Benutzeranleitung / Produktwartung ASPAS1BBA007 des Produzenten Bryant
Zur Seite of 24
GENERA C POWER SYSTEMS, INC. R R Owner’s Manual Air-cooled, Prepackaged Automatic Standby Generators Models: ASPAS1BBA007 (6 kW NG, 7 kW LP) ASPAS1BBA012 (12 kW NG, 12 kW LP) ASPAS1BBA015 (13 kW NG, 15 kW LP) DEADL Y EXHAUST FUMES.
Bryant I NTRODUCTION Thank you for purchasing this model of the Bryant product line. This model is a compact, high performance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure.
T able of Cont ents Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Bryant 1 Introduction ........................Inside Front Cover Read This Manual Thoroughly ..............................IFC Contents .........................................
2 Bryant Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained.
Bryant 3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation.
Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations.
Section 1 — General Information Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Bryant 5 1.4 TH E GEN ER A T OR Exhaus t En c lo su r e O i l Di p stic k D a t a D ecal C ontro l Pa n el F uel.
6 Bryant Section 1 — General Information Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 1.5 SP E CI F ICA TIONS 1.5.1 GEN ERA T OR Model ASPAS1BBA007 ASPAS1BBA012 ASPAS1BBA015 Rated Max. Continuous Power Capacity (Watts*) 6,000 NG/7,000 LP 12,000 NG/12,000 LP 13,000 NG/15,000 LP Rated Voltage 120/240 120/240 120/240 Rated Max.
Bryant 7 Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See Section 1.9 for instructions on reconfiguration of the fuel system. Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas.
1.1 0 B A TTER Y I NS T ALLA TION Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it. Before installing and connecting the battery, complete the following steps: 1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
Bryant 9 Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
10 Bryant 2.3 AUT OMA TIC TR ANSF ER OP ER A TION To select automatic operation, do the following: 1. Make sure the transfer switch main contacts are set to their UTILITY position, i.
Bryant 11 2.5 MAN U AL TR ANSF ER OP ER A TION 2.5.1 TRANSF ER T O GEN ER A T OR POWER S OURCE To start the generator and activate the transfer switch manually, proceed as follows: 1. Set the generator’s AUTO/OFF/MANUAL switch to OFF. 2. Set the generator’s main circuit breaker to its OFF (or open) position.
12 Bryant NOTE: The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 on the controller printed cir cuit board (Remote Not Auto) is ON.
Bryant 13 Section 3 — Maintenance Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Figure 3.1 – Generator Control Panel 3.2 CH E CKI NG TH E ENGI N E OI L LEVEL For oil capacities, see “Specifications,” Section 1.5. For engine oil recommendations, see Section 3.
14 Bryant Section 3 — Maintenance Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Figure 3.4 – Oil Drain Hose and Filter 3.4 CHANGI NG TH E OI L F I L TER Change the engine oil filter as follows: 1. With the oil drained, remove the old oil filter by turning it counterclockwise.
Bryant 15 Figure 3.7 – Setting the Spark Plug Gap 3.7 B A TTER Y MAI NTENANCE The battery should be inspected per the “Service Schedule,” Section 4.1. The following procedure should be followed for inspection: 1. Inspect the battery posts and cables for tightness and corrosion.
16 Bryant Figure 3.8 – Cooling V ent Locations The exhaust from this pr oduct gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
Bryant 17 Section 4 — Service Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 4.1 SERVICE S CH EDU LE A TTENTION: It is recommended that all service work be performed by the nearest Bryant Dealer .
18 Bryant Section 5 — T roubleshooting Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 5.1 TROU B LE SHOO TI NG GU I DE P ROB LEM CAUSE C OR R E CTION The engine will not crank. 1. Fuse blown. 1. Replace 15A fuse in generator control panel. 2.
Bryant 19 BRYANT "TWO YEAR" LIMITED WARRANTY FOR "PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS" For a period of two years from the date of original sale, Bryant warrants that its generator will be free from defects in material and workmanship for the items and period set forth below.
20 Bryant CALI FOR N IA EM ISSION C ONTROL W AR RANT Y ST A TEM ENT Y OUR W AR R ANTY R IGHTS AND OB LIGA TIONS The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System Warranty on your new engine.
Bryant 21 EM IS SION CONTROL S Y S TEM W ARR ANT Y Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines.
PART NO. 0F6906 CATALOG NO. OM18-5 REV. * (6/01/05) PRINTED IN U.S.A..
Ein wichtiger Punkt beim Kauf des Geräts Bryant ASPAS1BBA007 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Bryant ASPAS1BBA007 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Bryant ASPAS1BBA007 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Bryant ASPAS1BBA007 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Bryant ASPAS1BBA007 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Bryant ASPAS1BBA007 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Bryant ASPAS1BBA007 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Bryant ASPAS1BBA007. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Bryant ASPAS1BBA007 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.