Benutzeranleitung / Produktwartung A0554831 des Produzenten Sterling
Zur Seite of 70
2–40 hp Portable Chillers Part Number: A0554831 Bulletin Number: SC2-610C.10 Effective: 4/3/2008 Write Down Your Serial Numbers Here For Future Reference: _________________________ _________________.
2-40 HP Portable Chillers ii Shipping Information Unpacking and Inspection You should inspect your equipm ent for possible shipping damage. Thoroughly check the equipment for any damage that m ight have occu rred in transit, such as broken or loose wiring and components, loose hardware and mounting screws, etc.
2-40 HP Portable Chillers iii Table of Contents CHAPTER 1: SAFETY ................................................................. 6 1-1 How to Use This Manual ..........................................................................................
2-40 HP Portable Chillers iv 3-11 Initial Start-Up.......................................................................................................... .. 28 CHAPTER 4: OPERATION ........................................................ 29 4-1 Panel Buttons, Indicator Lights, and Switches .
2-40 HP Portable Chillers v Flow and Pressure Considerations...................................................................... 61 Recirculation Pump Specifications ...................................................................... 61 7-5 Remote Air-Cooled Chiller Configurations .
2-40 HP Portable Chillers Chapter 1: Safety 6 of 70 Chapter 1: Safety 1-1 How to Use This Manual Use this manual as a guide and reference for installing, operating, and maintaining your equipment. The purpose is to assist you in a pplying efficient, proven techniques that enhance equipment productivity.
2-40 HP Portable Chillers Chapter 1: Safety 7 of 70 1-2 Warnings and Precautions Our equipment is designed to provide safe and reliable operation when installed and operated within design specifications, following national and local safety codes.
2-40 HP Portable Chillers Chapter 2: Functional Description 8 of 70 Chapter 2: Functional Description 2-1 Models Covered in This Manual This manual provides operation, installation, an d maintenance instructions for air- and water- cooled portable chillers.
2-40 HP Portable Chillers Chapter 2: Functional Description 9 of 70 2-2 General Description Our portable chillers are reliable, accurate, a nd easy to use process cooling units. They are available in air-, water-, and remote air-cooled designs in a range of sizes from 2 to 40 tons.
2-40 HP Portable Chillers Chapter 2: Functional Description 10 of 70 2-3 Standard Features Mechanical Features Compressor. Hermetic scroll compressors are used on 2 hp through 30 hp (1.49 through 23.37 kW) models. Semi-hermetic discus compress ors are used on the 35 hp and 40 hp (26.
2-40 HP Portable Chillers Chapter 2: Functional Description 11 of 70 Electrical Features • Fully accessible NEMA 12-styl e electrical control enclosure • Single-point power and ground connection .
2-40 HP Portable Chillers Chapter 2: Functional Description 12 of 70 2-4 Safety Device s and Interlocks High/Low Thermostat Control The high/low thermostat is a cutout device that protects the chiller system in two ways.
2-40 HP Portable Chillers Chapter 2: Functional Description 13 of 70 Low Pressure Cutout This electro-mechanical cutout device opens th e compressor control circuit if refrigeration system compressor suction pressure drops below 15 psi. It automatically resets when refrigerant suction pressure reaches 30 psi.
2-40 HP Portable Chillers Chapter 2: Functional Description 14 of 70 2-5 Optional Features Options marked with “ * ” indicate options that can be factory installed or retrofitted in the field. Automatic Water Make-Up*. Not available on chillers less reservoir tank.
2-40 HP Portable Chillers Chapter 2: Functional Description 15 of 70 Mounting Features. • Locking 5” swivel casters with brake, opti onal on air- and water- cooled 5 hp to 15 hp models • Mounting rails: standard on remote air-c ooled models, optional on other m odels • Mounting rails with feet Optional Operating Voltages.
2-40 HP Portable Chillers Chapter 2: Functional Description 16 of 70 Figure 1: Optional Pump Amperages Voltage Construction HP Full Load Amps Bronze Turbine .75 5.4 1 6.4 1.5 7.5 2 9.6 208-230/1/60 SS 3 12.7 Bronze Turbine .75 1.5 1 1.8 1.5 2.3 2 3.1 3 4.
2-40 HP Portable Chillers Chapter 3: Installation 17 of 70 Chapter 3: Inst allation 3-1 Uncrating 2 hp to 5 hp m odels are shipped mounted on a skid, enclosed in a plastic wrapper, and contained in a cardboard box. 7.5 to 40 hp m odels are shipped mounted on a skid, enclosed in a plastic wrapper, and open-crated on all four sides and top.
