P ar t No . 550-110-260/0508 This manual must only be used by a qualifi ed heating installer/serv ice tec hnician. Bef ore installing , read all instructions, including this manual, the burner manual and any relat ed supplements. P erform steps in the order given.
Part number 550-110-260/0508 2 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual How it works . . . ① Control module The control module r esponds to signals from the room thermostat, air pressure switch and boiler limit circuit to operate the boiler cir culator , pilot burner , gas val ve and inducer .
Part number 550-110-260/0508 3 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual GOLD CGs Gas-Fir ed Induced-Draft W ater Boiler.
Part number 550-110-260/0508 4 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Contents Hazar d defi nitions The following defi ned terms are used throughout this manual t o bring attention to the presence of hazards of various risk le v els or to important infor mation co ncerning the life of the product.
Part number 550-110-260/0508 5 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Please r ead befor e pr oceeding Installer Read all instr uctions befor e in- stalling. Follo w all instructions in proper order to pr event personal injur y or death. • Also r efer to CGs V enting Supplements .
Part number 550-110-260/0508 6 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Prepare boiler location — codes & checklist 1a Installations must follow these codes: • Local, state, provincial, and national codes, laws, regulations and ordinanc es.
Part number 550-110-260/0508 7 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Pr epar e boiler location — clearances 1b Figure 2 Required MINIMUM clearances Figure 1 Recommended SER VICE clearances (see W ARNING below) Recommended SERVICE clearances (Fig.
Part number 550-110-260/0508 8 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Pr epar e boiler location — vent system 1c F ailure to follo w all instr uctions can result in fl ue gas spillage and carbon mono xide emissions, causing sev ere personal injur y or death.
Part number 550-110-260/0508 9 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Pr epar e boiler location — contamination 1d T able 1 Corrosive or destructive contaminants and likely locations T o prevent potential of severe personal injur y or death, check for products or ar eas listed below befor e installing boiler .
Part number 550-110-260/0508 10 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Pr epar e boiler location — air openings 1e Special considerations Tight construction ANSI Z223.
Part number 550-110-260/0508 11 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Figure 3 Sizing air openings for CGs installations ✷.
Part number 550-110-260/0508 12 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Place boiler/crate near position 1. Leav e boiler in crate and on pallet until installation site is read y . 2. M ove entir e crate and pallet next to selected loca- tion.
Part number 550-110-260/0508 13 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Pr epar e boiler — pr essure test 2b Hydr ostatic pressur e test Pr essure test boiler bef or e attaching water or gas piping (ex cept as noted belo w) or electr ical supply .
Part number 550-110-260/0508 14 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual W ater piping — general information 3a T able 3 W ater pipe size (based on 20°F rise) General piping information If installation is to comply with ASME or Canadian requir ements, an ad- ditional high temperat ure limit is needed.
Part number 550-110-260/0508 15 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Water piping — single-zone system 3b Figure 4 Diaphragm- or bladder -type expansion tank Piping to single-zone system See T able 3 for piping sizes. Figure 5 Closed-type expansion tank Piping to single-zone system See T able 3 for piping sizes.
Part number 550-110-260/0508 16 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual W ater piping — multiple zones 3c Piping multiple zones Follo w instructions on pages 14 and 15 to install near- boiler or single-zone piping. (Also r efer to Piping for radiant heating syst ems or conv ert ed gravity sys- tems , below , if applicable.
Part number 550-110-260/0508 17 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Figure 6 Zoning with circulators — return water 130°F or higher .
Part number 550-110-260/0508 18 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Piping — low temp systems 3d Failure to prevent low return water temperature t o the boiler c ould cause corrosion of the boiler sections or burners, r esulting in severe personal injury , death or substantial property damage.
Part number 550-110-260/0508 19 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 1 Boiler isolation (balancing) valves 2 Flow/check valv e 3 System or zone circulat or 4 Syst em temperature gauges 5.
Part number 550-110-260/0508 20 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Failure to prevent low return water temperature t o the boiler c ould cause corrosion of the boiler sections or burners, r esulting in severe personal injury , death or substantial property damage.
Part number 550-110-260/0508 21 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 1 Boiler isolation (balancing) valves 2 Flow/check valv e 3 System or zone circulat or 4 Syst em temperature gauges 5.
