INSTRUCTION MANUAL.
INSTRUCTION MANUAL 1272M001 Manual Revision: 9.4 - November 2007.
Contents 1 G e t t i n g S t a r t e d .................................... 1 - 1 2 Operations Overview Cv2 capa bilities (Advanced M ode) ........................... 2 - 1 W h a t c o n s t i t u t e s a n a l a r m ? .............................. 2 - 1 How are alarms processed? .
B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Regulatory Notices CAUTION The ProTalk Cv2, model B1272D, has been certified by the Fe deral Communications Commission (“FCC”) using the included a rticula ting dual-band dipole antenna. Unauthorized modifications or changes not expressly appr oved by Barnett Eng ineering L td.
Getting Started 1-1 B1272M001 BARNETT ENGINEERING LTD . ProTalk Cv2 1. Getting Started The Cv2 is a very flexible device capable of monitoring discrete or analog inputs and reporting alarm conditions at these inputs . I t is also capable of controlling multiple output s.
Getting Started 1-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 single function called Controls. The number of directories is redu ced from 6 to 2 in Ba sic mode. I t is possible to retain the Advance d directory commands even if the overall prog ramming is set for Basic operation.
Getting Started 1-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Table 1 Mode Comparison Function Advanced Mode Basic Mode I nput debounce I ndependent for each input Part of Alarms - same setting .
Operations Overview 2-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 2. Operations O v erv iew The purpose of this chapter is to provide an overview of the Cv2 ca pabilities. Chapter topics ar e organized in the same order that y ou would follow in setting up the sy stem.
Operations Overview 2-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 HARDWARE INPUTS 8 INPUTS 8 OUTPUTS POINTS UP TO 30 INPU TS OR O UTPUTS GRO UP 1 CELL PHONE HARDWA RE OUTPUTS GROUP 6 DIRECTORY A.
Operations Overview 2-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 2.1.4 What actions should occu r when an alarm is detected? All alarm conditions will be pr ocessed by placing a call on the cellular phone. The called number and the activitie s that occur with different ala rms are determine d by entries in the directories.
Operations Overview 2-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 alarm before the Cv2 advances to the next line in the directory. This can be done by using the Wait command on its own line ; the entry below will cause a four minute de lay before the next line is ex ecuted.
Operations Overview 2-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 allowing access to alarm i nformation or other control functions. At the highest level , the call is answered but there are no voice prompts; th e caller has ten seconds to enter the Access Code.
Operations Overview 2-6 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 ALARMS 8 INPUTS 8 OUTPUTS CELL PH ON E OUTPUTS DIRECTORY A DIRECTORY B DIALOUT COMMANDS CONTROL COM MANDS 5 HARDWARE CONTROLLED 3 USER CONTROLLED ACKN OWLEDGE IN TERROGATE ACCESS Figu re 2 Cv2 Blo ck Di agram - Basic Mode 2.
Operations Overview 2-7 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 2.2.4 How do you want to respond to an alarm call? After the Cv2 has finished speaking the alarm messag es, it prompts the called party with the phrase “Enter Acknowledge Code” and then waits five seconds for the code to be returned.
Operations Overview 2-8 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 2.3 Indi cators The Cv2 has four L ED indicators to show the operation of the unit and to assist in troubleshooting. When the Cv2 is initially powered up, the four LEDs will do the following: C All will turn on for a pproximately one second.
Operations Overview 2-9 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Are t he inputs co nnecte d properly? For digital inputs that are prog rammed for standard digital operation, create an alarm condition on the input and confirm that the Al arm LED comes on.
Install ation 3-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Figure 3 Packaged Cv2 3 Installation The Cv2 can be installed before or after the c onfiguration has been tr ansferred from the PC to the unit.
Install ation 3-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Figure 4 Sta nd-alone Cv2 Figure 5 Gr ound Closure Input Wiring 3.2.2 Stand-alone model The stand-alone Cv2 can be mount ed on a flat surface. Make sure that there is enough room around the unit to make connections.
Install ation 3-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Figure 6 +1 2 Volt Input Wiring Figure 7 +5 VDC Input Wiring Figure 9 Analog (unfiltere d) Input Wiring Figure 8 Analog (filtere d) Input Wiring 3.