2-40 HP Portable Chillers Chapter 3: Installation 18 of 70 3-3 Process Water Connections All of our portable chillers have two chille d water connections. The chilled water supply, labeled “To Process” is the outlet for the chille d water leading to the process being cooled.
2-40 HP Portable Chillers Chapter 3: Installation 19 of 70 3-7 Condenser Considerations Water-Cooled Chiller Condensers Water-cooled portable chillers can use city wate r or tower water as a cooling medium. Make sure that all external piping and connections suppl ying and discharging water to and from the condenser are full size.
2-40 HP Portable Chillers Chapter 3: Installation 20 of 70 Remote Air-Cooled Chiller Condensers Remote air-cooled portable chillers are shipped with nitrogen holding charge and a full charge of oil (excluding the am ount needed for field piping). The remote air condenser is shipped with a dry nitrogen charge.
2-40 HP Portable Chillers Chapter 3: Installation 21 of 70 System Configuration. The system can be configured in any of the arrangements shown on page 62 of the Appendix. The configurati on and distance between the chiller and the condenser affects pipe size, refrigerant charge, oil return, and oil charge.
2-40 HP Portable Chillers Chapter 3: Installation 22 of 70 Figure 2: Equivalent Length in Feet for Valves and Fittings Line Size Inches OD Globe Valve Equivalent Ft Angle Valve Equivalent Ft Short Radius Elbow Equivalent Ft Long Radius Elbow Equivalent Ft 1/2” 43 15 1.
2-40 HP Portable Chillers Chapter 3: Installation 23 of 70 Refrigerant Charge Determination. The approximate amount of re frigerant charge required by the system varies based on the total length of the refrigerant lines and the size of the chiller.
2-40 HP Portable Chillers Chapter 3: Installation 24 of 70 3-8 Checking Motor Direction All of our portable chillers have their moto r rotations properly phased at the factory. If compressors, pumps, or fans are running in reverse rotation, disconnect and lock out the power source and reverse any two power lead s into the chiller disconnect switch.
2-40 HP Portable Chillers Chapter 3: Installation 25 of 70 3-9 Water Reservoir All portable chillers shipped during the fall, winter , or spring, or those units that are shipped from stock are flushed at the factory with a water/ethylene glycol solution to prevent piping components prone to retaining water from fr eezing.
2-40 HP Portable Chillers Chapter 3: Installation 26 of 70 Figure 6: Ethylene Glycol and Propylene Glycol Curves Pe r ce n t G ly c ol C u r v e s f or Fr e e ze P r ot e c tio n -60.0 -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 30.0 40.0 0.0 10.0 20.
2-40 HP Portable Chillers Chapter 3: Installation 27 of 70 3-10 Automatic Water Make-Up Option The chiller may be connected to an automatic make-up sy stem if the optional package (float switch, pressure regulating, pipe fittings, sole noid valve and 1/2” NPT city water make-up connection) is factory installed.
2-40 HP Portable Chillers Chapter 3: Installation 28 of 70 3-11 Initial Start-Up • Check the shipping papers against the serial tag to be sure chiller size, type and voltage is correct for the process that will be controlled. Portable chillers are built with a voltage specific compressor and cannot be re-wired for an alternate voltage.
2-40 HP Portable Chillers Chapter 4: Operation 29 of 70 Chapter 4: Operation 4-1 Panel Buttons, Indicator Lights, and Switches Microprocessor Controllers Standard chillers use a microprocessor-based PI D controller. These controllers are modular, self-contained units that can slide from their mounting ho using.
2-40 HP Portable Chillers Chapter 4: Operation 30 of 70 Indicator Name Description SUB1 SUB 1 LED The orange SUB1 LED lights when the process temperature is three degrees or more below the “To Process” setpoint.
2-40 HP Portable Chillers Chapter 4: Operation 31 of 70 Figure 7: Typical Portable Ch iller Microprocessor Controllers PV SV OUT1 OUT2 MANU STOP RMT AT SUB1 AT E5CK OMRON.
2-40 HP Portable Chillers Chapter 4: Operation 32 of 70 Graphic Panel (See Figure 8 ) Indicator Name Description Compressor On Light The Compressor On light turns on whenever the compressor is operating. Low Temperature Light The Low Temperature light comes on if the process water/glycol temperature drops below the High/Low thermostat set point.
