Benutzeranleitung / Produktwartung 300 des Produzenten York
Zur Seite of 56
036- 21410-001- A-0502 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SINGLE P ACKAGE GAS/ELECTRIC UNITS AND SINGLE P ACKAGE AIR CONDITIONERS DJ 180, 210 , 240 & 30 0 15 & 25 NOMINAL TONS 1 1.80 EER (15 TONS), 1 1 .
036-214 10-001- A-0502 2 Unitary Products Group T ABLE OF CONTENTS D E S C R I P T I O N ...... ...... .......... ...... . 1 N O M E N C L A T U R E............. ....... ....... 3 F E A T U R E S ..... .......... ...... .......... . 8 F A C T O R Y - I N S T A L L E DO P T I O N S .
036-2141 0-001-A-0 502 Unitary Products Group 3 PRODUCT NOMENCLA T URE.
036-214 10-001- A-0502 4 Unitary Products Group PRODUCT NOMENCLA TURE - Continued 15-25T Sunl ine Magnu m™ Model Number Nom encla ture Addi tion al Optio ns AA None AB Phase Monitor AC Coil Guard AD.
036-2141 0-001-A-0 502 Unitary Products Group 5 EB Johnson UNT Controller , DFS, APS & Phase M onitor , Hinged Filter Door & T ooless A ccess Panels EC Johnson UNT Controller , DFS, APS & .
036-214 10-001- A-0502 6 Unitary Products Group JB Johnson UNT Controller , DFS , APS & Phase Monitor JC Johnson UNT Controller , DFS, APS & Coil Guard JD Johnson UNT Co ntroller , DFS, APS, P hase Monitor , & Coil Guard JE Johnson UNT Controller , DFS, APS & T echnicoat Cond.
036-2141 0-001-A-0 502 Unitary Products Group 7 TE T echnicoa t Condenser Coil, Phase M onitor , & Coil Guard TF T echnicoat Condenser Coil, Phas e Monitor , & Dirty F ilter Switch TG T echnic.
036-214 10-001- A-0502 8 Unitary Products Group FEA TURES All models are avai lable with a wide variety of fac tory- mounted op tions such as st ainles s steel hea t exchangers , phase mo nitor , dirty filter switc h, and co il guard to mak e them suit able for almost every ap plica tion.
036-2141 0-001-A-0 502 Unitary Products Group 9 • Electric Heat Op eration - Al l elec tric heat models (fac - tory ins tal led only ) are wire d for a single power source and i nclude a bank of nic.
036-214 10-001- A-0502 10 Unitary Products Group • FIL TER OPTIONS - S tandard unit s are shipped w ith 2” throw-a way filters in sta lled. 2” pleat ed and 4” pleated fil - ters are off ered as a factory inst all ed option.
036-2141 0-001-A-0 502 Unitary Products Group 11 • ENTHALPY ACCESSOR Y CONTROL KIT -T h i sk i t cont ains the requ ired com ponent s to convert a single enthalp y econom izer to dual ent halpy . • BURGLAR BARS - Mount i n the s upply and return opening s to prevent entry into the duct work.
036-214 10-001- A-0502 12 Unitary Products Group NOTE: All gas units are two-stage heating. First stage is 50% of total. S.S.E. = Steady S tate Efficiency (80%) - output divided by input. T ABLE 1: SOUND POWER RA TING 1 UNIT SIZE CFM ES P BLOW ER SOUND PO WER (db 10 -1 2 Wat ts) Octave Ban d Centerline Frequency (Hz) SWL dB(A ) dB(A ) @ 10Ft.
