INST ALLA TION AND OPERA TION INSTRUCTIONS BCP-3 Hydronic Multi-Stage Boiler Control Blue (Output 2) White (Output 3) Y ellow (Output 1) Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Ou.
2 BCP-3 Installation and Operation Manual thermostat is satisfied. Another, is a Setback input that will switch the heating system to a lower set point determined by the Set Back setting. T ype of Radiation in Building Reset Ratio Offset Radiators (Steel & Cast Iron) 1.
3 BCP-3 Installation and Operation Manual Mounting the Controller • The BCP-3 is designed to mount on a 1900 (4”x4”) deep electrical box. • If additional room is needed for wiring use the extension skirt provided. • Place the BCP-3 in an indoor convenient location near the unit to be controlled and away from excessive heat or cold.
4 BCP-3 Installation and Operation Manual IMPORT ANT Determining the proper location for the Outdoor Sensor is very important. The BCP-3 will base the heat on the outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice, its reading will be different from the actual outdoor temperature.
5 BCP-3 Installation and Operation Manual Output Mode T able Output Mode Description Output 1 (Y ellow Wires) Output 2 (Blue Wires) Output 3 (White Wires) Notes 1-On/Off+1-Pump One On/Off boiler and a.
6 BCP-3 Installation and Operation Manual T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24V AC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer 120 V AC Wiring 1 Lo/Hi Boiler + System Pump Sy.
7 BCP-3 Installation and Operation Manual Weil McLain V1.00 (c) 2008 BCP-3 Boiler Control Loading Default Values... DISPLAY UNIT: F C SENSOR FAULT: Output On Output Off SETUP COMPLETE! PRESS SET Startup Menu SYSTEM= 68 F TARGET= 150 F ------MAIN------ Set Point 170 F <Out.
8 BCP-3 Installation and Operation Manual Button and Navigating Menus The BCP-3 has three buttons. • The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When in the Menus and settings, the SET Button accepts the selected entry or setting value.
9 BCP-3 Installation and Operation Manual Outdoor Reset Mode • When Output-On is selected, the BCP-3 will energize all boiler and system relays when the System reads SHORT or OPEN and Outdoor is below Outdoor Cutoff. Thus, all boilers will run on their limits.
10 BCP-3 Installation and Operation Manual • If required: Adjust the RESET RA TIO in cold weather . If the ambient building temperatures are too cold in cold weather , move the ratio to a higher selection. That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.
11 BCP-3 Installation and Operation Manual Minimum T arget (A vailable when Startup Control Mode = Outdoor Reset) Options: From 70 º F/21 ºC to 170 º F/77 ºC Default: 140 º F/60 ºC SET SET /Set Point/<Out. Reset>/Min. Tgt • The Minimum T arget T emperature must be set to the boiler manufacturer ’ s specification.
12 BCP-3 Installation and Operation Manual Minimum Runtime Options: 1 to 60 minutes Default: 2 minutes SET SET /<Settings>/<Stage>/Min. Runtime • This is the minimum amount of time any stage will run. • The Minimum Runtime for the lowest firing stage on a boiler starts after the purge cycle.
13 BCP-3 Installation and Operation Manual Domestic Hot W ater (DHW) Priority Options: NO and From 1 min to 120 min Default: NO SET SET /Settings>/DHW Prior . DHW Priority: 60m • The DHW Priority , with a value set to other than NO, provides the user with an adjustable DHW priority timer for the domestic hot water call.
14 BCP-3 Installation and Operation Manual T roubleshooting No Display or LED Lights Check the power to the BCP-3. The BCP-3 requires 120V AC power to the Black wires or 24V AC to the right-most terminals. T urn the power off and back on to restore the display .
15 BCP-3 Installation and Operation Manual Boiler1 DHW Indirect Building Heat System Sensor Outdoor Sensor T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24VAC } System Sensor } Outdoor Sensor } DHW Call D.
16 BCP-3 Installation and Operation Manual 500 Blaine Street Michigan City , Indiana 46360 219-879-6561 http://www .weil-mclain.com HT #059075-00 A Specifications V oltage Input: . . . . . . . 120 V AC 60 Hz(2 Black wires) /24V AC 60 Hz (24V Ac terminals) (Only One Power Source) Power Consumption: .
Ein wichtiger Punkt beim Kauf des Geräts Weil-McLain BCP-3 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Weil-McLain BCP-3 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Weil-McLain BCP-3 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Weil-McLain BCP-3 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Weil-McLain BCP-3 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Weil-McLain BCP-3 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Weil-McLain BCP-3 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Weil-McLain BCP-3. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Weil-McLain BCP-3 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.