SSI EPS2U Power Supply Design Guide A Server System Infrastructure (SSI) Specification For Entry Chassis Power Supplies Revision 2.1 Revision History Orig.
SSI EPS2U Power Supply Design Guide, V2.1 Disclaimer: THIS SPECIFICATION IS PROVIDED "AS IS" WITH NO WARRA NTIES WHATSOEVER, INCLUDING ANY WARRANTY OF MERCHANTABILITY, NONINFRINGEMENT, FITNESS FOR ANY PARTICULAR PURPOSE, OR ANY WARRANTY OTHERWISE ARISING OUT OF ANY PROPOSAL, SPECIFICATION OR SAMPLE.
SSI EPS2U Power Supply Design Guide, V2.1 Contents 1 Purpose........................................................................................................................ .................................. 5 2 Conceptual Overview ...........
SSI EPS2U Power Supply Design Guide, V2.1 9 MTBF ........................................................................................................................... ................................. 30 10 Agency Requi rements .................
SSI EPS2U Power Supply Design Guide, V2.1 1 2 Purpose This 2U Rack Power Supply Specificatio n defines a comm on power supply used in entry-level serve rs. This supply may range typically from 400 to 700 watts and is used in a non-redundant configuration.
SSI EPS2U Power Supply Design Guide, V2.1 3 Definitions/T erms/Acronyms Required The status given to items within this design guide, which are required to meet SSI guidelines and a large ma jorit y of system applications.
SSI EPS2U Power Supply Design Guide, V2.1 4 Mechanical Overview STATUS Required (Optional) Note: Some enclosure features are noted as o ptional in the drawing below. These features may be use in some chassis desig ns where only top access is allowed for the cag e mounting.
SSI EPS2U Power Supply Design Guide, V2.1 4.1 Airflow Requirements STATUS Recommended The power supply shall have a two-spe ed fan(s) and prov ide cooling to both the supply an d the system. During low-speed fan operation, the power sup ply must not exceed a noise level of 43 dBa measured at one meter on all faces.
SSI EPS2U Power Supply Design Guide, V2.1 5 AC Input Requirements STATUS Required The power supply shall incorpo rate universal power input wi th active power fact or correction, which shall reduce line harmonics in accordance with the E N 61000-3-2 and JEIDA MITI standa rds.
SSI EPS2U Power Supply Design Guide, V2.1 5.4 AC Line Dropout STATUS Required An AC line dropout is defined to be when the AC input dr ops to 0 VAC at any phase of the AC line for any length of time. During an AC dropout of one cycle or less the power supply must meet dynamic voltage regulation requirements over the rated load.
SSI EPS2U Power Supply Design Guide, V2.1 Table 4: AC Line Sag Transient Performance AC Line Sag Duration Sag Operating AC Voltage Li ne Frequency Performance Criteria Continuous 10% Nominal AC Voltag.
SSI EPS2U Power Supply Design Guide, V2.1 6 DC Output Specification 6.1 Output Connectors The power supply shall have one of the two follo wing output connector and wire harness configurations, depending upon the type of 12V rail conf iguratio n needed by the system.
SSI EPS2U Power Supply Design Guide, V2.1 6.1.2 Baseboard power connector STATUS Required Connector housing: 24-Pin Molex 39-0 1-2240 or equivalent Contact: Molex 44476-1111 or equivalent Table 7: P1 Baseboard Power Connector – Common Plane Pin Signal 18 AWG Color Pin Signal 18 AWG Color 1 +3.
SSI EPS2U Power Supply Design Guide, V2.1 2. If 240VA limiting is not a requirement for the power s upply than all +12V outputs are common and ma y have the same wire color (yellow).
SSI EPS2U Power Supply Design Guide, V2.1 6.1.4 Peripheral Power Connectors STATUS Required Connector housing: Amp 1-480424 -0 or equivalent Contact: Amp 61314-1 contact or equivalent Table 11: Periph.
SSI EPS2U Power Supply Design Guide, V2.1 If the optional server signal connecto r is not used on t he power supply or the connector is un plugged, the power supply shall utilize the 3.
