High Speed Counter and Encoder Module
Order Number: PPX:505–81 13–2 Manual Assembly Number: 2586546–0019 Second Edition

Copyright 1992 by Siemens Industrial Automation, Inc.
All Rights Reserved — Printed in USA
Reproduction, transmission or use of this document or contents is not permitted without express consent of Siemens Industrial Automation, Inc. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Technical data is subject to change.
We check the contents of every manual for accuracy at the time it is approved for printing; however, there may be undetected errors. Any errors found will be corrected in subsequent editions. Any suggestions for improvement are welcomed.
Since Siemens Industrial Automation, Inc. does not possess full access to data concerning all of the uses and applications of customer’s products, we do not assume responsibility either for customer product design or for any infringements of patents or rights of others which may result from our assistance.
01/21/92


1.1 Features 1-2
1.2 Inputs 1-4
1.3 Outputs 1-5
1.4 LED Indicators 1-6
1.5 Counting Modes 1-7 1.5.1 Pulse-Counter Mode 1-7 1.5.2 Quadrature Mode Overview 1-8 1.5.3 1X Quadrature 1-8 1.5.4 2X Quadrature 1-9 1.5.5 4X Quadrature 1-10
Overview 1-1 Series 505 High Speed Counter and Encoder Module User’s Manual

The Series 505 High Speed Counter (HSC) module (PPX:505-7002) provides two independent high-speed counter channels.
Each channel has the following features.
Four counter modes:
A 10 kHz count rate with a minimum pulse width of 25 s.
Four inputs:
two count inputs
Two field outputs, each controlled by a separate programmable preset.
LED indicators display the status of the A and B count inputs, and of Y1 and Y2 outputs.
All inputs may be sinking or sourcing (with external 24 VDC power supply).
The HSC module operates asynchronously from the controller scan. You can program the controller to monitor the HSC and/or to provide high-level control of the HSC’s operation. To support these functions, the HSC provides reset, inhibit, output and counter status to the controller and accepts reset and inhibit commands, and preset values from the controller.
! The HSC module controls its four outputs. If the controller switches from the Run mode to the Program mode, the HSC continues to function as programmed, and outputs may be activated by the HSC. This means that if you switch the controller to Program mode, any devices controlled by the four outputs of the HSC will continue to operate as programmed.
1-2 Series 505 High Speed Counter and Encoder Module User’s Manual
Pulse counter · reset · inhibit

Figure 1-1 High Speed Counter Module
Overview 1-3 Series 505 High Speed Counter and Encoder Module User’s Manual

The HSC module has two independent channels. Each channel has four inputs.
Two counter inputs
Each input may be used as either sinking or sourcing (with external 5–24 VDC power supply). The input signals are connected to the field wiring terminal block on the front bezel.
Each channel has two counter inputs — Input A and Input B.
Current flow through the reset input sets the channel’s counter to zero. The counter will be held at zero until the reset input becomes inactive.
Current flow through the inhibit input inhibits the channel from counting. The counter holds at the last value and does not change until the inhibit input becomes inactive.
When in the pulse counter mode, if the A or B input is in a different state at the beginning and end of an inhibit signal, the count will change according to the normal counting logic. If both A and B inputs are in different states, the change may be as much as two counts.
There are also software reset and inhibit functions. See Section 3.
1-4 Series 505 High Speed Counter and Encoder Module User’s Manual
Reset · Inhibit

Each channel has two open collector outputs capable of driving TTL level signals or sinking up to 0.4 Amps of current (at 40C) from an external 24 VDC source and load.
The output transistor (Y or Y) turns on when the count is greater than or equal to the corresponding preset. Figure 1-2 shows the field output operation. You can invert this operation by setting the appropriate bits in the setup word, WY4. See Section 4.1.
Overview 1-5 Series 505 High Speed Counter and Encoder Module User’s Manual

Each channel contains four LED indicators which provide a visual indication of the channel’s status as shown in Figure 1-3.
Figure 1-3 High Speed Counter LEDs
Turns on when there is current flow through the A input.
Turns on when there is current flow through the B input.
Turns on when Output 1 is on.
Turns on when Output 2 is on.
If Reset or Inhibit is turned on, the HSC does not count, and the A and B LEDs are frozen.
1-6 Series 505 High Speed Counter and Encoder Module User’s Manual

