Benutzeranleitung / Produktwartung JK Series des Produzenten Toshiba
Zur Seite of 23
JK Series POWER DISTRIBUTION 400A & 720A Fixed T ype Medium V oltage Motor Contr ollers.
The low voltage section is oversized and is at a convenient height. This section is isolated from the medium voltage section and includes: Thermal Overload Protection Relay Pilot Lights (door mounted).
T oshiba's JK400 series complies with EEMAC, NEMA, UL and CSA standards and is available in non-reversing and reversing full voltage, autotrans- former , reactor , multi-speed, synchronous and wound rotor configurations. Latched contactors are also available.
MEDIUM VOL T AGE CONTROLLERS JK720 Series The new JK720 Series of motor controller is the result of extensive research and development. This state-of-the-art controller was designed in Houston, T exas, and is currently being manufac- tured under ISO 9001 standards in the same manufacturing facility as T oshiba motors and drives.
T oshiba's JK720 series complies with EEMAC, NEMA, UL and CSA standards and is available in non-reversing and reversing full voltage, autotrans- former , reactor , multi-speed, synchronous and wound rotor configurations. Latched contactors are also available.
JK Series Product Specification 400A MEDIUM VOLTAGE FIXED CONTROLLER 1. Standards 1.1 Basic controller shall comply with NEMA ICS3-1993, Part 2 (ICS2-324) and UL 347 Standards.
2.4 Handling and Installation 2.4.1 Removable angles or eye bolts shall be pr ovided at the top of t he structure for lifting. 3. Pow er Bus 3.1 Horizontal power bus shall be located at the cent er rear of the cubicle, in the same location as other JK Series controllers.
4.2 Bolted Pressure Isolation Switch 4.2.1 A Toshiba type JK fixed mounted, gang-oper ated isolation switch shall be provided with each controller to isolate the medium vo ltage compartment from the power source. 4.2.2 The switch shall be directly driven by an externally operable handle mounted on the right hand flange of the cubicle.
4.3.3 Power connections from the isolation switch to the main power fuses shall be made using bus bar. Connections from the contactor through the current transformers to the outgoing load terminals shall be made using power cable furnished by others. 4.
5. Ratings 5.1 Controller shall be rated as follows: 5.1.1 Interrupting Ratings: 400 Ampere Controller: - contactor 7.0kA @ 6.9kV - fused controller 50kA RMS Sym. @ 7.2kV 200MVA @ 2.3kV 350MVA @ 4.0kV 400MVA @ 4.6kV 570MVA @ 6.6kV 5.1.2 Continuous Thermal Ratings: 400 Ampere Controller: Enclosure type Max.
JK Series Product Specification 720A MEDIUM VOLTAGE FIXED CONTROLLER 1. Standards 1.1 Basic controller shall comply with NEMA ICS3-1993, Part 2 (ICS2-324) and UL 347 Standards.
2.4.1 Removable angles or eye bolts shall be pr ovided at the top of t he structure for lifting. 2.4.2 Optional removable sill channels shall be available. 3. Pow er Bus 3.1 Horizontal power bus shall be located at the cent er rear of the cubicle, in the same location as other JK Series controllers.
4.2 Bolted Pressure Isolation Switch 4.2.1 A fixed mounted, gang-operated isolation sw itch shall be provided with each controller to isolate the medium voltage compartment from the power source. 4.2.2 The switch shall be directly driven by an externally operable handle mounted on the right hand flange of the cubicle.
4.3.3 Power connections from the isolation switch to the contactor shall be made using bus bar. Connections from the contactor through the curr ent transformers to the outgoing load terminals shall be made using power cable. 4.3.4 The contactor shall be supplied with an optional mechanical latch with provisions for manual or electrical trip.
4.5.7 An electrical interlock shall be provided to ensure the isolation switch does not open with the control power transformer under load. This interlock shall be designed such that during switch opening, the transformer secondary is disconnected prior to the opening of the switch blades.
.
.
.
.
.
.
.
Medium V oltage Motor G7 Drive *pacjKSBROCH050218* ADJUST ABLE SPEED DRIVES MOTORS CONTROLS UPS INSTRUMENT A TION PLC INDUSTRIAL DIVISION 13131 W est Little Y ork Road, Houston, T exas 77041 T el 713/466-0277 Fax 713/466-8773 US 800/231-1412 Canada 800/872-2192 Mexico 01/800/527-1204 www .
Ein wichtiger Punkt beim Kauf des Geräts Toshiba JK Series (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Toshiba JK Series noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Toshiba JK Series - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Toshiba JK Series reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Toshiba JK Series erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Toshiba JK Series besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Toshiba JK Series verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Toshiba JK Series. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Toshiba JK Series gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.