P ar t No . 550-110-641/0605 Read all instructions befor e installing Installer Leav e all instruct ions with boiler for futur e referenc e. An y cla ims for dam age or sh ortage in shi pment must be filed immediat ely agai nst the transpor tation co mpany by the c onsignee.
P ar t Number 550-110-641/0605 2 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Codes Installation must comply w ith all local codes, laws, regu lations and or dinanc es. Als o Un ited Stat es N ational Fuel Gas Code ANSI Z223.1-latest edition.
P ar t Number 550-110-641/0605 3 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Combustion air and ventilation openings Comb ustion air and ve ntilation openi ngs must compl y w ith Sec- tion 5.3, Air for Combustion and V entilation, of N ational Fuel Gas Code ANSI Z223.
P ar t Number 550-110-641/0605 4 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Chimney or vent requir ements (also refer to Breaching erection, P age 12) V enting must be insta lled acc ord ing to P ar t 7, V enting of Equipment, of N ational Fuel Gas Code, ANSI Z223.
P ar t Number 550-110-641/0605 5 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Boiler foundation Never i nsta ll b oile r o n co mbus tib le flo ori ng or carpeting , even if a concrete or aerated foundation is used. S ev ere personal injur y , death or substantial property damage can result.
P ar t Number 550-110-641/0605 6 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Figure 2a Minimum recommended pipe sizes (Supply and return sizes refer to minimum size of pipe connected to the boiler for 20°F temperature drop between supply and retur n.
P ar t Number 550-110-641/0605 7 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al U se circulators or zone valves in each circuit for multiple circuit applications. Filling the system 1. Clos e manual air vent s, drai n cock, and autom atic air vent, if used.
P ar t Number 550-110-641/0605 8 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Bypass piping Bypass piping is not normall y requi red on any baseboar d system. Bypass piping should be used for the following instal- lations. (Bypass, supply , and return piping should be same size.
P ar t Number 550-110-641/0605 9 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al External heat exchangers The PFG boiler can be used w ith a storage tank/heat ex changer unit for domestic hot water .
P ar t Number 550-110-641/0605 10 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al If boi ler is to be pr opa ne fir ed , a co n v ers ion kit must be used. Failure to use kit or to proper ly in stal l kit w ill result in se vere personal injur y , death or substantial property damage.
P ar t Number 550-110-641/0605 11 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Figure 5a Leak test valv e (model PFG-8 ONL Y) Figure 5 Gas supply piping.
P ar t Number 550-110-641/0605 12 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Draft hood installation Sec ure the draft hood to the ou tlet at the top of th e boil er with sheet metal screws. The bottom of the draft hood or “skirt” must hav e the clearance dimension above the jacket to p panel as indicated on the draft hood.
P ar t Number 550-110-641/0605 13 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Figure 6 T ypical wiring – zoning with zone v alves Wiring multiple zones Re fer to zone valve manufacturer’ s literature for wiring and application.
P ar t Number 550-110-641/0605 14 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al ❏ Check to make sure base insulation is secure. See "T o inspect base insulation," page 17.
P ar t Number 550-110-641/0605 15 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Also Refer to Ad ditional Instructions Shipped With The Boiler For Specific Contr ol Operation and T roubleshooting. V erify Proper Operation After Servicing.
P ar t Number 550-110-641/0605 16 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Suggested Minim um Ser vice Sc hedule for Qualified Service T echnician Only Beginning of each heating season: 1. Annual service call by a qualified serv ice agency .
P ar t Number 550-110-641/0605 17 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Check main burner flames: 1. Pr oper burner flame - Y ellow-orange streaks may appear - caused by dust. 2. Impro per flame a) Overfir ed - Flames large.
P ar t Number 550-110-641/0605 18 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Inspect venting system: 1. Check v enting syste m at least once a month during heating season. W ith boiler in operation (at least 5 minut es), hold a candle or match below lower edge of draft hood “skirt.
P ar t Number 550-110-641/0605 19 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Common problems and possible solutions.
P ar t Number 550-110-641/0605 20 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Item Description Part Number 1 Draft hood: PFG-5 (7” x 7” dia x 24.45”) PFG-6 (8” x 8” dia x 27.80”) PFG-7 (9” x 9” dia x 31.05”) PFG-8 (9” x 9” dia x 36.
P ar t Number 550-110-641/0605 21 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al.
P ar t Number 550-110-641/0605 22 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al Factory Fire T ested Insulated Ext ended Jack et Built-In Air Separator Draft Hood (Shipped in separat.
P ar t Number 550-110-641/0605 23 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al * Locate manual main Shu t-Off Gas V alve (where r equired) acc ording to local utility requir ements.
P ar t Number 550-110-641/0605 24 PFG S erieS 7 G aS - Fired W a ter B oiler — B oiler M anu al.
Ein wichtiger Punkt beim Kauf des Geräts Weil-McLain PFG-7 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Weil-McLain PFG-7 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Weil-McLain PFG-7 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Weil-McLain PFG-7 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Weil-McLain PFG-7 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Weil-McLain PFG-7 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Weil-McLain PFG-7 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Weil-McLain PFG-7. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Weil-McLain PFG-7 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.