Fire Alarm Systems | FLM‑I 420‑S Short Circuit Isolator
▶Rotary switch for automatic and manual address

▶Preservation of LSN loop functions in the event of a
short-circuit by two integrated isolators
▶Power supply via LSN
▶Three free screw terminals
The Short Circuit Isolator isolates alarm zones in which a short circuit has occurred. This means the functionality of the remainder of the network remains preserved.
Features of improved LSN

Address switch (rotary switch)
The address of the Short Circuit Isolator is set using the rotary switches.
The following settings are possible:
0 0 0 Loop/stub in LSN mode improved version with automatic addressing (T-tap system not possible)
0 0 1 - 254 Loop/stub/T-tap system in LSN mode improved version with manual addressing
CL 0 0 Loop/stub in classic LSN mode
The Short Circuit Isolator isolates alarm zones in which a short circuit has occurred. The following illustrations show typical configurations of the isolator module.
b1+ / a- / b2+ LSN
N/A (3 x) free terminals, e.g. for looping through ext. auxiliary volt- age and for shielding
setting · Configuration · Description Connector


Qty. Components
1 Short Circuit Isolator with surface-mounted housing.
1 DIN rail adapter
Pos. Description
Input voltage 15 V DC to 33 V DC
I, II, III Floors
Max. current consumption
Typical wiring in a T‑Tap
< 0.25 mA
1 LSN
b2+
Pos. Description
1 Alarm zone / device group with LSN elements
Connections 6 threaded clamps
Complies with EN54-17:2005
Germany VdS G 207045 FLM-I 420-S; FLM-I 420-D
Signal white, RAL 9003
Installation/Configuration Notes • National standards and guidelines must be taken into account during the planning stage.
Dimensions Approx. 126 x 126 x 71 mm (4.96 x 4.96 x 2.8 in.)
Weight Approx. 150 g (5.3 ounces)

-20 °C to 50 °C (-4 °F to 122 °F)
-25 °C to 85 °C (-13 °F to. 176 °F)
Permitted relative humidity < 96%
Classes of equipment as per IEC 60950
Protection class as per IEC 60529
Ordering Information
FLM‑I 420‑S Short Circuit Isolator for the isolation of alarm zones in which a short circuit has occurred.
FLM‑IFB126‑S Surface-mounted Housing as retainer for the interface modules ser- ies 420 type DIN rail (-D) or spare housing for type surface-mount (-S)
www.boschsecurity.com

Americas: Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Europe, Middle East, Africa: Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Asia-Pacific: Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 apr.securitysystems@bosch.com www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice T1868129547 | Cur: en-US, V7, 16 Dec 2010
Represented by
In dieser Anleitung genannte Seiten – Hersteller, Support und Downloads.
Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.
Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.