No. EJL-114B Introduction The electromagnetic flowmeter uses Faraday’s Law of electromagnetic induction to measure the process flow. The device consists of two units: a detector, through which the f.
LF410/LF600 LF410/LF602 2 Fluid conductivity: 5µS/cm minimum Fluid temperature: –10 to +180 ° C : Ceramic type (14 to 356 ° F) Note : 120 ° C (248 ° F) above is separate type –10 to +120 ° C.
LF410/LF600 LF410/LF602 3 totalizer. Fixed-value outputs — Outputs fixed-values for current and pulse outputs. Zero adjustment — Executes zero adjust ment (on-stream at zero flow rate). Output signals Current output: 4–20mAdc (load resistance 0 to 750 Ω ) Note: The current output cannot be used with the PROFIBUS-PA ccommunication.
LF410/LF600 LF410/LF602 4 Cable connection ports: Cable glands — LF600 and LF602 without cFMus Approval: Provided as standard OD of cable φ 11 ~ 13mm Material Nylon 66 G (PF) 1/2 male screws. Note: When PROFIBUS option is specified , cable grands size is φ 6 ~ 8mm for signal cable, φ 11 ~ 13mm for power cable.
LF410/LF600 LF410/LF602 5 Installation Dimensions Unit : mm L1 Φ D1 (L2) 64 143 (35) 225 131 BS16, DIN PN16 and JIS 10K dimensions: Meter size (mm) L1 (mm) L2 (mm) D1 (mm) Weight (kg) 15 70 252 49 approx. 5 Note: 1 inch = 25.4m m ANSI class 150 and class 300 dimensions: Meter size (inch) L1 (inch) L2 (inch) D1 (inch) Weight (lb) 1/2 2.
LF410/LF600 LF410/LF602 6 Unit : mm (L2) L1 225 133 (35) 131 Φ D1 Note1: Eye bolts are provided at the top fo r flow mete rs sized 200mm (8"). BS16, DIN PN16 and JIS 10K dimensions Meter size (mm) L1 (mm) L2 (mm) D1 (mm) Weight (kg) 40 100 264 85 approx.
LF410/LF600 LF410/LF602 7 Unit : mm 88 40 (126) (35) 91 R(PT) ½ Male S crew (T wo places) (L2 ) Φ 66 87 L1 Note1: Cable glands are not provide d for LF414 of FM and CSA a pproved t ype. Refer to the pa rt Cable c onnection port at det ector. Note2: 1 inch = 25.
LF410/LF600 LF410/LF602 8 矢視A 信号ケ ー ブ ル グラ ン ド 電源ケ ー ブ ルグ ラ ン ド 封止栓 励 磁 ケー ブル グラ ンド 電流 出 力ケー ブルグラ ン ド 接地端子 (M4 ) 取付金具 4- φ 11 取付金具 82 (36) 156 13 15 1 178 200 151 74± 0.
LF410/LF600 LF410/LF602 9 T erm inal bo ard Conne cted de tecto r Excitation cabl e IV wi r e 5.5 mm 2 or more Pow e r sw itch (Ext er nal do uble -pol e po w e r sw itch ) Thi ck walled st eel con du.
LF410/LF600 LF410/LF602 10 Wiring Precautions (1) Explosion proof type flowmeters are not provided cable glands. Refer to the part Cable connection port at detector and converter. (2) Connect the grounding wire (IV wire 5.5mm² or more) to a good earth ground (100 Ω or less ground resistance).
LF410/LF600 LF410/LF602 11 Piping Precautions (1) Design piping so that t he flowmeter detector pipe is always filled with the fluid being measured, whether the fluid is flowing or not. (2)The detector has no adjustable piping mechanism. Install an adjustable short pipe where needed.
LF410/LF600 LF410/LF602 12 Meter Size To select the meter size: See Figure 13 and find meter sizes within the velocity of 0.1 to 10m/s for a specified full-scale (measuring range high limit) flow. Select one that has its full-scale velocity between 1 and 3m/s.
LF410/LF600 LF410/LF602 13 About establishment environment Do not store or install the flowmeter in: • Places where there is direct sunlight. • Places where excessive vibration or mechanical shock occurs. • Places where high temperature or high humidity conditions obtain.
LF410/LF600 LF410/LF602 14 Table 3. Specification Code (Waf er type detector LF410 Series) Detector ca tegory Model Specific ation Code Normal type Ex.
LF410/LF600 LF410/LF602 15 Table 4. Specification Code for converter s Model Specific ation Code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Contents L F 6 0 Elec tromagnetic flowmeter converter LF600 type LF602.
LF410/LF600 LF410/LF602 No. EJL-114B Specifications are subject to change without notice. Printed in Japan 2006-10 (TDOC) © TOSHIBA Corporation 2006 All Rights Reserved. Misuse of this product can result in da mages to property or human injury. Read related manuals carefully before using this product.
Ein wichtiger Punkt beim Kauf des Geräts Toshiba LF410/LF602 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Toshiba LF410/LF602 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Toshiba LF410/LF602 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Toshiba LF410/LF602 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Toshiba LF410/LF602 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Toshiba LF410/LF602 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Toshiba LF410/LF602 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Toshiba LF410/LF602. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Toshiba LF410/LF602 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.