TOSHIBA I NSTRUCTI ON MANUAL CURRENT RELAY RC803A-HP1 TOSHIEA CORPORATION.
- TOSHIBA 6F9E0090 CONTENTS 1. General Descrigtion __-----_-__----____--------------------- 2 2. Check Before Using -__-----__-_---_-_______________________- 2 2.1 External Amearance -_-_-_---_-__-__-_---------------- 2 2.2 Specifications _--_---_-__-__--_-__------------------- 3 3.
- =rosHl=A 6F9E0090 Please thoroughly read this instruction manual before using the RC803A Current SensinD Relay. 1. General DescriDtion This current relay is designed to detect current in AC circuits with a wide range of aDDiications, e.t., detection of abnoraai current of VariOUS electrical eauiment due to overloads or broken circuits (e.
TOSHIBA 6F9EO090 2.2 Specifications _____________-_-________________________------------------------------ ITEH Rated Current Range of current sensing Inout circuit voltage Type of Current ReSDOnSe delay time-adjustable range Detection delay tile-adjustable range Operating volt.
- TOSHIEA 6F9E0090 ITEH Ambient temp. range Temp. error Dielectric with- stand voltage Imgulse with- stand voltage Insulation resistance Vibration -Oscillation -1aoulse Overcurrent intensity Output contact rating (250VAC aax. I SPECIFICATIORS -10 - *SO% +10X at t30Y Between terminals and ground 2DOOVAC for 1 #in.
- TOSHIBA 6F9E0090 WEHA AC Rating Designation B300 Inductive load t-K&- 120 AC 240 24 DC 120 240 ITEH SPECIFICATIONS Hysteresis AgDrox. 10X of ooerating value. Power consumption oDperating Power 3.5VA olnput Circuit D.lVA (when 5A is applied) Height .
TOSHIBA 6F9E0090 Detection delay .I .pL1 mrellt 4 0 level (0.3-O.b5A) Undercurrent detect img FiD. 1 Characteristics 1. APDl ication 4.1 Overcurrent Detection on Hotors An aDDlication example Is shown in Fig.
TOSHIBA 6F9Eoo90 the uotor from being damaged. If the detected current is above !iA. and in case of a high voltage circuit, use an external CT and connect the secondary side of CT to the relay as show.
- TOSHIBA 6F9E0090 further, when this relay is used in a uotor circuit, the detection delay timer should be set lonfler than the startinv time (about 120%) so that this relay is not actuated by inrush current. If current flowinp in the uain circuit becomes abnormal after the tiee Deriod of the detection delay timer has elapsed.
TOSHIBA 6F9EOO90 ACJ-Phase Power SUDDIY Current relay Note: The RC803’s outDut contacts are shown with Dower source aDDl ied. Fig. 3 Application Example 4.3 Limiting Startino current of Rotors Many eotors of uediua and large capacity use a aethod to start by limiting starting current.
ToSHIEA 6F9EOO90 4.4 Transformers To use this current relay for detecting overcurrent on transformers. it is necessary to set the detection delay tiler with the inrush current of transforeer taken into consideration.
TOSHISA 6F9E0090 50 3-$7 Hole 7 z Hountino holes Fig. 4 Dimensions B !3 t. - ll-.
TOSHIBA GF9EOO90 6. AdjustDents 6.1 Current setting (1) When detected current is in a range of 0.5 - 5A: After confirming that the current value under noraal load condition is in a range of 0.5 - SA, set the current adjusting knob to the desired detecting value.
- TOSHIEA 6F9Eoo9o 6.3 Setting the ResDonse delay time Adjust the set tile according to the ourgose of detection (I.e. overcurrent or undercurrent). The set tire for the resoonse delay varies ger aDDllcation. Host applications cay not need any delay tile.
TOSHIBA 6F9E0090 (4) When the Dower source is aDDlied. the relay is excited and the OutDut contact’s states are reversed. The relationshiD between the input signal end the outDut contacts are shown in Table 2. Check this relationship during the test.
TOSHIBA 6F9E0090 (b) When undercurrent or disconnection is detected At the sale time the lain circuit switch is turned OH, the starting current and rated current flows, and the relay is picked U P . If current drODS below the undercurrent set point, the undercurrent State is detected and the relay drops out.
TOSHIBA 6F9E0090 (6) If the relay does not operate in the above test, check if the current setting is correct or if the ingut signal is above the set detection value. If the ingut signal is correct, check the operation of the relay by gradually reducing the setting of the current adjusting knob.
- TOSHIBA 6F9E0090 8. Cover Reroval To adjust the current and time settings the cover must be raaoved. Reaove the cover by amlYing a force in the direction of the arrow as shown below.
- TOSHIBA CORPORATION.
Ein wichtiger Punkt beim Kauf des Geräts Toshiba RC803A-HP1 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Toshiba RC803A-HP1 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Toshiba RC803A-HP1 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Toshiba RC803A-HP1 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Toshiba RC803A-HP1 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Toshiba RC803A-HP1 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Toshiba RC803A-HP1 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Toshiba RC803A-HP1. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Toshiba RC803A-HP1 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.