RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 1 FM 4/08 Configuring the EZ-ZONE ® RUI/Gateway 1.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 2 FM 4/08 3. Some notables regarding the graphic above. In the steps that follow we are going to focus on four of the prompt s shown: a.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 3 FM 4/08 9. Provide a name for the channel. 10. In this example the device driv er selected will be “Modbus Ethernet”.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 4 FM 4/08 11. Select the appropriate hardware (network adapter) used on the network.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 5 FM 4/08 13. The next selection allows for multiple master s on the network.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 6 FM 4/08 15. Once the channel configuration is complete it is now time to configure a device (RUI/Gateway).
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 7 FM 4/08 17. Recall that in steps 1-3 it was said that there ar e other configuration st eps that need to be addressed that are not covered in this paper.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 8 FM 4/08 19. If communications fail between KEPServer EX and RUI/Gateway stop polling device.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 9 FM 4/08 21. Use the defaults for port number and IP protocol.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 10 FM 4/08 23. The graphic below sh ows the default Modbus ® word order which also represents the default Modbus ® word order for the RUI/Gateway (Low/High).
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 11 FM 4/08 25. KEPServerEX allows for impor ted tags via a text file.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 12 FM 4/08 27. This concludes the device (RUI/Gateway) configuration.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 13 FM 4/08.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 14 FM 4/08 30. To create similar tags for PV2 - PV4 simply click on the duplicate ic on (circle) and change the fields accordingly (squares).
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 15 FM 4/08 said, look closely at the addresses given in defining the CLSP for each of the four PM controls.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 16 FM 4/08 34.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 17 FM 4/08 36.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 18 FM 4/08 38. Changing an element in the assembly is EZ. A new tag was created as shown below.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 19 FM 4/08 39.
RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 20 FM 4/08 42.
Ein wichtiger Punkt beim Kauf des Geräts Watlow Electric RUI/Gateway (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Watlow Electric RUI/Gateway noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Watlow Electric RUI/Gateway - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Watlow Electric RUI/Gateway reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Watlow Electric RUI/Gateway erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Watlow Electric RUI/Gateway besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Watlow Electric RUI/Gateway verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Watlow Electric RUI/Gateway. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Watlow Electric RUI/Gateway gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.