036-2141 0-001-A-0 502 Unitary Products Group 13 T ABLE 4 : COOLING CAPACITIES FOR DJ18 0 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 85 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 14 Unitary Products Group T ABLE 5 : COOLING C AP ACITIES FOR DJ180 AT 95°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 95 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 15 T ABLE 6 : COOLING CAPACITIES FOR DJ18 0 AT 105° F RETURN AIR OUTDOOR AMBIENT TEM PERA TURE (°F): 105 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 16 Unitary Products Group T ABLE 7 : COOLING C AP ACITIES FOR DJ180 AT 1 15 °F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 115 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 17 T ABLE 8 : COOLING CAPACITIES FOR DJ18 0 AT 125° F RETURN AIR OUTDOOR AMBIENT TEM PERA TURE (°F): 125 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 18 Unitary Products Group T ABLE 9 : COOLING C AP ACITIES FOR DJ210 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 85 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 19 T ABLE 1 0: COOLING CAPACITIES FOR DJ2 10 AT 95° F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 95 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 20 Unitary Products Group T ABL E 1 1: COO LING CAPACITIES FOR D J210 AT 105°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 105 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 21 T ABLE 1 2: COOLING CAPACITIES FOR DJ2 10 AT 1 15°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 115 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 22 Unitary Products Group T ABLE 1 3: COOLING CAPACITIES FOR DJ2 10 AT 125 °F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 125 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 23 T ABLE 1 4: COOLING CAPACITIES FOR DJ2 40 AT 85° F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 85 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 24 Unitary Products Group T ABLE 1 5: COOLING CAPACITIES FOR DJ2 40 AT 95°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 95 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 25 T ABLE 1 6: COOLING CAPACITIES FOR DJ2 40 AT 105 °F RETURN AIR OUTDOOR AMBIENT TEM PERA TURE (°F): 105 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 26 Unitary Products Group T ABLE 1 7: COOLING CAPACITIES FOR DJ2 40 AT 1 15°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 115 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 27 T ABLE 1 8: COOLING CAPACITIES FOR DJ2 40 AT 125 °F RETURN AIR OUTDOOR AMBIENT TEM PERA TURE (°F): 125 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 28 Unitary Products Group T ABLE 1 9: COOLING CAPACITIES FOR DJ3 00 AT 85°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 85 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 29 T ABLE 2 0: COOLING CAPACITIES FOR DJ3 00 AT 95° F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 95 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 30 Unitary Products Group T ABLE 2 1: COOLING CAPACITIES FOR DJ3 00 AT 105 °F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 105 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 31 T ABLE 2 2: COOLING CAPACITIES FOR DJ3 00 AT 1 15°F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 115 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-214 10-001- A-0502 32 Unitary Products Group T ABLE 2 3: COOLING CAPACITIES FOR DJ3 00 AT 125 °F RETURN AIR OUTDOOR AMBIENT TEMPERA TURE (°F): 125 CFM WB TEMP °F GROSS CAP ACITY 1 (MBH) INPU T POWER 2 (kW) GROSS SENSIBLE CAP ACITY 1 (MBH) (R ETUR N AIR DR Y BULB TEMP .
036-2141 0-001-A-0 502 Unitary Products Group 33 NOTES: 1. Blower perform ance include s fixed outdoor air, 2” T/A filters, a dry evapor ator coil and no ele ctric heat. 2. Refer to T a ble 13 f or addi tional static r esistanc es. ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-214 10-001- A-0502 34 Unitary Products Group NOTES: 1. Blower perform ance include s fixed outdoor air, 2” T/A filters, a dry evapor ator coil and no e lectric heat. 2. Refer to T a ble 13 f or addi tional static r esistanc es. ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-2141 0-001-A-0 502 Unitary Products Group 35 NOTES: 1. Blower perform ance include s fixed outdoor air, 2” T/A filters, a dry evapor ator coil and no ele ctric heat. 2. Refer to T a ble 13 f or addi tional static r esistanc es. ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-214 10-001- A-0502 36 Unitary Products Group NOTES: 1. Blower perform ance include s a gas-fired heat exch anger, fixed outdoor air , two-inch T/ A filters and a dry evaporat or coil. 2. Ref er to the ad diti onal S t atic R esi stance s table . ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-2141 0-001-A-0 502 Unitary Products Group 37 NOTES: 1. Blower perform ance include s a gas-fired heat exch anger, fixed outdoor air , two-inch T/ A filters and a dry evaporat or coil. 2. Ref er to the ad diti onal S t atic R esi stance s table . ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-214 10-001- A-0502 38 Unitary Products Group NOTES: 1. Blower perform ance include s a gas-fired heat exch anger, fixed outdoor air , two-inch T/ A filters and a dry evaporat or coil. 2. Ref er to the ad diti onal S t atic R esi stance s table . ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-2141 0-001-A-0 502 Unitary Products Group 39 NOTES: 1. Blower perform ance include s a gas-fired heat exch anger, fixed outdoor air , two-inch T/ A filters and a dry evaporat or coil. 2. Ref er to the ad diti onal S t atic R esi stance s table . ESP = E xternal Static Pressure ava ilable fo r the supp ly and retur n air duct system.
036-214 10-001- A-0502 40 Unitary Products Group T ABLE 31: BLOWER MOTOR AND DRIVE DA T A MODEL SIZE DRIVE BLOWER RANGE (RPM) MOT OR 1 ADJUST ABLE MOTOR PULLEY FIXED BLOWER PULLEY BEL T (NOTCHED) HP FRA ME EFF . (%) DESIG- NA TION OUTS ID E DIA. (IN. ) PITC H DIA.