Part number 550-110-260/0508 22 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Failure to prevent low return water temperature t o the boiler c ould cause corrosion of the boiler sections or burners, r esulting in severe personal injury , death or substantial property damage.
Part number 550-110-260/0508 23 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 3 System or z one circulator 7 System t emperature valves (see instructions to the left for adjusting valv es) 8 Blen.
Part number 550-110-260/0508 24 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Venting and combustion air 4 CGs Boiler must be vented and supplied with combus- tion and ventilation air as described in W eil-McLain CGs V enting Supplements packed in env elope as- sembly with boiler .
Part number 550-110-260/0508 25 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Gas piping 5 26020 Manual main shutof f gas valve (when required) Ground joint union (when required) Nipple Te e Cap T able 4 Pipe capacity for 0.60 specifi c gravity natural gas Natural Gas: 1.
Part number 550-110-260/0508 26 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Field wiring 6 Thermostat 1. Connect thermostat as shown on wir ing diagram on boiler . 2. Install on inside wall away from in fl uences of draf ts, hot or cold wat er pipes, lighting fi xtur es, television, sunra ys, or fi replaces.
Part number 550-110-260/0508 27 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Start-up — pr eparation 7a Fill the system with water 1. Close manual and aut omatic air vents and boiler drain cock. 2. Fill to correct system pressure . Co r- rect pressur e will var y with each application.
Part number 550-110-260/0508 28 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Start-up — operate boiler 7b Inspect system water piping After fi lling the boiler and system with water , inspect all piping throughout the system for leaks. If found, repair immediately .
Part number 550-110-260/0508 29 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Start-up — operate boiler (continued) 7b Figure 16 T ypical pilot bur ner fl ame Figure 17 T ypical main bur ner fl ame Check bur ner fl ames V iew pilot and main fl ames through the inspection port in the A ir inlet box fr ont cov er .
Part number 550-110-260/0508 30 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Check-out pr ocedur e — checklist 8 ❏ Boiler and heat distribution units fi lled with water? ❏ A utomatic air .
Part number 550-110-260/0508 31 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Operation — sequence 9a Figure 18 Control module sequence of operation — status light indications 1. Read appr opr iate Operating instr uctions in Section 9c . This information is also located on a label on the inside of the boiler jack et door panel.
Part number 550-110-260/0508 32 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Operation — wiring diagrams 9b Figure 19 Schematic wiring diagram.
Part number 550-110-260/0508 33 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Figure 20 Ladder wiring diagram.
Part number 550-110-260/0508 34 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 9c Operating instructions CGs-3 to CGs-6 • Spark pilot • Natural or propane gas • Gas valve: Honeywell VR8204/V.
Part number 550-110-260/0508 35 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Operating instructions CGs-3 to CGs-6 • Spark pilot • Natural or propane gas • Gas valve: White-Rodg ers 36E 9c.
Part number 550-110-260/0508 36 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 9c Operating instructions CGs-3 to CGi-6 • Spark pilot • Natural or propane gas • Gas valve: White-Rodg ers 36C.
Part number 550-110-260/0508 37 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T able 5 Service and maintenance schedules Service and maintenance — schedule 10a Service technician (see following.
Part number 550-110-260/0508 38 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Service & maintenance — annual start-up 10b Air openings 1. V erify that combustion and ventilation air openings to the boiler room and/or building ar e open and unobstr ucted .
Part number 550-110-260/0508 39 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual ❏ Inspect . . . Burners, base and inlet air box The boiler contains c eramic fi ber and fi berglass materials. U se care when handling these materials per instructions on page 68 of this manual.
Part number 550-110-260/0508 40 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Service & maint. — annual start-up continued 10b ❏ Check/test . . . Gas piping 1. Sniff near fl oor and around boiler area for an y in- dication of a gas leak .
Part number 550-110-260/0508 41 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Safety relief valv es should be reinspected A T LEAST ONCE EVER Y THREE YEARS , by a licensed plumbing c ontr actor o.
Part number 550-110-260/0508 42 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Service & maint. — annual start-up 10b ❏ Review with owner 1. Review the User’ s Information Manual with the ow ner. 2. Emphasize the need to perform the maintenance schedule specified in the User’ s Information Manual (and in this manual as well).