SSI EPS2U Power Supply Design Guide, V2.1 6.4 Output Power/Currents STATUS Recommended The following tables define the powe r and current ratings for 480 W, 550 W, 600 W, and 650 W power supplies. The combined output power of all outpu ts shall not exceed the rated output power.
SSI EPS2U Power Supply Design Guide, V2.1 Table 16: 600 W Load Ratings – Split Plane Voltage Minimum Continuous Maximum Continuous Peak +3.3 V 0.8 A 24 A +5 V 0.5 A 20 A +12V1 0 A 12 A 15 A +12V2 0 A 12 A 15 A +12V3 0.9 A 14 A +12V4 0.1 A 8.0 A 13 A -12 V 0 A 0.
SSI EPS2U Power Supply Design Guide, V2.1 6.5 Voltage Regulation STATUS Required The power supply output voltages must stay within the following voltage limits when operating at steady state and dynamic loading conditions. These limits incl ude the peak-pea k ripple/noise specified in Section 5.
SSI EPS2U Power Supply Design Guide, V2.1 6.6 Dynamic Loading STATUS Required The output voltages shall remain within the limits specifi ed in Table 18 for the ste p loading and within the limits specified in Table 20 for the capacitive loadin g.
SSI EPS2U Power Supply Design Guide, V2.1 6.8 Ripple / Noise STATUS Required The maximum allowed ripple/noise out put of the power supply is defined in Table 22. This i s measured over a bandwidth of 0 Hz to 20 MHz at the power su pply output connectors.
SSI EPS2U Power Supply Design Guide, V2.1 V4 V3 V2 V1 T vout_off T vout_on T vout _ rise 10% Vout Vout Figure 2: Output Voltage Timing Table 24: Turn On/Off Timing Item Description MIN MAX UNITS T sb_on_delay Delay from AC being applied to 5 VSB being within regulation.
SSI EPS2U Power Supply Design Guide, V2.1 STATUS Recommended Item Description MIN MAX UNITS T vout_holdup Time all output voltages stay within regulati on after loss of AC. 21 ms T pwok_holdup Delay from loss of AC to deassertion of PWOK. 20 ms T sb_holdup Time 5VSB output voltage stays within regulation after loss of AC.
SSI EPS2U Power Supply Design Guide, V2.1 7 Protection Circuits STATUS Required Protection circuits inside the power supply shall cause only the power su pply’s main outputs to shutdown.
SSI EPS2U Power Supply Design Guide, V2.1 Table 26: Over Current Protection Common Plane Split Plane Voltage Over Current Limit (Iout lim it) Over Current Limit (Iout limit) +3.
SSI EPS2U Power Supply Design Guide, V2.1 8 Control and Indicator Functions The following sections define the input and output si gnals from the power supply. Signals that can be defined as low true use the following co nvention: signal # = low true 8.
SSI EPS2U Power Supply Design Guide, V2.1 8.2 PWOK (Power OK) STATUS Required PWOK is a power OK signal and will be pulled HIGH by the pow er supply to indicate that all the outputs are within the regulation limits of the power supply.
SSI EPS2U Power Supply Design Guide, V2.1 8.3.2 FRU Data Format The information to be contained in the FRU device i s shown in the following table. Table 30: FRU Device Information Area Type Descripti.
SSI EPS2U Power Supply Design Guide, V2.1 8.3.2.2 MultiRecord Area Implement as defined by the IPMI FRU document. The follo wing record types shall be used on this power sup ply: • Power Supply Information (Record Type 0x00) • DC Output (Record Type 0x01) • No other record types are r equired for the power supp ly.
SSI EPS2U Power Supply Design Guide, V2.1 9 MTBF STATUS Recommended The power supply shall have a minimum MTBF at continuous operat ion of 1) 50,000 hours at 100% load and 45 ° C, as calculated by Bellcore RPP, or 2) 100,000 hours demonstrated at 100 % load and 50 ° C.
Ein wichtiger Punkt beim Kauf des Geräts SSI America EPS2U (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie SSI America EPS2U noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für SSI America EPS2U - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von SSI America EPS2U reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über SSI America EPS2U erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon SSI America EPS2U besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von SSI America EPS2U verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit SSI America EPS2U. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei SSI America EPS2U gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.