036-2141 0-001-A-0 502 Unitary Products Group 41 T ABLE 3 4: DJ ELEC TRICAL DATA ~ 72.9 90 13.5 72.9 90 27.0 112.9 125 40.6 160.1 175 54.1 169.1 200 ~ 71.9 90 18.0 72.1 9 0 36.0 126.3 150 54.0 147.9 175 72.0 191.2 225 ~ 36.4 45 18.0 36.4 4 5 36.0 63.1 7 0 54.
036-214 10-001- A-0502 42 Unitary Products Group T ABLE 3 5: DJ VOL T AGE LIMIT A TIONS 1 VO L T AG E LIM IT A TIONS POWER SUPPL Y V O LTA G E MIN. MA X. VOL T AGE LIMI T A T IONS 208/ 230-3-60 187 253 460-3-60 414 506 575-3-60 518 630 1. Utilization Range “A” in accordance with ARI S tandard 1 10.
036-2141 0-001-A-0 502 Unitary Products Group 43 T ABLE 3 7: ELECTRIC HEA T CORRECTION F ACTORS NOMINAL VOL T AGE VOL T A GE kW CAP . M UL TIPLIER 208 208 1.
036-214 10-001- A-0502 44 Unitary Products Group NOTE: A 1” c learan ce mu st be p rovid ed betw een a ny com- bustibl e materi al and the s upply air duc twork for a d istan ce of 3 feet from the unit. NOTE: The product s of com bustion m ust not b e allo wed to accum ulate wi thin a confined spac e and r ecircu late.
036-2141 0-001-A-0 502 Unitary Products Group 45 NOTE: Units are s hip ped wi th the bo ttom d uct o penin gs oc ov- ered. An accessory flange kit is availab le for connect ing side duct s.
036-214 10-001- A-0502 46 Unitary Products Group FIGURE 6: UNIT DIMENSIONS DJ180, 210, 24 0 & 300 (RAI NHOOD) S U P P L Y A I R C O M P A R T M E N T P O W E R E X H A U S T R A I N H O O D ( o n .
036-2141 0-001-A-0 502 Unitary Products Group 47 FIGURE 8: FOUR AND SIX POIN T LOADS A D C E B F A D B C T ABLE 4 0: FOUR AND SIX POINT LOADS 180 Gas 2540 474 768 802 495 210 Gas 2928 510 954 954 510 .
036-214 10-001- A-0502 48 Unitary Products Group 1. The 2 ” sp ace b etween t he duct s allows for “jumping” an existi ng roof joist. 2. The 58-1/ 2” overall di mensi on of the duct s allows du ct- work penetrati on betw een roof joist s that are sp aced on 72” cent ers.
036-2141 0-001-A-0 502 Unitary Products Group 49 FIGURE 12: SIMPLICITY C ONTROL WIRING D IAGRAM W1 W2 Y1 G OCC P P1 Y2 X R SD C C SD SD R OCC C RC G Y2 Y1 W2 W1 Jumper Smoke Detector 24 VAC Class 2 X .
036-214 10-001- A-0502 50 Unitary Products Group GUIDE SPECIFICA TIONS GENERAL Unit s shall be manu facture d by Y ork Internationa l Un itary Product s Group in an ISO 9001 cert ified facili ty . Y ork's Sunline M agnum ™ units are co nvertible si ngle p ack- age unit s.
036-2141 0-001-A-0 502 Unitary Products Group 51 bearings , intern ally protec ted agai nst ove rload cond itions and stag ed indepe ndentl y . REFRIGERANT COMPONENTS Compresso rs: a. Shall be Scroll c ompresso rs inte rnally prot ected wi th inter nal high-pr essure relief and over temperatu re protecti on.
036-214 10-001- A-0502 52 Unitary Products Group UNIT OPERA TING CHARACTERISTICS Unit s hall be c apabl e of s tarti ng and run ning a t 125° F outdoo r te mper atur e, exce edi ng max imum l oad cri teri a of ARI S tandard 210/240 .
036-2141 0-001-A-0 502 Unitary Products Group 53 • TECHNICOA T PHENOLIC COA TED CONDENSER AND EV APO RA TOR COIL • ELECTRONIC SINGLE ENTHALPY ECONOMIZER • DIRTY FIL TER SWITCH • PHASE MONITOR .
036-214 10-001- A-0502 54 Unitary Products Group.
036-2141 0-001-A-0 502 Unitary Products Group 55.
Subject to change without not ice. Pri nted in U .S.A. Copyri ght © by Un itary Produ cts 2002. All rig hts reserved. Supersed es: Nothin g 036-214 10-001 -A-0502 Unit ary 5005 Norma n Product s Y or.
Ein wichtiger Punkt beim Kauf des Geräts York 300 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York 300 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York 300 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York 300 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York 300 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York 300 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York 300 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York 300. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York 300 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.