2-40 HP Portable Chillers Chapter 4: Operation 33 of 70 Indicator Name Description Low Water Flow/Pressure Light The Low Water Flow/Pressure light comes on when the flow switch (pressure switch on 2 & 3 hp models) senses that the water/glycol flow rate through the evaporator has dropped below an acceptable level.
2-40 HP Portable Chillers Chapter 4: Operation 34 of 70 Figure 8: Typical Graphic Panels (With E5CK Controller) (Eurotherm 3216 Controller) ON OFF CONTROL POWER A0554705 SILENCE ALARM COMPRE SSOR ON H.
2-40 HP Portable Chillers Chapter 4: Operation 35 of 70 4-2 Start-up 1. Turn on the chiller and put it under a process load. 2. Set the controller for the To Process temperature you want, using the Up Arrow button or the Down Arrow button located on the face of the controller.
2-40 HP Portable Chillers Chapter 4: Operation 36 of 70 4-6 Programming the Electronic High/Low Thermostat The thermostat control is located in the chiller enclosure. The control has three control ke ys and a one-line, four-character LCD display. The thermostat control has a lockout slide switch to prevent tampering by unaut horized personnel.
2-40 HP Portable Chillers Chapter 4: Operation 37 of 70 Perform the following procedures to pro gram the electronic High/Low Thermostat control: Select Fahrenheit or Celsius 1. Press the Set key once to access Fahrenheit/Celsius mode. Factory set to F.
2-40 HP Portable Chillers Chapter 5: Maintenance 38 of 70 Chapter 5: Maintenance 5-1 Lubrication Grease all blower bearings, fan and blower m otors, and pump motors that do not have permanently sealed bearings.
2-40 HP Portable Chillers Chapter 5: Maintenance 39 of 70 5-3 Maintaining the Condenser Dirty condenser heat exchange surfaces reduce sy stem capa city and efficiency. Air- and Remote Air-Cooled Chillers Brush or vacuum light dirt accumulations off th e aluminum condenser fins.
2-40 HP Portable Chillers Chapter 5: Maintenance 40 of 70 5-6 Preventative Maintenance Service Follow a systematic preventive maintenance pr ogram to help avoid costly down time. Call the Service Department to arrange a schedule of inspections. This service can be tailored to fit your maintenance requirements.
2-40 HP Portable Chillers Chapter 6: Troubleshooting 41 of 70 Chapter 6: T roubleshooting Problem Possible cause Solution No power. Check main disconnect, fuses, wiring, and power lead to unit. Wrong voltage supplied to unit. Voltage m ust be withi n plus or m inus 10% of nameplat e rating.
2-40 HP Portable Chillers Chapter 6: Troubleshooting 42 of 70 Problem Possible cause Solution Plugged Y-St r a i ner Clean Hot gas not comi ng on Replace relay board on control bed hot gas coil Pump runs, co mpressor cycles at short intervals.
2-40 HP Portable Chillers Chapter 7: Appendix 43 of 70 Chapter 7: Appendix 7-1 Returned Material Policy Credit Returns Prior to the return of any material, authorization must be given by the manufacturer . A RMS number will be assigned for the equipment to be returned.
2-40 HP Portable Chillers Chapter 7: Appendix 44 of 70 7-2 Technical Assistance Parts Department Call toll-free 7am–5pm CST [ 800 ] 423- 3813 or call [262] 641 -8610, Fax [262] 641-8653 The ACS Cust.
2-40 HP Portable Chillers Chapter 7: Appendix 45 of 70 7-3 Drawings and Specifications 2 hp and 3 1/2 hp Air-Cooled Portable Chillers Nominal operating parameters for air-cooled models are 50º F (10ºC) leaving water tem perature at 2.4 gpm per ton (9.
2-40 HP Portable Chillers Chapter 7: Appendix 46 of 70 5 hp and 7.5 hp Air-Cooled Portable Chillers Nominal operating paramet ers for air-co oled models are 50ºF (10º C) le aving water temperature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35º C) a mbient air.
2-40 HP Portable Chillers Chapter 7: Appendix 47 of 70 10 hp and 15 hp Air-Cooled Portable Chillers Nominal operating parameters for air-cooled models are 50º F (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air.
2-40 HP Portable Chillers Chapter 7: Appendix 48 of 70 20 hp, 25 hp, and 30 hp Air-Cooled Portable Chillers Nominal operating parameters for air-cooled models are 50º F (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air.