1.5.1 Pulse Counter Each channel has two inputs, A and B. In the pulse counter mode, counting Mode occurs on the rising or falling edge of the incoming pulses. The relationship of the states of these two inputs determines the direction of the count. See Table 1-1. Typical devices for counting are high-speed static switches or incremental encoders.
Table 1-1 Determining Count in Pulse Counter Mode
Counter Direction Edge A Input B Input
In the pulse counter mode, the channel senses the edges of the A or the B input to count up or down. See Figure 1-4. To reliably record this transition from low to high, the pulse width must be at least 8 s.
2 3 2 1 8 s min
11 s min
Count Up Count Down
Figure 1-4 Pulse Counter Mode 0
Overview 1-7 Series 505 High Speed Counter and Encoder Module User’s Manual

1.5.2 Quadrature Mode For quadrature mode, each channel counts according to rising and/or falling edges. Typical devices for quadrature inputs are optical encoders. Different quadrature modes are selected based on the resolution required by the application and the encoder used.
1.5.3 1X Quadrature The module counts on the edges of the A input pulses.
When input A leads input B, the HSC counts up on each rising edge of input A.
When input B leads input A, the HSC counts down on the falling edge of input A.
Figure 1-5 illustrates the relationship between inputs A and B and the count value in 1X Quadrature mode.
1 2 1 0
26.7 s min
25 s min
Count Up (A Leading)
Figure 1-5 1X Quadrature Mode
1-8 Series 505 High Speed Counter and Encoder Module User’s Manual

1.5.4 2X Quadrature If input A leads input B, the module counts up on both the rising and falling edges of input A. If input B leads input A, the module counts down on the rising and falling edges of input A.
Figure 1-6 illustrates the relationship between inputs A and B and the count value in the 2X quadrature mode.
1 2 3 4 3 2 1 0
26.7 s min
25 s min
Counts Up (A Leading)
Figure 1-6 2X Quadrature Mode
Overview 1-9 Series 505 High Speed Counter and Encoder Module User’s Manual

1.5.5 4X Quadrature If input A leads input B, the module counts up on rising and falling edges of both input A and input B. If input B leads input A, the module counts down on the rising and falling edges of input A and input B.
Figure 1-7 shows the relationship between inputs A and B and the count value in the 4X quadrature mode.
1 2 3 4 5 6 7 8 7 6 5 4 3 2 1 0
26.7 s min
25 s min
Counts Up (A Leading)
Figure 1-7 4X Quadrature Mode
1-10 Series 505 High Speed Counter and Encoder Module User’s Manual

2.1 Before Installing the Module 2–2 2.1.1 Visual Inspection 2-2 2.1.2 Additional References 2-2 2.1.3 Handling the Module 2-2 2.1.4 General Wiring Considerations 2-3 2.1.5 Hierarchy of Installation 2-4
2.2 Selecting Counter Operation 2-5 2.2.1 Selecting Counter Mode 2-5 2.2.2 Selecting the Reset Filter 2-6
2.3 Inserting the Module in the I/O Base 2-7
2.4 Wiring the Module 2-8 2.4.1 Wiring the Terminal Block 2-8 2.4.2 Powering Up the Module 2-8
2.5 Logging the Module into the Controller 2-10 2.5.1 Updating the I/O Configuration Definition 2-10 2.5.2 Selecting the I/O Configuration 2-10 2.5.3 Viewing I/O Configuration Chart 2-11
Installation 2-1 Series 505 High Speed Counter and Encoder Module User’s Manual

2.1.1 Visual Inspection If there is any visible damage to the module, contact your Siemens Industrial Automation, Inc. distributor for replacement.
2.1.2 Additional Refer to the manuals listed below for instructions on installing, References programming, and troubleshooting your Series 505E controller.
SIMATIC TI545 System Manual (PPX:545–8101)
SIMATIC TI525/TI535 Hardware and Installation Manual (PPX:505–8103)
SIMATIC TI505 Programming Reference Manual (PPX:505–8104)
2.1.3 Handling the Many integrated circuit (IC) devices are susceptible to damage by the Module discharge of static electricity. Follow the suggestions listed below to reduce the probability of damage to these devices when you are handling a controller, a base controller, or any of the I/O modules.
Both the module and the person handling the module should be at the same ground potential. To accomplish this, ensure the following.
The module is transported in an anti-static container or antistatic material.
The work area has a conductive pad with a lead connecting it to a common ground.
You are grounded by making contact with the conductive pad and/or by wearing a grounded wrist strap.
2-2 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