Installat ion 3-4 B1272M001 BARNET T ENGINEERING LT D. ProTa lk Cv 2 Figure 10 Output Wiring Figure 11 Serial Cable 3.4 Output port c onnections The output ports are open collector drivers that can sink up to 500 mA through a load connected to a voltage of up to +50 VDC.
Install ation 3-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Figure 12 Stand-alone Cv2 Figu re 13 Packag ed Cv2.
Configuration using the PC 4-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 4 Configuration using the PC This chapter describe s how to install the programming software and configure the opera tion of the Cv2. When the configuration is comp lete, it can be viewed through the Summary command found on the File pull-down menu.
Configuration using the PC 4-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 4.5 Progr am Funct ions - A dvanced mode The menu and taskbar for the a dvanced mode is shown below: File Ope rations File Open I f y ou do not want to edit the de fault database, use the File Op en button to select a different configuration file.
Configuration using the PC 4-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Groups Each of the six groups can be set to provi de different alarm re porting operations for selected points. Poi nts In the points section, any of the hardware i nputs and outputs can be selected for the Cv2 to use as alarm reporting or remote contro l functions.
Configuration using the PC 4-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 way to get the unit operational when in the Advan ced mode. I f the Cv2 uses any of the special port functions -- Alarm A.
Configuration using the PC 4-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Watchdog I nterval timer. Refer to the precedin g Dig ital input description for details on the Debounce timer. Two Watchdog time rang es, seconds and minutes, are available.
Configuration using the PC 4-6 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Two timer ranges, seconds and minutes, are available. The seconds range has a maximum value of 1638 seconds (27 minutes) with a re solution of 25 msec. For longer times the minutes range should be used.
Configuration using the PC 4-7 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 <RING> Output used to indicate that the phone is ringing. <CD> Output used to indi cate that the modem is in the connected st ate. Default Port Selec tion: Unused, not included in any reporting a ctivities.
Configuration using the PC 4-8 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Decimal Place A decimal place can be inserted into the s poken message for a totalizer.
Configuration using the PC 4-9 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 announced in engineering units. Calibrate is a secondary dialog box that is activated from the Analog Point dialog box.
Configuration using the PC 4-10 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Minimum: 0 Maximum: +100.0 L ow Setpoint: +25.0 High Setpoint: +75.0 Hysteresis Hy steresis is a quick method of establishi ng the reset values for the hig h and low setpoints.
Configuration using the PC 4-11 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 interval, the output port may have returned to the Off state before the announcement is made. This code can be 1 to 7 digits in leng th and may use any of the 16 DTMF digits including A, B, C, and D.
Configuration using the PC 4-12 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Interrogate Code The I nterrogate Code is a 1 to 7 dig it DTMF string that is used to make the Cv2 announce the condition of points in the group.
Configuration using the PC 4-13 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including A, B, C, and D. Default Shift Selection: Dire ctory A for all shifts. Special F unction Outputs Outputs can be assigned to indicate certain conditions within the Cv2.
Configuration using the PC 4-14 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 in a line-by -line format. A line represents one complete action, usually a cellular call. Edit the highlighted line by pressing Enter, double-c licking on the line, or selecting the Edit L ine command from the menubar in the summary window.
Configuration using the PC 4-15 B1272M001 BARNET T ENGINEERING LT D. ProTa lk Cv 2 separated by 100 ms ec of quiet. Alert must be preceded by a Dial command; it cannot be the first entry in the list.
Configuration using the PC 4-16 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Level 2 When the incoming call is answered by the Cv2, only the Site I D is announced; for further access to the C v2 the caller must enter the Access Code.
Configuration using the PC 4-17 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Ring Output Ring output is used to select one of the eigh t outputs to e xternally indicate that the re is an incoming c all. The output will follow the ring ing cade nce if selec ted.
Configuration using the PC 4-18 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Configurat ion Data To transfer configura tion data, use the two buttons in the Configuration box.
Configuration using the PC 4-19 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 4.8.2 Control section Use the Control section to configure the hardware outputs if the Cv2 is going to be used for remote control.
Configuration using the PC 4-20 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 keeping the rest of the c onfiguration in basic mode. Insert - I nsert a new phone number at the highlighted location De.
Rem ote Data Acce ss 5-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Figure 14 - D ata Cable for Externa l Equipment 5 Remote Data A ccess External equipment connected to the serial port can be acce ssed by calling the Cv2 with a remote modem.
