CTV -PRC0 0 1 -GB September 2004 Centrifugal W at er Chillers Model CVGF W at er -Cooled Her metic Centr ifugal Refrigeration Capacities From 40 0 to 1 00 0 T ons (1400 kW -351 0 kW) 50 and 60 Hz.
CTV -PRC0 01 -GB © 2004 American Standard Inc. All rights reserved. Introduction Intr oducing T r ane’ s Model CV GF Centr ifugal W ater Chiller Introduction The basic gear driven centrifugal water chiller design was introduced in 1976 and has been proven in thousands of installations.
3 CTV -PRC0 0 1 -GB Introduction Features and Benefits Application Considerations General Data Jobsite Connections Controls Physical Dimensions Mechanical Specifications Con version T able Contents 2 .
CTV -PRC0 01 -GB 4 Environmental Features and Benefits Improved Efficiency: • High Ef ficiency: 0.55 kW/T on at ARI conditions • Motor cooling vented to economizer cycle, efficiency advantage • .
5 CTV -PRC0 0 1 -GB Features and Benefits Microprocessor Controls with CH530 DynaV iew Operat or Interf ace DynaVi ew ™ is the unit-mounted control panel and also serves as the main processor and operator interface. It has a touch-sensitive overlay on a 1/4 V GA display .
CTV -PRC0 01 -GB 6 Features and Benefits Serviceability Previous T rane c hiller controller s included a user interface that presented all chiller data necessary for both daily tasks and service or maintenance tasks. The amount of information presented on a limited display made a number of tasks dif ficult.
7 CTV -PRC0 0 1 -GB Features and Benefits Feedf orwar d A daptive Control The T racer c hiller controller allows the system designer to explore energy saving strategies and allows the centrifugal chiller to be used in ways that were never thought possible.
CTV -PRC0 01 -GB 8 • Communication capabilities: several communication levels are provided: — local, through a PC workstation keyboard. Summit can be programmed to send messages to local or remote workstations and or a pager in the following cases: — Analog parameter exceeding a programmed value.
9 CTV -PRC0 0 1 -GB T w o-Stage Compr essor Widens the Application Range Why Centrifugal Compressors Surge Centrifugal compressors produce their pressure differential (head) by converting the kinetic energy of the gas leaving the impeller into static pressure.
CTV -PRC0 01 -GB 10 Condenser W at er Limitations Te m p e r a t u r e T rane centrifugal c hiller s star t and operate over a range of load conditions with controlled water temperatures. Reducing the condenser water temperature is an effective method of lowering the chiller power input.
11 CTV -PRC0 0 1 -GB General Data T able GD-1 – Model CV GF Descr iption Model CVGF Nominal Cooling Capacity NTON 400 500 500 650 800 1000 Heat Exchanger Size Evaporator EVSZ 500 500 7 00 700 1000 1.
CTV -PRC0 01 -GB 12 T able GD-3 – Evaporator and Condenser Flow rates (Minimum and Maximum, liters per second, gallons per minute) High Efficiency Shells - 0.
13 CTV -PRC0 0 1 -GB Jobsite Connections Supply and Motor Lead Wiring and Connections Copper conductors only should be connected to the compressor motor due to the possibility of galvanic corrosion as a result of moisture if aluminum conductors are used.
CTV -PRC0 01 -GB 14 Controls Standard Features Field Connection The field-connected elements are involved in physically turning the chiller on or off. This involves ensuring that the chiller is not in an emergency or external stop condition, starting the pumps, and verifying that flow has been established.
15 CTV -PRC0 0 1 -GB Extended Operation Package Select the extended-operation package for chillers that require external , hot water control, and/or base-loading capabilities. This package also includes a 4-20 mA or 0-10 Vdc analog input for a refrigerant monitor .
CTV -PRC0 01 -GB 16 Controls Standard Protections T r acer ™ Chiller Contr oller The chiller controller uses proportional- integral-derivative (PID) control for all limits—there is no dead band. This removes oscillation above and below setpoints and extends the capabilities of the c hiller .
17 CTV -PRC0 0 1 -GB Controls Standard Protections Momentary Power Loss and Distribution Fault Protection Three-phase momentary power loss (MPL) detection gives the chiller improved performance through many different power anomalies. MPLs of 2.5 cycles or longer will be detected and cause the unit to shut down.
CTV -PRC0 01 -GB 18 Figure PD-2 – Model CVGF Cooling Only Without Unit Mounted Start er (for Remote Mount ed Starter) Figure PD-1 – Model CVGF Cooling Only With Unit Mounted Star ter Physical Dime.
19 CTV -PRC0 0 1 -GB Physical Dimensions Ev aporator Wa ter Bo x Length — SI (English) Length No. mm (in) Shell Pressure Evap. Passes Supply Return 500 10 bar (150 psig) NMAR 2 371 (14.61) 156 (6.14) 10 bar (150 psig) NMAR 3 371 (14.61) 371 (14.61) 700 10 bar (150 psig) NMAR 2 489 (19.
CTV -PRC0 01 -GB 20 The T rane CVGF pac k aged centrifugal water chillers using HFC-134a refrigerant consist of a hermetic two stage, gear -dri ve centrifugal compressor , evaporator, condenser , interstage economizer , unit-mounted microprocessor based control panel and compressor motor star ter .
21 CTV -PRC0 0 1 -GB W elded steel two pass water boxes are bolted to the tube sheets. W ater connections are steel pipe stubs grooved for V ictaulic couplings; flanged connections are optionally available. Maximum waterside working pressure of 10.5 bars (150 psi) is standard.
CTV -PRC0 01 -GB 22 Unit-mounted or remote-mounted starters for Europe (CE mark) will be star -delta, solid-state, across-the-line, primary reactor , and auto transformer only in a IP 20 enclosure. A steel panel door with optional mechanical interlock disconnects the system when the door is opened (required for CE listing).
23 CTV -PRC0 0 1 -GB Conversion T able T o Convert Fr om: T o: Mulgpiy By: Length Feet (ft) meters (m) 0.30481 Inches (In) millimeters (mm) 25.4 Arca Square Feet (ft 2 ) square meters (m 2 ) 0.093 Square Inches (In 2 ) square millimeters (mm 2 ) 645.2 V olume Cubic Feet (ft 3 ) Cubic meters (m 2 ) 0.
www .trane.com For more information, contact your local district office or e-mail us at comfort@trane.com T rane has a policy of continuous product and product data improvement and reserves the right to c hange design and specifications without notice.
Ein wichtiger Punkt beim Kauf des Geräts Trane CVGF (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Trane CVGF noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Trane CVGF - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Trane CVGF reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Trane CVGF erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Trane CVGF besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Trane CVGF verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Trane CVGF. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Trane CVGF gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.