SCC 2-Pump 12-Station Controllers Part Number: 882.00249.0 0 Bulletin Number: CV3-650 Effective: 10/25/05 Write Down Your Serial Numbers Here For Future Reference: _________________________ __________.
Please note that our address and phone i nformation has changed. Please reference this page for updated contact information. These manuals are obsolet e and are provided only for their technical inf ormation, data and capacities.
2–Pump 12-Station Controllers Chapter 1: Safety 2 Shipping Information Unpacking and Inspection You should inspect your equipm ent for possible shipping damage. Thoroughl y check the equipment for any damage that m ight have occu rred in transit, such as broken or loose wiring and components, loose hardware and mounting screws, etc.
2–Pump 12-Station Controllers Chapter 1: Safety 3 Returns Do not return any damaged or incorrect items until you receive shipping instructions from the shipping departme nt. Credit Returns Prior to the return of any material, authorization must be given by the manufacturer.
2–Pump 12-Station Controllers Chapter 1: Safety 4 Table of Contents CHAPTER 1: SAFETY ................................................................ 6 1-1 How to Use This Manual .....................................................................
2–Pump 12-Station Controllers Chapter 1: Safety 5 4-2 Controller Description and Operation ........................................................................ 35 Text Area ........................................................................
2–Pump 12-Station Controllers Chapter 1: Safety 6 Chapter 1: Safety 1-1 How to Use This Manual Use this manual as a guide and reference for installing, operating, and maintaining your equipment. The purpose is to assist you in a pplying efficient, proven techniques that enhance equipment productivity.
2–Pump 12-Station Controllers Chapter 1: Safety 7 Controller Safety Tags 1-2 Warnings and Precautions Our equipment is designed to provide safe and reliable operation when installed and operated within design specifications, following national a nd local safety codes.
2–Pump 12-Station Controllers Chapter 1: Safety 8 1-3 Responsibility These machines are constructed for maximum operator safety when used under standard operating conditions and when recommended inst ructions are followed in the maintenance and operation of the machine.
2–Pump 12-Station Controllers Chapter 1: Safety 9 Operator Responsibility The operator’s responsibility does not end with e fficient production. The operator usually has the most daily contact with the equipment and intimately knows its capabilities and limitations.
2–Pump 12-Station Controllers Chap ter 2: Functional Description 10 Chapter 2: Functional Description 2-1 Models Covered in This Manual This manual provides operation, installation, and m aintenance instructions for 2-Pump, 12- Station Conveying Controllers.
2–Pump 12-Station Controllers Chap ter 2: Functional Description 11 2-3 Standard Features Mechanical Features Time-fill Capability. The length of time a station’s v acuum valve remains open to allow material to be drawn into its receiver. Volume-fill Capability.
2–Pump 12-Station Controllers Chap ter 2: Functional Description 12 2-5 Safety Device s and Interlocks This section includes information on safety devices and procedures that are inherent to the Controller. This manual is not intended to s upersede or alter safety standards established by the user of this equipment.
2–Pump 12-Station Controllers Chap ter 2: Functional Description 13.
2–Pump 12-Station Controllers Chapter 3: Installation 14 Chapter 3: Inst allation 3-1 Uncrating 2-Pump, 12-Station Controllers are shipped mounted on a skid, enclosed in a pla stic wrapper, and contained in a cardboard box. 1. Pry the crating away from the skid.
2–Pump 12-Station Controllers Chapter 3: Installation 15 Connecting the Control Panel to Vacuum Hoppers Refer to the wiring connection diagram in Figure 1 on the next page that applies to your application. Note: Wire size depends on control volt age, distance, number of vacuum hoppers, and the number of wires in each raceway.
2–Pump 12-Station Controllers Chapter 3: Installation 16 Figure 1: Typical 24-Volt Junction Box Wiring Diagram A0544675 (115VAC)/(0V DC) TO CONTROLLER INPUT FOR PUMP HIGH -VACUUM 6 4 3 T 2 T 1 T 2 R.
