TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 18 SEER – R-410A MODELS: YZH024 THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .
2 Unitary Products Group 345094-YTG-D-0108 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request.
Unitary Products Group 3 345094-YTG-D-0108 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table.
4 Unitary Products Group 345094-YTG-D-0108 COOLING CAP ACITY - With A ir Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B 17 FC/MC43B 1 645 18.
Unitary Products Group 5 345094-YTG-D-0108 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 18.
6 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)8*C16 FC/MC/PC48C 21 1 880 33.0 23.4 16.3O 13.30 2 1500 46.0 34.6 1 1.70 P(C,V)8*C20 FC/MC/PC48C 21 1 1030 33.0 25.0 16.4O 13.40 2 1610 46.5 35.4 1 1.80 P(C,V)9*C16 FC/MC/PC48C 21 1 1090 34.0 26.
Unitary Products Group 7 345094-YTG-D-0108 ** Refer to Quick Selection Chart for specific furnace match-up. HEA TING CAP ACITY - With Air Handler UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 O D 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B FC/MC43B 17 1 645 19.
8 Unitary Products Group 345094-YTG-D-0108 HEA TING CAP ACITY - With V a riable Speed F urnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 19.
Unitary Products Group 9 345094-YTG-D-0108 YZH0361 1 P(C,V)8*C20 FC/MC62D 24 1 780 26.4 - - 4.00 2 1200 36.0 26.2 9.55 4 .20 2 780 36.0 23.8 9.35 3.20 P(C,V)9*C20 FC/MC62D 24 1 790 26.4 - - 4.00 2 1 195 36.0 26.0 9.55 4.20 2 790 36.0 24.0 9.35 3.40 P(C,V)9*D20 FC/MC62D 24 1 775 26.
10 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)9*D20 FC/MC/PC60D 24 1 985 36.0 - - 3.80 2 1560 48.0 32.6 9.8 4. 00 2 985 39.0 25.6 9.5 3. 20 P(C,V)8*C20 FC/MC62D 24 1 1030 36.0 - - 3.80 2 1610 48.0 32.8 9.8 4. 00 2 1030 38.5 25.2 9.5 3. 20 P(C,V)9*C20 FC/MC62D 24 1 1010 36.
Unitary Products Group 11 345094-YTG-D-0108 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion valves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB1370012 4) - The bonnet sensor is used to sense plenum temperature, and is optional with a gas or oil back-up heat source.
12 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 13 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
14 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 15 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
16 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 17 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
18 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 19 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
20 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 21 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
22 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 23 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
24 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 25 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
26 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 27 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Subject to change without notice. Printe d in U.S.A. 345094-YTG-D-0108 Copyright © by Unitary Products Gr oup 2008. All ri ghts reserved. Supersedes: 345094-YTG-C-1007 Unitary 5005 Norman Product s Y.
Ein wichtiger Punkt beim Kauf des Geräts York YZH024 THRU 060 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York YZH024 THRU 060 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York YZH024 THRU 060 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York YZH024 THRU 060 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York YZH024 THRU 060 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York YZH024 THRU 060 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York YZH024 THRU 060 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York YZH024 THRU 060. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York YZH024 THRU 060 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.