036-21528-007-A-12 05 FOR DISTRIBUTION USE ONL Y - NOT TO BE USED A T POINT OF RET AIL SALE ® AFFINITY™ SERIES SINGLE PACKAGE HEAT PUMPS BHP024 THRU 060 2 THRU 5 NOMINAL TONS 13 SEER FACTORY MOUNTED TXV DESCRIPTION York ® Affinity™ Series packaged heat p umps are designed for outdoor installation.
036-21528-007-A-12 05 2 Unitary Products Group CONDENSA TE P AN A non-corr osive, long-la sting, water -tight pan is posi- tioned below the e vaporator coi l to collect and dra in all condensate; less collection of stagnate c ondensate will build-up.
036-21528-007-A-1205 Unitary Products Group 3 PROTECTED COMPRESSOR The compressor is internally pr otected against high pressure and tempe rature. This is accomplished by the simultaneous operatio n of high pressure relief valve and a temperature se nsor which protec ts the compres- sor, if undesirable o perating conditions occur.
036-21528-007-A-12 05 4 Unitary Products Group RECT ANGLE TO ROUND ADAPTERS Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed an d designed to fit over current duct openin gs on the base unit. Transition is from 15" square to 14 " round.
036-21528-007-A-1205 Unitary Products Group 5 SEER =Seasonal Energy Ef ficiency Ratio - t he total cool ing o utput in BTU's during a no rmal annual usage per iod for cooling divi ded by the to tal electric power input in watt-hours during the same period.
036-21528-007-A-12 05 6 Unitary Products Group T ABLE 3: COOLING CAP ACITIES - 2 TON (BHP024) TEMPERA TURE AIR ON OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR COIL 800 CFM 900 CFM WB °F WB °F 72 67 62 57 72 67 62 57 85 °F NET CAP . MBH 29.1 26.0 23.8 23.
036-21528-007-A-1205 Unitary Products Group 7 T ABLE 4: COOLING CAP ACITIES - 2-1/2 TON (BHP030) TEMPERA TURE AIR ON OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR COIL 1000 CFM 1 125 CFM WB °F WB °F 72 67 62 57 72 67 62 57 85 °F NET CAP . MBH 34.1 31.
036-21528-007-A-12 05 8 Unitary Products Group T ABLE 5: COOLING CAP ACITIES - 3 TON (BHP036) TEMPERA TURE AIR ON OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR COIL 1050 CFM 1200 CFM WB °F WB °F 72 67 62 57 72 67 62 57 85 °F NET CAP . MBH 41.1 37.5 34.
036-21528-007-A-1205 Unitary Products Group 9 T ABLE 6: COOLING CAP ACITIES - 3-1/2 TON (BHP042) TEMPERA TURE AIR ON OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR COIL 1300 CFM 1400 CFM WB °F WB °F 72 67 62 57 72 67 62 57 85 °F NET CAP . MBH 48.8 44.5 40.
036-21528-007-A-12 05 10 Unitary Products Group T ABLE 7: COOLING CAP ACITIES - 4 TON (BHP048) TEMPERA TURE AIR ON OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR COIL 1500 CFM 1600 CFM WB °F WB °F 72 67 62 57 72 67 62 57 85 °F NET CAP . MBH 54.3 50.4 45.
036-21528-007-A-1205 Unitary Products Group 11 T ABLE 8: COOLING CAP ACITIES - 5 TON (BHP060) TEMPERA TURE AIR ON OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR COIL 1600 CFM 2000 CFM WB °F WB °F 72 67 62 57 72 67 62 57 85 °F NET CAP . MBH 64.0 58.5 53.
036-21528-007-A-12 05 12 Unitary Products Group T ABLE 9: HEA TING CAP ACITIES - 2 TON (BHP024) CFM RETURN AIR °F CAP 1 & KW OUTDOOR AIR TEMPERA TURE, °F (72% RH) -10 0 10 20 30 40 50 6 0 600 55 MBH 10.216 1 1.748 13.601 15.843 18.554 21.834 25.
036-21528-007-A-1205 Unitary Products Group 13 T ABLE 1 1: HEA TING CAP ACITIES - 3 TON (BHP036) CFM RETURN AIR °F CAP 1 & KW OUTDOOR AIR T EMPERA TURE, °F (72% RH) -10 0 10 20 30 40 50 60 900 55 MBH 10.597 12.792 15.448 18.6 60 22.545 27.244 32.