2–Pump 12-Station Controllers Chapter 3: Installation 17 Main Power Your 12-station controller system can operate from a 115 VAC or 220 VAC source at 50 Hz or 60 Hz. The main power switch on the controller is located on the right side of the housing.
2–Pump 12-Station Controllers Chapter 3: Installation 18 Gaining Access to the Menu System To enter the menu system, make sure that the controller is in the OFFLINE state. Press the MENU key to initiate the menu system. The menu has three (3) top level menus: 1.
2–Pump 12-Station Controllers Chapter 3: Installation 19 STATION SETTINGS? NO/YES OPERATION MODE? NO/YES Station Settings Menu To access the Station Settings menu, place the controller in the OFFLINE state: 1. Press the ENTER/MENU key to enter the menu syste m .
2–Pump 12-Station Controllers Chapter 3: Installation 20 ALL NORMAL MODE? NO/YES ALL SIGHTGLASS MODE? NO/YES STATION: 1 NORMAL Y=NORMAL N=SIGHTGLS To set all the stations to Normal mode and return to the Station Settings menu: • Press the YES key at the following screen prompt.
2–Pump 12-Station Controllers Chapter 3: Installation 21 TO SELECT A STATION PRESS STATION <1-12> SET DUMP DELAY? NO/YES DUMP DELAY 11: 15.0s PRESS ENTER TO SAVE Set Dump Delay, Station Settings Menu The second submenu in Station Settings is the Set Dump Delay submenu.
2–Pump 12-Station Controllers Chapter 3: Installation 22 SET INPUT DELAY? NO/YES TO SELECT A STATION PRESS STATION <1-12> The screen displays the station you selected (11 in the above example), and the current dum p delay time setting. Using number keys 1 to 0, enter th e new dump delay time (in seconds) into controller memory.
2–Pump 12-Station Controllers Chapter 3: Installation 23 INPUT DLY 11: 0.250s PRESS ENTER TO SAVE SET STATION ALARMS? NO/YES To alter station input delay time: • Select a station to alter, then press the related Station ST nn key. nn is the station number you selected.
2–Pump 12-Station Controllers Chapter 3: Installation 24 TO SELECT A STATION PRESS STATION <1-12> ALARM 11: ENABLED Y=ENABLE N=DISABLE Each station has its own No Convey alarm setti ngs.
2–Pump 12-Station Controllers Chapter 3: Installation 25 ALARM AFTER 3 LOADS PRESS ENTER TO SAVE STATION SETTINGS? NO/YES ASSIGN PUMP>STATION? NO/YES TO SELECT A STATION PRESS HOPPER <1-12> To exit from the Alarm Setting time menu and return to the Station Settings menu: • Press the CLEAR key.
2–Pump 12-Station Controllers Chapter 3: Installation 26 STATION 10: PUMP 1 SELECT PUMP 1 OR 2 To assign a station to a pump: 1. Press the related station ST key. The following menu screen displays: To assign Pump 1 to the station you selected: • Press 1.
2–Pump 12-Station Controllers Chapter 3: Installation 27 PUMP SETTINGS? NO/YES PUMP MODE? NO/YES SET PUMP MODE? Y=SINGLE N=DUAL Pump Settings Menu The Pump Settings menu lets you set all pump parameters. These include: • Pump Mode • Blowback • Delay Time Setting the Pump Mode The first setting to be configured is the Pump mode .
2–Pump 12-Station Controllers Chapter 3: Installation 28 SET ACTIVE PUMP SELECT PUMP 1 OR 2 If you have a single pump system (default): 1. Press the YES key. Selecting Single Pump mode requires the assignment of the default pump; the screen then displays the following: Selecting Dual Pump mode requires ALL stations to be assigned to a pump.
