Benutzeranleitung / Produktwartung G9000 des Produzenten Toshiba
Zur Seite of 17
CORPORATE OFFICE 13131 WES T LITTLE YORK ROAD HOUSTON, TX 7704 1 PHONE: (713) 466- 0277 (800 ) 231- 1412 FACSIMILE: (713) 896 - 5226 1 TOSH I BA G9000 80/100/160/225 kVA GUIDE SPECIFICATION THREE PHAS.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 2.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 3 Table of Contents 1 SCOPE ..........................................................................................................................................................
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 4 9.2 R EMOTE S TATUS A LARM P ANEL (RSAP) ............................................................................................................................... 15 10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION) .
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 5 1 SCOPE 1.1 Sy stem Th ese specifications desc ribe a high eff iciency continuous duty, three-pha se, on-line, solid-state Uninterruptible Power Supply system (UPS).
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 6 2.3 Sy stem Operation: The UPS shall operate as a f ully automatic on-line sy stem i n the following modes: 2.3.1 Normal I GBT Rectifier c onverts AC input power to DC power for the inverter and for cha rging the batteries.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 7 3.2.3 Clearances for installation Ceiling L evel : 20 ” minimum from top of UPS to ceiling Front : 40 ” minimum for maintenan.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 8 Current THD : <3% THD at 60% – 100% load <6% THD at 25% – 59% load (No input harmonic filter require d) 4.1.3 Charging Function: DC Nominal Voltage : 480 V AC Ripple on DC Bus : < 0.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 9 Harmonic Voltag e Distortion : < 2% THD (100% L inear L oad) : < 5% THD (100% Non-linear L oad) Phase Displacement : 1° Ma.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 10 5.2.3 Battery Protection The converter shall be provided with monitoring and control cir cuits to protect the battery sy stem from damag e due to excessive discharg e.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 11 5.3.5 Overload Capacity : The I nverter output shall be c apable of providing an overload curre nt of 125% for 2 min. and 150% for 1 min. A messag e on the control panel shall indicate this condition.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 12 I f the by pass sourc e is bey ond the conditions stated be low, interrupted transfer sha ll be made upon detection of a f ault condition. By pass voltage greater than + 10%, -10% from the UPS rated output voltag e.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 13 5.5.4 Mimic Panel A one-line diag ram of the sy stem shall be display ed on the touch pane l display panel to provide a visual status of contactors within UPS.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 14 6 MECHANICA L DESIGN 6.1 UPS Enclosure The UPS shall be a free standing NEMA1 enclosure equipped with a leveling c hannel base. The enclosure shall include provisions for hoisting , jacking, and fo rklift handling.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 15 9.1.2 HTTP Familiarity The RemotEy e I I shall provide a HTTP interfac e for the UPS to allow easy access of the UPS information from any machine with a web browser. At any ti me, a network workstation or management sta tion shall be able to open a RemotEy e II website.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 16 10 TOSHIBA DISTRIBUTION CABN ET (TDC) (OP TION) The manufacture r can optionally provide a matching TDC for the UPS. The TDC can include a step-down, 480/208/120 V transformer in a matching NEMA1 cabinet.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 17 14 EXTENDED SER VICES (OPTION) The UPS manufacturer c an offer : Startup Service Maintenance Contrac ts (Silver, Gold, Platinum).
Ein wichtiger Punkt beim Kauf des Geräts Toshiba G9000 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Toshiba G9000 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Toshiba G9000 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Toshiba G9000 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Toshiba G9000 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Toshiba G9000 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Toshiba G9000 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Toshiba G9000. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Toshiba G9000 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.