2-40 HP Portable Chillers Chapter 7: Appendix 49 of 70 2 hp and 3.5 hp Water-Cooled Portable Chillers Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water.
2-40 HP Portable Chillers Chapter 7: Appendix 50 of 70 5 hp and 7.5 hp Water-Cooled Portable Chillers Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water.
2-40 HP Portable Chillers Chapter 7: Appendix 51 of 70 10 hp and 15 hp Water-Cooled Portable Chillers Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water.
2-40 HP Portable Chillers Chapter 7: Appendix 52 of 70 20 hp, 25 hp, and 30 hp Water-Cooled Portable Chillers Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water.
2-40 HP Portable Chillers Chapter 7: Appendix 53 of 70 40 hp Water-Cooled Portable Chillers Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water tem perature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water.
2-40 HP Portable Chillers Chapter 7: Appendix 54 of 70 5 hp and 7.5 hp Remote Air-Cooled Portable Chillers Nominal operating parameters for remo te air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air.
2-40 HP Portable Chillers Chapter 7: Appendix 55 of 70 10 hp and 15 hp Remote Air-Cooled Portable Chillers Nominal operating parameters for remo te air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air.
2-40 HP Portable Chillers Chapter 7: Appendix 56 of 70 20 hp through 40 hp Remote Air-Cooled Portable Chillers Nominal operating parameters for remo te air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air.
2-40 HP Portable Chillers Chapter 7: Appendix 57 of 70 Remote Condenser Assembly Models To convert inches to cm , multiply dimension by 2.5 4. Fan(s) d e f Remote Condenser Re frigeration g Each Totals e f Overall Dimensions Connections Charge HP Dia.
2-40 HP Portable Chillers Chapter 7: Appendix 58 of 70 7-4 Pump Curves, Flow, and Pressure Considerations 60 Hertz Pump Curves DWG. No. A0554823.
2-40 HP Portable Chillers Chapter 7: Appendix 59 of 70 50 Hertz Pump Curves DWG. No. S0554823.
2-40 HP Portable Chillers Chapter 7: Appendix 60 of 70 Evaporator Water Pressure Drop Tables Note: A recirculation pump is required for flows greater than the maximum or less than the minimum indicated. Note: Process flow less than or greater than the flow rates shown below requires a recirculation pump.
2-40 HP Portable Chillers Chapter 7: Appendix 61 of 70 Evaporator Flow and Pressure Considerations Model c Design flow Desig n Δ P Standard pump power To Process pressure gpm lpm psig kPa hp kW psi kPa bars -A, 2 hp 4.6 17.5 4.4 30.4 1 0.746 34.1 235.
2-40 HP Portable Chillers Chapter 7: Appendix 62 of 70 7-5 Remote Air-Cooled Chiller Configurations.
2-40 HP Portable Chillers Chapter 7: Appendix 63 of 70 7-6 Typical Ductwork for Air-Cooled Chillers *See specification tables on pages 45-48 for air flow and pressure capacities.
2-40 HP Portable Chillers Chapter 7: Appendix 64 of 70 7-7 Piping Diagrams Central and Gravity Return Piping with Standpipe Diagram.
2-40 HP Portable Chillers Chapter 7: Appendix 65 of 70 Typical Piping Schematic, 2 and 3 1/2 hp Models μ.
2-40 HP Portable Chillers Chapter 7: Appendix 66 of 70 Typical Piping Schematic, 5 hp through 40 hp, One-Pump Models.
2-40 HP Portable Chillers Chapter 7: Appendix 67 of 70 Typical Piping Schematic, 5 hp through 40 hp, Two-Pump Models μ.
2-40 HP Portable Chillers Chapter 7: Appendix 68 of 70 Typical Piping Schematic, 5 hp through 40 hp, No-Pump Models.
2-40 HP Portable Chillers Chapter 7: Appendix 69 of 70 Typical Piping Schematic, 5 hp through 40 hp, One-Pump Models.
2-40 HP Portable Chillers Chapter 7: Appendix 70 of 70 7-8 Electrical Schematics Typical Electrical Subpanel Please refer to your owner’s information packet for more details regarding your specific unit.
Ein wichtiger Punkt beim Kauf des Geräts Sterling A0554831 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Sterling A0554831 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Sterling A0554831 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Sterling A0554831 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Sterling A0554831 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Sterling A0554831 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Sterling A0554831 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Sterling A0554831. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Sterling A0554831 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.