Benutzeranleitung / Produktwartung H3CE120 des Produzenten York
Zur Seite of 16
GENERAL These condensing units are designed for outdoor installation on a roof or at ground level. Every unit is completely piped and wired at the factory and is shipped ready for immediate installa- tion.
035-15407-002-B-0404 2 Unitary Products Group General ................................................................................ 1 Reference ............................................................................ 1 Inspection ..............
LIMIT ATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply , installation must conform with the appropriate national codes. See T able 1 for Unit Application Data. Units are designed to meet National Safety Code Standards.
CLEARANCES All units require certain minimum clearances for proper opera- tion and service. Refer to Figure 4 for these clearances. WARNING: Do not permit overhanging structures or shrubs to obstruct condenser air discharge. Additional height may be required for snow clearance if winter operation is expected.
035-15407-002-B-0404 Unitary Products Group 5 Model HCE V oltage Code Compressor Condenser Fan Motor Unit Ampacity (Amps) Max. Fuse Size 1 (Amps) Power Supply RLA LRA Power Supply HP Qty . FLA 090 25 208/230-3-60 25.6 190 208/230-1-60 3/4 1 3.03 35.1 60 46 460-3-60 12.
035-15407-002-B-0404 6 Unitary Products Group FIG. 5 - UNIT DIMENSIONS AND CLEARANCES A I R O U T A I R I N 4- 5/ 8 ( 118) 2 5 - 3 / 4 ( 6 5 5 ) 1 0 - 1 / 8 ( 2 5 8 ) 2 - 1 / 2 ( 6 . 4 ) 4 - 1 / 2 ( 115) G U A G E L I N E A C C E S S 1 - 1 / 8 " ( 2 8 .
REFRIGERANT PIPING GENERAL GUIDELINES Many service problems can be avoided by taking adequate precautions to provide an internally clean and dry system and by using procedures and materials that conform with estab- lished standards. Use hard drawn copper tubing where no appreciable amount of bending around pipes or other obstructions is necessary .
035-15407-002-B-0404 8 Unitary Products Group NOTE: Add the operating charge of the condensing unit, the evaporator coil and the refrigerant lines to determine the total refrigerant charge of the system. 1 Charges are based on 40 ° F suction temperature and a 105 ° F liquid temperature.
EXTENDING THE SERVICE PORTS (Refer to Fig 7.) 1. Loosen the screws securing the service ports in shipping position. 2. Push the service ports through the corner post.
10. After the disc has been removed, burnish the external sur - faces and clean the internal surfaces as outlined above. The suction piping can now be brazed to the suction connection on the evaporator coil while maintaining a minimum flow of dry nitrogen.
035-15407-002-B-0404 Unitary Products Group 11 FIG. 7 - EXTENDING THE SERVICE PORTS.
035-15407-002-B-0404 12 Unitary Products Group FIG. 8 - CHARGING CURVE HCE090 FIG. 9 - CHARGING CURVE HCE120.
035-15407-002-B-0404 Unitary Products Group 13 FIG. 10 - CHARGING CURVE HCE150.
UNIT OPERATION - 7-1/2, 10 & 12-1/2 TON When the external control calls for cooling at terminal Y1: 1. The system controller (SC) is energized. The system con - troller starts the compressors and enables the condenser fans by energizing contactor 1M (and 2M on the 12-1/2 ton, 208/230 volt models).
If the unit continues to be shut down by one of its safety con - trols, service should be called to determine the cause of the problem. Repeatedly resetting the lockout circuit may damage the unit. The following accessories are available to provide low am - bient operation to 0 ° F.
Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright © 2004 by Y ork International Corporation.
Ein wichtiger Punkt beim Kauf des Geräts York H3CE120 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York H3CE120 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York H3CE120 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York H3CE120 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York H3CE120 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York H3CE120 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York H3CE120 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York H3CE120. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York H3CE120 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.