2–Pump 12-Station Controllers Chapter 3: Installation 29 BLOWBACK SETTINGS? NO/YES SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER ENABLE BLOWBACK? NO/YES Changing Blowback Settings, Pump Settings Menu As an option, you can equip the conveying s ystem filter chamber with a blowback feature to pulsate compressed air through the filter.
2–Pump 12-Station Controllers Chapter 3: Installation 30 BLOWBACK PULSES: 10 SETTING FOR PUMP 1 ON TIME: 0.500 s SETTING FOR PUMP 1 OFF TIME: 0.500 s SETTING FOR PUMP 1 The screen continues to the next prompt. The first setting for the blowback feature is the number of blowback pulses.
2–Pump 12-Station Controllers Chapter 3: Installation 31 BLBK AFTER 12 LOADS SETTING FOR PUMP 1 IDLE DELAY TIME? NO/YES Next, set the Pulse Off time value. This is th e duration that the blowback solenoid is turned OFF. • Using the number keys, enter the new Off Time setting, then press ENTER to save the new value.
2–Pump 12-Station Controllers Chapter 3: Installation 32 SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER IDLE TIME: 10.000 s SETTING FOR PUMP 1 The following screen displays. Each pump can have separate idle delay times. To alter idle delay, select a pump: • Using the keypad, enter the pump num ber (1 or 2).
2–Pump 12-Station Controllers Chapter 3: Installation 33 Service Settings Menu The settings in this menu are not meant to be m odified by floor personnel (operators). See the section at the end of this manual for these settings. Saving Controller Settings to Flash Memory Your 12 station controller uses a new technology called flash memory .
2–Pump 12-Station Controllers Chapter 4: Operation 34 TO SELECT A STATION PRESS STATION <1-12> LOAD TIME 10: 63sec PRESS ENTER TO SAVE Chapter 4: Operation 4-1 Startup ??????????????? Setting Load Times You can alter load times anytime while not in the menu system by pressing the SET key.
2–Pump 12-Station Controllers Chapter 4: Operation 35 SECTION 1 SECTION 2 SECTION 3 SECTION 4 2. Using number keys 1 to 0, enter the new time. 3. Press the ENTER key to save the new setting into controller memory. If several stations require altering: 1.
2–Pump 12-Station Controllers Chapter 4: Operation 36 STATION:-- OFFLINE TIME: --- LOGO P1:S--:--- OFFLINE P2:S—-:--- OFFLINE Pump Modes Single Pump Mode In Single Pump mode , the screen displays as shown below. The upper left corner displays the active station being loaded.
2–Pump 12-Station Controllers Chapter 4: Operation 37 Station Icons Below the text portion of the screen, 12 station ic ons display the status of each station in the system. Each station icon contains four segments. Figure 3: Station Icon Segments Label Description Segment 1 The top segment indicates the status of the valve above each station.
2–Pump 12-Station Controllers Chapter 4: Operation 38 Status Indicators Four (4) status indicators are located below th e station icons at the bottom of the display. These indicators include PUMP, BLOWBACK, HIGH VACUUM, and SYSTEM. Each icon word has a 1 and a 2 icon with it, indicating Pump 1 or Pum p 2.
2–Pump 12-Station Controllers Chapter 4: Operation 39 Controller Keypad Your 12-station controller has a 16-position ke ypad to let you operate and alter controller parameters. With the exception of the SET ke y, each key has at least two functions.
2–Pump 12-Station Controllers Chapter 4: Operation 40 4-3 Operation Your 12 station controller electrically controls valves and solenoids to convey material from a central location to individual stations as need ed. The controller works within this process by sensing a material demand and responds in a tim ely fashion to that demand.
2–Pump 12-Station Controllers Chapter 4: Operation 41 Label Description LOADING Following the IDLE (Startup) state, the vent valve is closed and the first station in demand loads when that station sequence valve opens. This is the LOADING state. You can define load ti mes for each station.
2–Pump 12-Station Controllers Chapter 4: Operation 42 4-4 Shut-Down.