Part number 550-110-260/0508 43 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — pr ocedur e 11a Label all wires prior to disconnection when serv icing co ntrols.
Part number 550-110-260/0508 44 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — air pr essur e switch 11b Air pr essure switch Mak e sure boiler water t emperature is 100 °F or cooler before starting procedur e to obtain appropriate readings.
Part number 550-110-260/0508 45 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module 11c Contr ol module Solder or wat er splatter between plugs and circuit boar d can cause improper operation of control module. Place a shield ov er the boiler internal controls and c omponents during installation.
Part number 550-110-260/0508 46 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module (continued) 11c Figure 25 Control module connections.
Part number 550-110-260/0508 47 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module lights 11d CHART 1 — Troubleshooting POWER light status Electrical shock haza rd — Wherever you se e ▲ TURN OFF POWER ▲ , follow the instructions.
Part number 550-110-260/0508 48 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module lights 11d Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instructions. Failure to follow instructions could result in severe personal inju ry, death or substantial property damage.
Part number 550-110-260/0508 49 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module lights (cont.) 11d CHART 3 — PRESS SWITCH & POWER lights flashing Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instruction s.
Part number 550-110-260/0508 50 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 11d T r oubleshooting — contr ol module lights (cont.) • Turn off power to the boiler at service switch or breaker. • Wait at least 45 seconds. • Turn on power to boiler.
Part number 550-110-260/0508 51 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module lights (cont.) 11d • ▲ TURN OFF POWER ▲ to boiler at service switch or breaker. • Remove air inlet box cover (see Figure 27 , page 56 for location).
Part number 550-110-260/0508 52 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual 11d T r oubleshooting — contr ol module lights (cont.) CHART 6 — PRESS SWITCH light flashing and POWER light on steady Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instruction s.
Part number 550-110-260/0508 53 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual T r oubleshooting — contr ol module lights (cont.) 11d CHART 7 — Insufficient heat or no heat to system ( POWER light on steady) Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instructions.
Part number 550-110-260/0508 54 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Replacement parts 12a Section assembly .............................................. 55 Base .................................................................. 56 Jacket .
Part number 550-110-260/0508 55 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Replacement parts — section assembly 12b Item number Description Weil-McLain part number 1 End section, left hand, .
.
Part number 550-110-260/0508 57 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Replacement parts — base (continued) 12c I t em De sc rip t ion Weil-M c L a in p a r t number B a se i nsul a t i .
Part number 550-110-260/0508 58 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Replacement parts — jacket 12d Figure 28 Jacket assembly.
Part number 550-110-260/0508 59 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Boiler Model 1 2 3 4 5 6 Boiler Model Junction box, 2 x 4 Panel, left side , with insu lation Panel, right side , wit.
Part number 550-110-260/0508 60 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Replacement parts — trim 12e Figure 29 T rim assembly I t em number De sc rip t ion M a nuf act urer M a nuf act ur.
Part number 550-110-260/0508 61 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Replacement parts — contr ols 12f Figure 30 Gas control assembly I t em number De sc rip t ion M a nuf act urer M a.
Part number 550-110-260/0508 62 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Dimensions 13a Figure 31 Dimensional drawing Boiler model number Supply tappin g (inches NPT) Return tappin g (inches.
Part number 550-110-260/0508 63 GOLD CGs Gas-Fired W ater Boiler — Boiler Manual Ratings T able 7 Boiler ratings DOE 13b (N ote 5) CGs boilers for residential radiant panel systems, con ver ted grav.
64 Part Number 550-110-260/0508 GOLD CGs Gas-F ired Water Boiler — Boiler Man ual Handling ceramic fi ber and fi ber glass materials REMOV AL OF COMBUSTION CHAMBER LINING OR BASE P ANELS The combustion chamber lining or base insulation panels in this prod- uct contain c eramic fi ber materials.
Ein wichtiger Punkt beim Kauf des Geräts Weil-McLain 550-110-260/0508 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Weil-McLain 550-110-260/0508 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Weil-McLain 550-110-260/0508 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Weil-McLain 550-110-260/0508 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Weil-McLain 550-110-260/0508 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Weil-McLain 550-110-260/0508 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Weil-McLain 550-110-260/0508 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Weil-McLain 550-110-260/0508. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Weil-McLain 550-110-260/0508 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.