95%96%94%94%96%97%97%95% DC89%92%88%88%91%93%93%90% PFD (1oo1) avg4.6E044.7E044.5E044.5E043.5E043.6E043.4E043.4E04 PFD % SIL2 _4.6%4.7%4.5%4.5%3.5%3.6%3.4%3.4%
Page 7 of the Emerson Rosemount 975 Flame Detectors user manual — Remarks:
Seite 7 · Zum Vergrößern klicken
Seite 7
Emerson Rosemount 975 Flame Detectors — 4 Safety parameters diagram (page 7)
Abb. 3 · 4 Safety parameters
Rosemount 975HR4U, 975MR4U (IR)Rosemount 975UF4U, 975UR4U (UV/IR) MAORYORYO2FDOMAORYORYO2FDO PFH (1oo1, 1/h)1.0E07N/A1,0E07N/A7.9E08N/A7.7E08N/A PFH % SIL2 _10.4%N/A10.2%N/A7.9%N/A7.7%N/A PFD (1oo2) avg9.4E069.6E069,3E069.2E067.1E067.3E063.4E046.9E06 PFD % SIL3 _ _0.9%1.0%0.9%0.9%0.7%0.7%3.4%0.7% PFH (1oo2, 1/h)2.2E092.2E092.1E092.1E091.6E091.7E097.7E081.6E09 PFH % SIL3 _ _2.2%2.2%2.1%2.1%1.6%1.7%7.7%1.6%

Remarks:

  • N/A.: Not allowed for high demand mode
  • RYO: Using only the alarm-relay for alarming
  • RYO2: Using alarm and acc-relay for alarming (serial connected contacts)
  • MAO: Using the 4-20 mA - Interface for alarming
  • FDO: Using the analog OUT interface for alarming
  • Failure rates of the electronic components as per Siemens SN 29500, calculated based upon an ambient temperature of 55 °C and statistical data of the sensor elements
  • The calculation was performed based on a proof-test interval T1 = 365 days.
  • Without knowledge of the partly redundant internal structure of the detector a calculation with other proof-test intervals (e.g., two years) leads only to an approximate result.
Page 8 of the Emerson Rosemount 975 Flame Detectors user manual — 5 Guidelines for configuring, installing, operating, and service
Seite 8 · Zum Vergrößern klicken
Seite 8

5 Guidelines for configuring, installing, operating, and service

The alert conditions according to SIL 2 can be implemented by an:

  • Alert signal via 20 mA current loop
  • Alert signal via alarm relay and the fault relay

or

Page 9 of the Emerson Rosemount 975 Flame Detectors user manual — 6.3 Using the alarm and acc-relay for alarming
Seite 9 · Zum Vergrößern klicken
Seite 9

6 Conditions for safe operating

1. The flame detector shall consist only of the approved hardware and software modules.
2. The 24 V power supply must fulfill the requirements for PELV/SELV of EN 60950.
3. The automatic built-in test (BIT) must be activated.
4. The function of the Rosemount 975 Flame Detector (flame detector, function of the 0-20 mA interface, and relay functions) must be checked completely.

6.1 Using the 0-20 mA interface for alerting

The following parameters shall be set:

  • Automatic built-in test: On
  • Connected to 0-20 mA terminals

The following allowed output current must be supervised with an accuracy of ±5 percent.

  • Normal state: 4 mA
  • Warning state: 16 mA
  • Alarm state: 20 mA

6.2 Using the alarm relay contact for alerting

The following parameters shall be set:

  • Automatic built-in-test: On
  • Connected to normally closed (N.C.) contact of alarm relay terminals
  • Connected to fault relay terminals

The relay contacts (alarm and faulty relay) must be protected with a fuse rated at 0.6 of the nominal specified relay contact current.

The maximum contact rating that is allowed per SIL-2 is 30 Vdc.

The contact of the alarm relay opens if there is a fire alarm.

During the forwarding and evaluation of the alarm, the relay contact opens.

6.3 Using the alarm and acc-relay for alarming

The following parameters shall be set:

  • Automatic built-in-test: On
Page 10 of the Emerson Rosemount 975 Flame Detectors user manual — 6.5 Other
Seite 10 · Zum Vergrößern klicken
Seite 10
  • Connected to normally closed (N.C.) contact of alarm relay terminals and auxiliary relay terminals.
  • The contacts of alarm relay and auxiliary relay must connected serial.
  • Connected to fault relay terminals.
  • The relay contacts of auxiliary relay, alarm relay and faulty relay must be protected with a fuse rated at 0.6 of the nominal specified relay contact current.
  • The maximum contact rating that is allowed per SIL-2 is 30 Vdc.
  • The contacts of the alarm relay and the auxiliary relay open if there is a fire alarm.
  • During the forwarding and evaluation of the alarm, the relay contacts opens.

6.4 Using the analog voltage output for alerting

The following parameters shall be set:

  • Automatic built-in-test: On
  • Connected to analog voltage output terminal. The following allowed output voltage must be supervised with an accuracy of ±20 percent. — Normal state: 2 V
— Fault state<1 V
— Alarm state5 V

The analog voltage output can be used as low demand only.

6.5 Other

1. The window of the sensor must be examined at appropriate time intervals for partial contamination.
2. The HART ® and the RS-485 interfaces must not be used for the transmission of the safety-related data.
Page 11 of the Emerson Rosemount 975 Flame Detectors user manual — 6.4 Using the analog voltage output for alerting
Seite 11 · Zum Vergrößern klicken
Seite 11
Page 11 of the Emerson Rosemount 975 Flame Detectors user manual — 6.4 Using the analog voltage output for alerting
Page 12 of the Emerson Rosemount 975 Flame Detectors user manual — *00825-0400-4975* Safety Quick Start Guide 00825-0400-4975, Rev. AA June 2021
Seite 12 · Zum Vergrößern klicken
Seite 12

*00825-0400-4975* Safety Quick Start Guide 00825-0400-4975, Rev. AA June 2021

For more informationwww.emerson.com
Quellen

Referenzen & Links

In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.

Frage zu Emerson Rosemount 975 Flame Detectors stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Emerson Rosemount 975 Flame Detectors

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Emerson Rosemount 975 Flame Detectors PDF-Anleitung

12 Seiten·453 KB·Sensor·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…