2–Pump 12-Station Controllers Chapter 5: Maintenance 43 Chapter 5: Maintenance Updating BIOS Software Occasionally, BIOS software updates are available to enhance the operation of the controller. These updates are available through the Service Deptartment or for download from the internet.
2–Pump 12-Station Controllers Chapter 5: Maintenance 44 Figure 5: BIOS Connection, Electrical Diagram; Drawing 1 A 0 5 6 0 9 7 0 + 2 4 V D C 4 + 2 4 V D C 4 2 0 I / O C O N T R O L L E R A E C P / N.
2–Pump 12-Station Controllers Chapter 5: Maintenance 45 Figure 6 : BIOS Connection, Electrical Diagram; Drawing 2 A0560970 LEGEND FIELD WIRING OPTION/SERVICE WIRING NOTE: ALL WIRES ARE #18 AWG UNLES.
2–Pump 12-Station Controllers Chapter 6: Troubleshooting 46 Chapter 6: T roubleshooting 6-1 General Troubleshooting Problem Possible cause Solution The controller panel is not plugged in. Plug in the controller pan el. The external disconnect (recommend ed) in the dedicated circuit is open (off).
2–Pump 12-Station Controllers Chapter 6: Troubleshooting 47 Problem Possible cause Solution Defective wiring. Correct/replace wi ring. Defective terminal block. Replace defective terminal block. Defective PCB. Replace defective PCB. Output icon comes on, solenoid doesn’t.
2–Pump 12-Station Controllers Chapter 6: Troubleshooting 48 WRITING PARAMETERS TO FLASH-PLEASE WAIT SAVING BACKUP TO FLASH-PLEASE WAIT Controller Recovery using Flash Memory Technology It is possible for a write error to occur while information is being saved in the controller’s memory.
2–Pump 12-Station Controllers Chapter 7: Appendix 49 Chapter 7: Appendix 7-1 Warranty Unless otherwise specified, this product includes a Standard ONE YE AR PARTS AND LABOR WARRANTY.
2–Pump 12-Station Controllers Chapter 7: Appendix 50 Warranty Liabilities THE COMPANY EXPRESSLY DIS CLAIMS ANY AND ALL LIABILITY FOR ANY SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES OR EXPENSES THAT RESULT FROM THE USE OF THIS PRODUCT.
2–Pump 12-Station Controllers Chapter 7: Appendix 51 7-2 Drawings and Diagrams Figure 7: 2 pump 12 station Controller Control Panel Depth dimension of subpanel: 8.0” D (20 .3 cm). Also, review electrical drawings supplied in the packet with this manual.
2–Pump 12-Station Controllers Chapter 7: Appendix 52 7-3 Spare Parts List Figure 8 : Typical 12-Station Controller Ext erior Components, Exploded View A0560974 Power cord A0560954 13 12 10 11 10 14 .
2–Pump 12-Station Controllers Chapter 7: Appendix 53 Figure 9 : Exterior Components Parts List Refer to Figure 8 on Page 51 when identifying parts. Item Qty. Part no. Description 1. 1 A0560963 ENCL, CARL ON, MOUNT FLNG, MNK1 0L 2. 1 A056096 4 ENCL, CARLON, 12 X 10 BODY, NP1210B 3.
2–Pump 12-Station Controllers Chapter 7: Appendix 54 Figure 10 : Typical 12-Station Controller Inte rior Components, Exploded View A0560974 11 8 5 4 3 1 13 11 12 10 9 7 6 2.
2–Pump 12-Station Controllers Chapter 7: Appendix 55 Figure 11: Interior Components Parts List Refer to Figure 10 on Page 53 when identifying parts. Item Qty. Part no. Description 1. 4 W00001055 WASH, #6 SAE FLAT, PLD 2. 1 A0560961 PNL, SUB, C ARLON, JP1210, 10 X 8 3.