Voice Storage and Configuration with t he Telset 6-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 6 Voice Storage and Confi guration w ith the Telset 6.1 Setup The Cv2 can be configured by transferring a data base from the PC, eithe r in Basic or Advanced mode, or by using the programming phone.
Voice Storage and Configuration with t he Telset 6-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Directory programming, where the called numbers ar e entered, require s care to ensure tha t these numbers ar e valid.
Voice Storage and Configuration with t he Telset 6-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 6.4 Telset Programming Summary A Cv2 is set for Basic mode programming when it is shipped. The only way to change it to the Advanced mode is by using the PC configuration software.
Voice Storage and Configuration with t he Telset 6-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 6.5 Programmi ng Fl ow chart Voice Menu (Basi c an d Ad vanced mo de) Cv2: “Enter Voice.
Voice Storage and Configuration with t he Telset 6-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Direc tory Line Cv2: “Directory A Line 1 is DI AL 2559545 VO ICE” Y ou: Edit current .
Voice Storage and Configuration with t he Telset 6-6 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Turn call progress detector on Exit to Main Menu Accept call progress co.
Voice Storage and Configuration with t he Telset 6-7 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Exit to Main Menu Accept alarm form at and advance to Debounce Scale Debounce Scal.
Voice Storage and Configuration with t he Telset 6-8 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Contro l Timer Scale Cv2: “Control Timer is seconds” Y ou: Change timer scale to seco.
Voice Storage and Configuration with t he Telset 6-9 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Transceiv er State Cv2: “Code Five is 8 1” Y ou: Exit to Main Menu Advance to .
Voice Editor 7-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 7 Voice E ditor 7.1 Voice Edit or Access to the Voice Editor is through the drop-down File menu. The voice ed itor is a utility for manipulating and orga nizing the individual phra ses that the Cv2 uses to identify groups, points and the site ID.
Voice Editor 7-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Controls in the Voice Editor dialog box are: I ndividual Voice Phrase Section Hardware The setting of the tab control at the bottom of the box determines which pa rt of the messag e config uration is shown in the phrase list boxes.
Voice Editor 7-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 Messag e File Sec tion Lo ad A File Open dialog box is used to sel ect the require d message file with the .msg extension. Message files contain the phrases used by the Cv2 to identify Site ID, Groups and Points.
Voice Editor 7-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 7.2 Wave Fi l e Conversi on Access to the wave file converter is through the drop-down F ile menu. The Cv2 uses Adaptive Differential Pulse C ode Modulation (ADPCM) operating at 32 kbps to convert audio signals to digital form.
Specifications 8-1 B1272M001 BARNET T ENGINEERING LT D. ProTa lk Cv 2 8 Specific ations 8.1 G eneral Alarm I nputs • 8 inputs: analog or digital, latching or momentary ; plug in screw terminal block.
Specifications 8-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 intervals are adjustable from 1 to 249 minutes; the short timer can be used from 1 to 9 time s. Acknowledge Code • Stops the transmissi on cycle when received. 1 to 7 DTMF digits with individual codes allowed for each gr oup.
Cellphone Status Codes 9-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 9 Cellphone Status Codes Following is summary of the transceiver codes th at can returned to the telset from the cellphone configuration section. 9.1 Receiv ed Signal Strength Indicator - RSSI ( code 1) Speaks “Code One is 8, 8, 8, 8, .
Cellphone Status Codes 9-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 9.6 Channel / Power (code 6) Speaks “Code Six is ABC point DE”, where ABC = current transceiver center frequency channel DE = current transmitter powe r (negative dBm) 9.
Cellphone Status Codes 9-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 9.8 Extended State/ Drop R eason/ Online Mode (code 8) Speaks “Code Eight is A point BC point D”, where: A = Power Availa.
W arranty 10-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv 2 10 Warranty Barnett Eng ineering L td. warrants that a ll equipment supplied shall be free from defects in materia l or workmanship at the time of delivery . Such warranty shall extend from the time of delivery for a period of one y ear.
Ein wichtiger Punkt beim Kauf des Geräts Barnett Engineering CV2 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Barnett Engineering CV2 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Barnett Engineering CV2 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Barnett Engineering CV2 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Barnett Engineering CV2 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Barnett Engineering CV2 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Barnett Engineering CV2 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Barnett Engineering CV2. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Barnett Engineering CV2 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.