Benutzeranleitung / Produktwartung 1500 SERIES des Produzenten Toshiba
Zur Seite of 32
TOSHIBA UNINTERRUPTIBLE POWER SYSTEM SINGLE PHASE - .6/.8/1.0/1.2 kVA SINGLE PHASE - .6/.8/1.0 kVA PL U S March, 2003 Part # 46370-002 MANUF ACTURED IN THE U .
TOSHIBA.
TOSHIBA The instructions contained in this manual are not intended to cover all of the details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance.
TOSHIBA CONTENTS SECTION PAGE Disclaimer ................................................................................................. i Contents ................................................................................................ ii-iii Introduction .
TOSHIBA CONTENTS (Cont'd) SECTION PAGE 5.0 Operating the UPS (cont'd) .................................................................... 5-1 5 .3 Operation Monitoring ...................................................................... 5 -3 5.
TOSHIBA iv INTRODUCTION Thank you for purchasing the 1500/1500 Plus Series UPS. This Series features the very latest state of the art microprocessor technology and also uses IGBT transistors for fast, high power and low noise P WM (pulse width modulation) switching.
TOSHIBA v GENERAL SAFETY INSTRUCTIONS Warnings in this manual appear in any of four ways: 1) Danger - The danger symbol is a lightning bolt mark enclosed in a triangle which precedes the 3/16" high letters spelling the word "DANGER".
TOSHIBA SA VE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during the installation and maintenance of the UPS and it's batteries. Use for models UE1A1A006C6, UE1A1A006C6T , UE1A1A008C6, UE1AIA008C6T , UE1A1A010C6, UE1A1A010C6T , UE1A1A012C6.
TOSHIBA IMPORT ANT SAFETY INSTRUCTIONS Installation and servicing of batteries should be performed by personnel knowledgeable of batteries and the required precautions.
TOSHIBA Model Capacity Manufacturer T ype Quantity 600 VA / 600 VA Plus Y uasa NP4-12FR 5 800 VA / 800 VA Plus 1000 VA / 1000 VA Plus Y uasa NPH5-12FR 5 1200 VA viii © Copyright 1994 INSTRUCTIONS IMPORT ANTES CONCERNANT LA SÉCURITÉ Cette notice contient des instructions importantes concernant la sécurité.
TOSHIBA 1.0 Product Description 1 . 1 Theory of Operation An uninterruptible power supply is a system that is installed between the commercial power and the load equipment. It is used during short-term blackouts or brownouts. The UPS provides steady ac output power during these commercial power interruptions.
TOSHIBA 2.0 Inspection/Storage/Disposal 2 .1 Inspection of the new UPS equipment Upon receipt of the UPS, a careful inspection for shipping damage should be made.
TOSHIBA 3 - 1 3.0 Precautions 3 . 1 Installation Precautions (General) 1) Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on all sides for air ventilation and for maintenance. 2) Install the unit in a stable, level, and upright position which is free of vibration.
TOSHIBA 3.0 Precautions 3 .2 Prestart Precautions 1) Before connecting the UPS to a power source; move the operation switch (STOP/RUN), on the front panel (See sections 9.1), to the STOP position. 3 . 3 Operating Precautions 1) The UPS should not be powered up until the entire operation manual has been reviewed.
TOSHIBA MODEL NUMBER UE1A1A006C6 UE1A1A008C6 UE1A1A010C6 CAPACITY 600 VA (0.42 kW) 800 VA (0.56 kW) 1000 VA (0.7 kW) Input Input voltage Single phase, 120 Vac, +10% to -30% (*) Input frequency 45 to 65 Hz Input capacity 600 VA 800 VA 1000 VA Input power factor Approximate unity (0.
TOSHIBA MODEL NUMBER UE1A1A012C6 CAPACITY 1200 VA (0.84 kW) Input Input voltage Single phase, 120 Vac, +10% to -30% (*) Input frequency 45 to 65 Hz Input capacity 1200 VA Input power factor Approximate unity (0.95 to 1.0) Battery Battery rated voltage 60 Vdc Battery backup time when fully charged 5 min.
TOSHIBA MODEL NUMBER UE1A1A006C6T UE1A1A008C6T UE1A1A010C6T CAPACITY 600 VA (0.42 kW) 800 VA (0.56 kW) 1000 VA (0.7 kW) Input Input voltage Single phase, 120 Vac, +10% to -30% (*) Input frequency 45 to 65 Hz Input capacity 600 VA 800 VA 1000 VA Input power factor Approximate unity (0.