2–Pump 12-Station Controllers Chapter 7: Appendix 56 7-4 Controller Identification (Serial Number) Tag (Located on the side of the controller box) 7-5 Technical Assistance (Contact Information) Part.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 57 SET RAMP UP TIME? NO/YES SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER RAMP UP DLY: 1.500s SETTING FOR PUMP n Chapter 8: Service Only Information Note: Hidden, programmable features and hidden menu pages should not be made available to floor operators.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 58 SET RAMP DOWN TIME? NO/YES RAMP DN DLY: 8.000s SETTING FOR PUMP n SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER Setting the Ramp Down Time Ramp down time is a delay that allows the pump to come to a full stop when needed.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 59 SET PUMP STAGE TIME? NO/YES STAGE DELAY: 3.000s PRESS ENTER TO SAVE Setting the Pump Stage Time Pump stage time is a delay that prevents both pumps from engaging at the same time. Although rare in a two-pump system, both pumps can sometimes start at the same time.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 60 SET LCD BLINK DELAY? NO/YES BLINK DELAY: .500s PRESS ENTER TO SAVE Setting the LCD Blink Delay LCD Blink Delay lets you alter the ON/OFF time that the LCD blinks during an alarm. This delay does not effect the Visual or Audible alarm outputs.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 61 HI VAC SENSOR DELAY? NO/YES SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER HIVAC DELAY: 3.000s SETTING FOR PUMP n Setting the Hi Vacuum Sensor Delay Hi vac sensor delay is the time that a high vacuum condition must exist before it is sensed by the controller.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 62 HI VAC VENT DELAY? NO/YES SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER HV VENT DLY: 10.000s SETTING FOR PUMP n Setting the Hi Vacuum Vent Delay Hi vacuum vent delay is the vent time initiated by a high vacuum condition.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 63 HI VAC LOAD COUNT? NO/YES SELECT PUMP 1 OR 2 USE KEYPAD TO ENTER HV LOAD CNT: 7 SETTING FOR PUMP n Setting the Hi Vacuum Load Count Hi vacuum load count sets the maximum number of loads on a station in a high vacuum condition.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 64 INPUT MONITOR? NO/YES IN BNK0: 0000000000 IN BNK1: 0000000000 Using the Installation Aids Menus Input Monitor Screen To assist in the installation process or to aid in problem diagnoses, the controller uses two (2) OEM menu functions.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 65 OUTPUT CONTROL? NO/YES AUTOMATIC OR MANUAL? N=AUTO Y=MANUAL Output Control Menu The Output Control menu gives you direct access to all 20 outputs of the controller. The menu has two (2) modes: Manual and Automatic .
2–Pump 12-Station Controllers Chapter 8: Service Only Information 66 OUTBNK0: 0000000000 OUTBNK1: 0000000000 To access the outputs manually, at the AUTOMATIC OR MANUAL? screen prom pt: 1. Press the YES key. The following screen displays. A cursor displays on the screen.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 67 OEM MENU ACCESS IS NOW AVAILABLE! OEM SETTINGS? NO/YES 8-2 Other Controller Restricted Areas Using the OEM Service Menu The OEM service menu ( O riginal E quipment M anufacturer) lets you set parameters not commonly used.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 68 PWL1:1111 PWL2:2222 PWL3:3333 PWL4:4444 Recovering Passwords By following this procedure, passwords can be displayed should they be lost or forgotten. Note: In the interest of system security and integrity, make sure that only setup people and supervisors know this procedure.
2–Pump 12-Station Controllers Chapter 8: Service Only Information 69 ROM CHECKSUM: 0x0000 PRESS YES TO RESUME Restoring the Controller to Factory Defaults Although rare, you may experience a condition when you need to perform a total reset of the controller.
Ein wichtiger Punkt beim Kauf des Geräts Sterling 882.00249.00 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Sterling 882.00249.00 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Sterling 882.00249.00 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Sterling 882.00249.00 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Sterling 882.00249.00 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Sterling 882.00249.00 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Sterling 882.00249.00 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Sterling 882.00249.00. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Sterling 882.00249.00 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.