2 LIBERTY II Standard working pressure 30 psi water , 15 psi steam. All boilers hydrostatically tested — A.S .M.E. * For f orced hot water heating systems where the boiler and all piping are located within the area to be heated, the boiler ma y be selected on the basis of g ross D .
L IBERTY II 3 BOILER LOCA TION Provide a le v el, solid f oundation f or the boiler . Location should be near the chimney so that the Flue Pipe Connector or Breeching to the chim- ney is short and direct. A. The foundation m ust be capable of supporting the weight of the boiler when filled with water: B.
4 LIBERTY II Any oil-fired boiler must ha v e a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney dr aft* is unreliable , CO 2 and ov erfire draft* will change unpredictab ly . DO NO T v ent this boiler to the same chimney flue used b y a fireplace or coal or wood burning furnace or boiler.
L IBERTY II 5 Figure 3a. Appliances located in confined spaces. Air from inside the building. See T able 2 (2.3). Figure 3b. Appliances located in confined spaces. Air from out- doors. See T able 2 (2.4). Figure 3c. Appliances located in confined spaces.
6 LIBERTY II INST ALLING CONTROLS AND A CCESSORIES ON BOILER UNITS Note : Jac ket m ust be installed on boiler units prior to installation of trim. I. STEAM BOILER TRIM, see page 2 f or tapping locations, and figure 4 for illustr ation of steam boiler .
L IBERTY II 7 C . HO T W A TER RADIA TION VENTING - Manual air v ents should be installed at the top of all "drops"(where piping goes downward).
8 LIBERTY II VENT PIPING AND DRAFT REGULA T OR A. V ent pipes must be installed having the same diameter as the boiler outlet. (See page 2) B. V ent pipes and breeching must be pitched upward a minimum of 1/4" per foot. C . Connect vent pipe to the chimney using as f ew elbows as possible .
L IBERTY II 9 CLEANING AND FILLING A NEW STEAM BOILER I. BEFORE USING STEAM BOILER A. Check burner to be cer tain it is ready for firing. DO NOT FIRE into an empty boiler . B. Be prepared to heat raw w ater to at least 180°F . as soon as it is introduced into the boiler .
1 0 LIBERTY II CA UTION: When flushing float type low water cut-off control, hot water and steam will flow out the b low do wn valv e . Blow down v alve is illus- trated below . A. SPECIAL FLUSHING INSTRUCTIONS For ne w boiler installed in old system.
L IBERTY II 11.
1 2 LIBERTY II T T 24 VOLT T HERMOSTAT FLAME DETECTOR BLACK RED WHITE 4 2 1 3 NOZZLE LINE HEATER IF EQUIPPED G REEN GROUNDING SCREW QUICK DISCONNECT PLUG 1 3 L2 L1 W HITE OTHER SAFETY CONTROL BLACK RED GREEN HIGH LIMIT 2 1 ELECTRICAL POWER SUPPLY. PROVIDE DIS CONNECT MEANS AND OVERLO AD PROTECTION AS R EQUIRED BY CODES.
L IBERTY II 13 4 2 1 3 1 2 2 H EX NUT LOOSE WHITE WIRE LEAD TO PROBE BLACK WHITE R ED G REEN L 4006A LOW LIMIT FOR TANKLESS OPTIONAL T T F F FLAME DETECTOR WHITE BLACK RED GREEN GROUNDING SCREW L OW W.
1 4 LIBERTY II.
L IBERTY II 15 BURNER D A T A – BECKETT CF-375 BURNERS FOR P A CKA GED BOILERS ONL Y ( For knoc k ed-down & boiler b urner units see publication no . L-42KB) LD-60 CF-375 2.60 2.25 45˚ P HA GO 135 10 3 1 LD-60 CF-375 2.85 2.25 45˚ P HA GO 160 10 2 2 LD-70 CF-375 3.
1 6 LIBERTY II.
L IBERTY II 17 NO TE: ELECTRODES ARE PRESET A T THE F ACT ORY . REGULA TION OF THE TURBULA TOR AND AIR SHUTTER FOR PROPER COMBUSTION T urbulator Setting 1. Loosen nut, 1, then turn the screw , 2, until the index marker , 3, is aligned with the correct index n umber .
1 8 LIBERTY II.
L IBERTY II 19.
L IBERTY II 20 I. EXTENDED SHUTDOWN, CLEANING OR REMO V AL OF BOILER FROM SER VICE. D ANGER: Use CA UTION when handling chemicals and draining hot w ater from a boiler . Scalding water and/or chemicals can cause per - manent injur y to the skin, e y es and respir ator y system.
Ein wichtiger Punkt beim Kauf des Geräts Slant/Fin BOILERS (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Slant/Fin BOILERS noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Slant/Fin BOILERS - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Slant/Fin BOILERS reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Slant/Fin BOILERS erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Slant/Fin BOILERS besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Slant/Fin BOILERS verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Slant/Fin BOILERS. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Slant/Fin BOILERS gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.