036-21528-007-A-12 05 14 Unitary Products Group T ABLE 13: HEA TING CAP ACITIES - 4 TON (BHP048) CFM RETURN AIR °F CAP 1 & KW OUTDOOR AIR T EMPERA TURE, °F (72% RH) -10 0 10 20 30 40 50 60 1200 55 MBH 13.91 1 17.096 21.021 25.859 31. 821 39.170 48.
036-21528-007-A-1205 Unitary Products Group 15 NOTE: Above data inclu des allowan ces for a dry indoor coil and no filter s. For additional pressure drop s, refer to the “Addit ion al S tatic Pressure Resistance” t able. T ABLE 15: SIDE & BOTTOM SUPPLY AIR BL OWER PERFORMANCE (208/230/460 VOLT 1 ) MODEL NO.
036-21528-007-A-12 05 16 Unitary Products Group FIGURE 2 - FIELD WIRING DIAGRAM R G W R C Y Y W2 C W1 O O G THERMOST A T UNIT TERMINAL STRIP * ** ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire. * = Only required on units with supplemental electric heat.
036-21528-007-A-1205 Unitary Products Group 17 T ABLE 17: ELECTRIC DA T A (BASIC UNIT) Model BHP Power Supply Voltage Limitations 1 Compressor OD Fan Motor FLA Supply Air Blowe r Motor FLA MCA (Amps) Max. Fuse Size (Amps) 2 Max HACR Breaker Size (Amps) Unit Power Factor Transformer Size (VA) Min.
036-21528-007-A-12 05 18 Unitary Products Group * KW listed is for 240 volts, use T able 17 for 208 or 230 volts. ** KW listed is for 480 volts, use T able 17 for 460 volts. *** KW listed is for 600 volts, use T able 17 for 575 volts. T ABLE 18: ELECTRICAL DA T A (13 SEER HEA T PUMP / ELECTRIC HEA T) Model BHP Power Supply Compressor Cond.
036-21528-007-A-1205 Unitary Products Group 19 T ABLE 19: APPLICA TION DA T A MODEL BHP 024 030 036 042 048 060 MINIMUM AIR FLOW (CFM) COOLING 800 1000 1050 1300 1500 1500 HEA TING 800 1000 1050 1400 .
036-21528-007-A-12 05 20 Unitary Products Group FIGURE 5 - UNIT DIMENSIONS )5217 )5217 $OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH &HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW $ 29(5$// %$&.
036-21528-007-A-1205 Unitary Products Group 21 FIGURE 6 - TYPICAL APPLICA TIONS.
036-21528-007-A-12 05 22 Unitary Products Group FIGURE 7 - ROOF CURB DIMENSIONS.
036-21528-007-A-1205 Unitary Products Group 23 FIGURE 8 - TYPICAL WIRING DIAG RAM (208/230-1 -6 0 POWER SUPPLY).
036-21528-007-A-12 05 24 Unitary Products Group FIGURE 9 - TYPICAL WIRING DI AGRAM (230-3-60 POWER SUPPLY).
036-21528-007-A-1205 Unitary Products Group 25 FIGURE 10 - TYPICAL WIRING DI AGRAM (460/575-3 -60 POWER SUPPLY).
036-21528-007-A-12 05 26 Unitary Products Group MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION Units shall be factory-asse mbled, single pack aged, Heat Pumps, designed for outdoo r mounted installa- tion. Units shall have mini mum SEER ratings of 13.0.
036-21528-007-A-1205 Unitary Products Group 27 B. Shal l have internal isolation and sound muffling to minimize vibration and noise, a nd be externally iso- lated on a dedica ted, independent mounting.
Subject to change without notice. Printed in U.S.A. 036-21528-007-A-1205 Copyright © by Unitary Products Group 2005. All rights re served. Supersedes: 036-21528-006-A-1005 Unitary 5005 Norman Product.
Ein wichtiger Punkt beim Kauf des Geräts York AFFINITY BHP024 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York AFFINITY BHP024 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York AFFINITY BHP024 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York AFFINITY BHP024 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York AFFINITY BHP024 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York AFFINITY BHP024 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York AFFINITY BHP024 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York AFFINITY BHP024. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York AFFINITY BHP024 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.