TIC-LF414C Introduction The electromagnetic flowmeter uses Faraday’s Law of electromagnetic induction to measure the process flow. The device consists of two units: a detector, through which the flu.
TIC-LF414C 2 Power consumption: 17W(27VA) or less 19W(29VA) or less (with PROFIBUS) Conformance to European Co mmunity Directives: EMC directive 89/336/EEC The low voltage 93/68/EEC PED 97/23/EC (Note 1) Note : See Table 1 for detail.
TIC-LF414C 3 Digital input DI (opt.) Signal type: 20 to 30Vdc voltage signal Input resistance: 2.7k Ω Number of inputs: one point DI function — One of the following functions can be assigned to the optional DI signal. Range switching — Selects either the higher or lower range in the unidirectional or bidirectional 2-range setting.
TIC-LF414C 4 Conditions when power fails: Parameter setting values are stored in non–volatile memory and the values will be restored when the power r eturns to normal condition.
TIC-LF414C 5 Installation Dimensions Unit : inch( mm) L1 Φ D1 (L2 ) 2. 5 2 ( 64 ) 5.63( 143) 1.42 ( 36) 8.86 ( 225) 5.16( 131) ANSI class 150 and class 300 dimensions: Meter size (inch) L1 (inch) L2 (inch) D1 (inch) Weight (lb) 1/2 2.76 9.92 1.93 approx.
TIC-LF414C 6 Unit : inch(mm) (L2 ) L1 8.86( 225) 5.63 ( 143) 1.42( 36) 5.16( 131 ) Φ D1 Note1: Eye bolts are provided at the top fo r flow mete rs sized 8"(200mm). Note2: 1 inch = 25.4mm ANSI class 150 and class 300 dimensions Meter size (inch) L1 (inch) L2 (inch) D1 (inch) Weight (lbs) 1-1/2 3.
TIC-LF414C 7 Unit : inch(mm) R ( P T ) 1/2Male S c r e w ( T w o Pl a c e s) 3.46( 88) 1.57 ( 40 ) 4.96 ( 126 ) 3.58 ( 91 ) 1.38( 35) (L2 ) Φ 1.93( Φ 49) 2.52( 64 ) L1 Note1: Cable glands are not provide d for LF414 of FM and CSA appr oved type. Refer to the part of Cable connection port at detector.
TIC-LF414C 8 Unit : inch(mm) 3.46(88) 1.57 ( 40 ) 4.96(126) 1.38(35) 3.58(91) R(PT)½ Mal e Screw (T wo places) (L2) Φ 2.60( Φ 66) 3.43 ( 87 ) L1 Note1: Cable glands are not provide d for LF414 of FM and CSA appr oved type. Refer to the part Cable c onnection port at detector.
TIC-LF414C 9 Unit : inch(mm) 3.46( 88) 1 .57 ( 4 0 ) 4.9 6( 126) 1. 38 ( 3 5 ) 3.58(91) R( PT )½M a le Sc r e w ( T w o p l a c e s ) (L 2) L1 Φ D1 Note1: Cable glands are not provide d for LF414 of FM and CSA appr oved type. Refer to the part of Cable connection port at detector.
TIC-LF414C 10 矢視 A 信号ケ ー ブ ル グラ ン ド 電源ケ ー ブ ル グ ラ ン ド 封止栓 励磁 ケ ー ブ ル グ ラ ン ド 電流出力ケ ー ブ ル グ ラ ン ド 接地端子 (M 4 ) 取付金具 4 - φ 11 取付金具 82 (3 6 ) 1 5 6 1 3 1 51 178 20 0 1 51 74 ± 0 .
TIC-LF414C 11 ・ Separate type LF410/LF612 and LF414/LF612F flowmeters T erminal board Connected detecto r IV wire 5.5 mm 2 or more Power switch (External double- pole power switch ) Thick walled ste.
TIC-LF414C 12 Wiring Precautions (1) Explosion proof type flow meters are not provided cable glands. Refer to the part Cable connection port at detector and converter. (2) Connect the grounding wire (IV wire 5.5mm² or more) to a good earth ground (100 Ω or less ground resistance).
TIC-LF414C 13 Meter Size To select the meter size: See Table 3 to 4 and find meter sizes within the velocity of 0.3 to 32.8 ft/s (0.1 to 10m/s) for a specified full-scale (measuring range high limit) flow. Select one that has its full-scale velocity between 3.
TIC-LF414C 14 Table 6. Specification Code (Waf er type detector LF410 Series) Detector ca tegory Model Specific ation Code Normal type Ex. type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Description Gr.
TIC-LF414C 15 Table 7. Specification Code for converter s Model Specific ation Code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Contents L F 6 1 Elec tromagnetic flowmeter c onverter LF610 type LF612 type 0 Comb.
TIC-LF414C TIC-LF414C Specifications are subject to change without notice. Printed in Japan 2008-6 (TDOC) © TOSHIBA Corporation 2008 All Rights Reserved. http://www.toshiba.com/ind / Misuse of this product can result in damages to property or hum an injury.
Ein wichtiger Punkt beim Kauf des Geräts Toshiba TIC-LF414C (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Toshiba TIC-LF414C noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Toshiba TIC-LF414C - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Toshiba TIC-LF414C reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Toshiba TIC-LF414C erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Toshiba TIC-LF414C besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Toshiba TIC-LF414C verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Toshiba TIC-LF414C. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Toshiba TIC-LF414C gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.