SUPPLEMENTAL INSTRUCTIONS

8403-062 Remote Indoor Air Temperature Sensor

Installation

1. Shielded twisted pair, 22 AWG (or heavier) should be used to avoid possible interference from other electrical systems. The shield (drain) should be connected to 24V Common (C) on the controller end.

Carefully read and follow entire instructions before starting the installation. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage the controller sensor.

2. The sensor comes with a cover and mounting base to mount and protect the remote indoor sensor.
3. Select the exact mounting location and route a 2-conductor interconnecting wire between the remote indoor sensor and the 8403-060 controller location.

The 8403-062 Remote Indoor Temperature Sensor is a 10k-ohm Type II thermistor, which can be used as an accessory for use with Bard 8403-060 controller system or the Bard CompleteStat controller series. The 8403-060 can be configured to control using the 8403-062 remote sensor as the only sensor, or to average the measured temperature at the remote sensor location with the temperature at the controller location.

4. Terminate the interconnection wiring at the two screw terminals on the remote indoor sensor. See Figure 1 for 8403-060 and CompleteStat connections.

FIGURE 1

CONNECTION SENSOR INDOOR

COMPLETE STAT CONNECTION

A+

B-

GND

OD

ID

REM

GND

GND

MIS-2300 B

Bard Remote Indoor Air Temperature Sensor (8403-062) — FIGURE 1 diagram (page 1)
Abb. 1

Bard Manufacturing Company, Inc. Bryan, Ohio 43506

Manual7960-554B Supersedes: 7960-554A Date: 10-2-20

www.bardhvac.com

Page 1 of 2

+

Page 2 of the Bard Remote Indoor Air Temperature Sensor (8403-062) user manual — SUPPLEMENTAL INSTRUCTIONS
Seite 2 · Zum Vergrößern klicken
Seite 2
5. The termination point at the controller will be GND and ID terminals at the right side of the controller subbase. Sensor polarity is not important.

When the 8403-062 sensor is properly connected, the 8403-060 controller will recognize the sensor connection and automatically place Remote Indoor Sensor selection options in the Installer menu.

Access Installer menu and go to Remote Indoor Sensor option. Select either “Remote sensor only” or “Average with stat”.

See Table 1 for Temperature/Ohm relationship of the sensor.

TABLE 1 Degrees F/Ω

Temp °FΩ 085,378 182,710 280,135 377,649 475,249 572,931 670,693 768,531 866,442 964,475 1062,475 1160,592 1258,771 1357,012 1455,311 1553,667 1652,077 1750,540 1849,054 1947,616 2046,225 2144,880 2243,578 2342,318 2441,099 2539,920 2638,778 2737,672 2836,602 2935,566 3034,563 3133,591 3232,650
Temp °FΩ 3331,738 3430,855 3530,000 3629,171 3728,367 3827,589 3926,834 4026,103 4125,394 4224,706 4324,039 4423,393 4522,766 4622,158 4721,568 4820,996 4920,441 5019,902 5119,379 5218,872 5318,379 5417,902 5517,438 5616,987 5716,550 5816,125 5915,713 6015,312 6114,923 6214,545 6314,178 6413,822 6513,475
Temp °FΩ 6613,138 6712,811 6812,493 6912,184 7011,883 7111,591 7211,307 7311,031 7410,762 7510,501 7610,247 7710,000 789,760 799,526 809,298 819,077 828,862 838,651 848,448 858,250 868,056 877,868 887,685 897,507 907,333 917,164 927,000 936,839 946,683 956,531 966,383 976,238 986,098
Temp °FΩ 995,961 1005,827 1015,697 1025,570 1035,446 1045,326 1055,208 1065,094 1074,982 1084,873 1094,767 1104,663 1114,562 1124,464 1134,368 1144,274 1154,183 1164,094 1174,007 1183,922 1193,839 1203,758 1213,679 1223,602 1233,527 1243,453 1253,382 1263,312 1273,243 1283,177 1293,112 1303,048

Manual 7960-554B Page 2 of 2

Testing Completed Wiring

Quellen

Referenzen & Links

In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.

Frage zu Bard Remote Indoor Air Temperature Sensor (8403-062) stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Bard Remote Indoor Air Temperature Sensor (8403-062)

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Bard Remote Indoor Air Temperature Sensor (8403-062) PDF-Anleitung

2 Seiten·52 KB·Sensor·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…