Benutzeranleitung / Produktwartung 317913-000 des Produzenten State Water Heaters
Zur Seite of 16
Printed in the U.S.A. 0210 317913-000 A TECHNICAL GUIDE TO DESIGNI NG ENERGY-EFFICIENT COMMERCIAL WATER HEATER SYSTEMS.
2 l . Introduction T o Commercial W ater Heating Pages Parameters .................................................................................................................................... 2- 3 What is Hot Water? ............................
3 What is Hot Water? Hot water is water to which heat energy has been added . . .as more heat is added the water becomes hotter . This water temperature guide shows typical water heating system design temperatures.
4 Evaluating Water The coldest water inlet temperature experienced during the year should be the base from which the maximum system temperature rise is established. Y our water supplier can provide this information. Surface water sources such as lakes and rivers tend to fluctuate as the seasons change.
5 Hot Water Demand The major determination in sizing and the basis of all computations is establishing the probable demand for hot water . In addition, any unusual conditions which might relate to hot water consumption must also be recognized and planned for .
6 • This example could represent an industrial process which is operated for two continuous shifts a day . • Hot water is used at a maximum rate of 3.3 gpm or 198 gph. (It is important to establish maximum flow rate and water temperature rise in order to select a heater model.
7 When used at altitudes of 2000’ or more above sea level, gas-fired heater recovery capacities must be derated 4% for each 1000’ above sea level in order to reflect actual recovery . Recovery Capacity means hot water at the heater recovery rate minute after minute, hour after hour .
8 State commercial tank type water heaters, hot water storage tanks and water heating systems using tanks have assigned tank efficiencies as follows: Gas and Oil-Fired T ank T ype Heaters • Use 70% tank draw efficiency for all one and two temperature applications.
9 Eight hour demand period, per hour capacity . 171 gph recovery Storage: + 8 gal storage 179 gal/8 hour 100 gallon tank Recovery provides 96% x 70% tank efficiency of demand.
10 When Using Electricity T o Heat Water The system designer may want to modify the preceding heater recovery and storage tank capacity information when using electricity to heat water . This is because electricity for commercial use, including water heating, is often sold on a demand rate basis.
11 IV . Sy st em T ypes and Application Design Objective The objectives in the design of commercial water heating systems are numerous and varied. The major considerations which the system designer should include in the planning stages are: 1.
12 2. T wo T emperature provides two temperature hot water service by means of a water mixing valve or through a pre-heater/booster heater combination. In the first concept the heater storage tank is maintained at the highest system temperature required (usually at 180°F) and the mixing valve externally produces the 140°F hot water requirement.
13 Creating the Successful System Creating the successful commercial water heating system is a joint venture involving many persons and skills. In order to select the right system using either tank type or copper type heaters, one should understand the role that each of the persons concerned with the installation plays.
14 2. Select a trial size heater 2 / . 3. Subtract the hourly heater recovery from the demand. 4. The difference in gallons between demand and recovery must come from the tank. 5. Multiply the difference by the number of demand hours. The result is the “usable” number of gallons which must come from the tank.
15 T wo temperature example 1. A one hour demand of 75 gallons of 180°F water and 110 gallons of 140°F water has been established. The lowest incoming water temperature is 40°F . The shortest time in any day in which the demand will be repeated is 3 hours.
16 ST A TE W A TER HEA TERS ASHLAND CITY , TENN. © 200 4 TECHNICAL INFORMA TION 800-365-0577.
Ein wichtiger Punkt beim Kauf des Geräts State Water Heaters 317913-000 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie State Water Heaters 317913-000 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für State Water Heaters 317913-000 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von State Water Heaters 317913-000 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über State Water Heaters 317913-000 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon State Water Heaters 317913-000 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von State Water Heaters 317913-000 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit State Water Heaters 317913-000. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei State Water Heaters 317913-000 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.