TOSHIBA 5.0 Operating the UPS 5 . 1 Operation Modes 5.1.1 AC Input Mode (normal operation) Power flow in AC input mode The above illustration shows circuit power flow in the ac input mode. The UPS unit's rectifier , included in a boost chopper circuit, converts ac input power to dc power .
TOSHIBA 5.0 Operating the UPS 5 . 1 Operation Modes 5.1.3 Ci rc u it-bypass mode Power flow in circuit-bypass mode. If the UPS unit is severely overloaded or develops an internal fault, the power flow is automatically switched from the unit's main circuit to the bypass circuit mode.
TOSHIBA 5.0 Operating the UPS 5 . 3 Operation Monitoring 5.3.1 V isual Indicator Functions The following LED (light emitting diode) indicators are located on the front panel (see Section 9.2 "Panel Layout"). Refer to these lamps for visual information about the operating condition of the UPS (see Section 5.
TOSHIBA Output Display Status Explanation During battery backup all green lamps flash and the red Backup lamp is lit continuously . As the batteries discharge, the Battery green lamps extinguish Backup from top to bottom to indicate remaining battery capacity (This sample display shows battery voltage between 75% and 90% of battery capacity).
TOSHIBA 5 - 5 5.0 Operating the UPS (Cont'd) 5 . 6 Battery Recharging The graph below shows the typical voltage requirements for recharging the UPS unit's batteries. Model Vmax. Vmin. Charge 600 VA / 600 VA Plus 68.2 48.0 0.4 (A) 800 VA / 800 VA Plus 68.
TOSHIBA 5 - 6 5.0 Operating the UPS 5 . 7 Battery Backup Tim e The UPS unit's batteries provide about 5-12 minutes of back-up time depending on the capacity of the UPS. These times are valid when a unit is operating under full load. When the units are operating at half load, the batteries can power the load equipment about 3 times longer .
TOSHIBA 6 - 1 6.0 UPS Control Interface 6 . 1 DB25 Connector Pinout RS-232C serial communication and Dry Contacts are both standard features available through a DB25 female connector located on the back panel of the UPS (see Section 9.
TOSHIBA 6.0 UPS Control Interface 6 .2 RS-232C Serial Communication Interface The available data from the UPS, via RS-232C communication, is shown below: Output voltage Output current Operating condit.
TOSHIBA Fault Display status Probable cause Corrective action Remove cause of Output low Inverter fault or short short circuit. If none is voltage circuit in UPS output found, contact your T oshiba service representative. Output Resonance with load Remove load overvoltage equipment equipment one piece at a time.
TOSHIBA Fault Display status Probable cause Corrective action D C Inverter fault overcurrent D C Chopper fault overvoltage Contact your T oshiba service representative. Input Chopper fault overcurrent UPS system T rouble with the control error P W B 7 - 2 7.
TOSHIBA 8.0 Preventive and Scheduled Maintenance/Parts Replacement 8 . 1 Preventive Maintenance T oshiba's 1500 and 1500 Plus Series of uninterruptible power systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance.
TOSHIBA Fuse rating Model Amp rating Fuse model no. 600 V A 15.0A LittleFuse 314015 800 V A 15.0A LittleFuse 314015 1000 V A 15.0A LittleFuse 314015 1200 V A 15.0A LittleFuse 314015 600 V A Plus 15.0A LittleFuse 314015 800 V A Plus 15.0A LittleFuse 314015 1000 V A Plus 15.
TOSHIBA 8.00 10.00 Input power cord connector Fuse Computer Interface Connector Output Receptacles Air V ents 20.38 9.0 External Dimensions/Shipping Weights/Panel Layout 9 .
TOSHIBA 9.0 External Dimensions/Shipping Weights/Panel Layout 9 . 2 Panel Layout 9 .3 Shipping W eights UPS Shipping W eight Model Pounds Kilograms 600 VA 48.8 22.2 800 VA 48.8 22.2 1000 VA 52.2 23.7 1200 VA 52.2 23.7 600 V A Plus 66.0 30.0 800 V A Plus 66.
TOSHIBA TOSHIBA INTERNATIONAL CORPORA TION INDUSTRIAL DIVISION 13131 W est Little Y ork Rd., Houston T exas 77041 T el: [800] 231-1412 Fax: [713] 466-8773 T elex: 762078 Printed in U.
Ein wichtiger Punkt beim Kauf des Geräts Toshiba 1500 SERIES (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Toshiba 1500 SERIES noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Toshiba 1500 SERIES - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Toshiba 1500 SERIES reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Toshiba 1500 SERIES erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Toshiba 1500 SERIES besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Toshiba 1500 SERIES verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Toshiba 1500 SERIES. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Toshiba 1500 SERIES gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.