Benutzeranleitung / Produktwartung TCGD12 THRU 60 des Produzenten York
Zur Seite of 18
TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: TCGD12 THRU 60 (1 THRU 5 NOMINA L TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.
400034-YTG-B-0708 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 3 Additional R-22 Charge / Orifice Size for V arious Matched Systems Outdoor Unit TCGD12 S21S2(H) TCGD18 S21S2(H) TCGD24 S21S2(H) TCGD30 S21S2(H) TCGD36 S21S2(H) TCGD42 S21S2(H) TCGD48 S21S2(H) TCGD60 S21S2 Required Orifice or TXV 1,2 0.
400034-YTG-B-0708 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for th e condenser , the smallest evaporator and 15 feet of inter- connecting line tubing.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 5 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SENS. 13 SEER AC WITH MA TCGD18S21S2(H) MA08B 17 F C/MC18B 600 18.
400034-YTG-B-0708 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER AC WITH AHP / SHP / F*FP TCGD12S21S2(H) AHP18 17 – 450 12.0 8.9 13.00 1 1.00 TCGD18S21S2(H) AHP18 17 – 650 18.0 12.6 13.00 1 1.00 AHP24 17 – 650 18.0 12.6 13.00 1 1.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SENS. TCGD12S21S2(H) 450 - 750 14,17 FC/MC/PC18 450 12.
400034-YTG-B-0708 8 Johnson Controls Unitary Products 1 COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 13 SEER AC WITH V ARIABLE SPEED FUR NACES 2 TCGD18S21S2(H) PV8*A12 FC/MC/PC18A 14 600 18.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 9 TCGD36S21S2(H) PV8*A12 FC/MC/PC37A 14 1200 35 .2 25.0 14.00 12.00 PV9*A12 FC/MC/PC37A 14 1200 35 .2 25.0 14.00 12.00 PV8*B16 FC/MC/PC43B 17 1200 35.4 25.0 14.00 12.00 PV8*C16 FC/MC/PC43C 21 1200 35 .
400034-YTG-B-0708 10 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Required when using TXV i ndoor coil. Also, provides increased starting torque for a reas with low voltage. OFF CYCLE TIMER DELA Y - Provides a 5-minute off cycle to prevent rapid recycling of the compressor .
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
400034-YTG-B-0708 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 13 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
400034-YTG-B-0708 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 15 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
400034-YTG-B-0708 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
400034-YTG-B-0708 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between.
Subject to change without notice. Printe d in U.S.A. 400034-YTG-B-0708 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 400034-YTG-A-0408 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections.
Ein wichtiger Punkt beim Kauf des Geräts York TCGD12 THRU 60 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York TCGD12 THRU 60 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York TCGD12 THRU 60 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York TCGD12 THRU 60 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York TCGD12 THRU 60 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York TCGD12 THRU 60 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York TCGD12 THRU 60 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York TCGD12 THRU 60. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York TCGD12 THRU 60 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.