2.1.4 General Wiring The count, inhibit, and unfiltered reset inputs are high-speed inputs which Considerations may respond to noise present on the lines. To avoid problems, follow these guidelines when installing the HSC module.
Use the shortest possible wires.
Avoid placing signal wires parallel to high-energy wires. If the two must meet, cross them at right angles.
Avoid bending the wire into sharp angles.
Use wireways for wire routing.
When using shielded wires, ground them only at the source end for better noise immunity.
Place wires so that they don’t interfere with existing wiring.
Label the wires.
In some installations when both the HSC and TI505-49XX series of relay modules are used, false counts may be induced when switching high voltage in the relay module, (voltage > 40 Vrms). This is the result of internal arcing of the relay contacts.
If you encounter this problem, place a snubber consisting of a 47 ohm 1/4 watt resistor and a 0.022 Fd capacitor across the relay contact terminals on the terminal block. Snubbers were not included in the relay modules in order to meet the need for lower current leakage in many applications.
: Snubber components must be UL component recognized and/or CSA Certified for use across the rated voltage being switched by the relay module.
Installation 2-3 Series 505 High Speed Counter and Encoder Module User’s Manual

2.1.5 Hierarchy of Figure 2-1 provides a simple flowchart of the installation process. Installation
Set Jumper Configuration on Module
Figure 2-1 Hierarchy of Installation
2-4 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

2.2.1 Selecting The HSC module has two channels. You can configure each channel Counter Mode to operate in any of four counter modes.
Prior to installing the module into the I/O backplane, configure the module by setting the jumper for each channel. Figure 2-2 shows the location of the jumpers on the printed circuit board. The top set of four pins set the counter mode for Channel 1. The bottom set of four pins set the counter mode for Channel 2. The default setting for the jumpers is 1X Quadrature mode for both channels.
CH 1 Jumper in SLW (filtered) position
CH 2 Jumper in FST (unfiltered) posi- tion
Figure 2-2 Jumper Settings
Each channel must have one (and only one) jumper installed.
Installation 2-5 Series 505 High Speed Counter and Encoder Module User’s Manual

2.2.2 Selecting the Some applications require faster response on the reset input line than Reset Filter the standard 3.75-ms filter allows. For faster response, select the optional 0.95-ms filter. (The 0.9-ms filter is more sensitive to noisy signals, as noted in the Environmental Specifications in Appendix B.)
The reset filter may be selected independently for each input channel by placing the jumper in the (fast) or (slow) position as shown in Figure 2-2.
2-6 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

The HSC is a single-wide module. Insert it into any available slot on any Series 505 I/O base. Do not touch the printed circuit board while inserting the module. This could cause electrostatic damage to the components on the board. Insert the module as shown in Figure 2-3.
! To minimize potential shock, turn off power to the I/O base and any modules installed in the base before inserting or removing a module. Failure to do so may result in potential injury to personnel or damage to equipment.
Figure 2-3 Inserting the Module into the I/O Base
Installation 2-7 Series 505 High Speed Counter and Encoder Module User’s Manual
Base Plane Connectors ·

2.4.1 Wiring the Wiring the module consists of wiring the the input and output signals. Terminal Block See Figure 2-4 and Figure 2-5 for general guidelines. All connections are made at the module terminal block. See Figure 2-5. Output returns for Channel 1 and 2 are internally connected.
Use the Terminal Block Worksheet in Appendix B for planning your wiring.
! Turn off power to the I/O base and any modules installed in the base before inserting or removing a module. Failure to do so may cause potential injury to personnel or can damage equipment.
2.4.2 Powering Up After wiring the terminal block for the HSC, restore power to the the Module base.
1 cm Wire Gauge: 22–16
Figure 2-4 Wiring Guidelines
2-8 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

5–24 VDC
5–24 VDC
Figure 2-5 Sample Terminal Block Wiring Diagram
Installation 2-9 Series 505 High Speed Counter and Encoder Module User’s Manual

2.5.1 Updating the I/O After inserting the module into the base, update the I/O configuration Configuration in the controller. The module does not automatically onfigure itself. Definition A VPU or other programming device must be connected to the controller to register and verify controller module communication.
2.5.2 Selecting the I/O With your VPU or other programming device, select the I/O Configuration Configuration option. For example, if you have the module inserted into the first slot of the first I/O base, configure it as displayed in Figure 2-6. Refer to the manual that came with the programming device for instructions.
The HSC module is logged in as three input words (WX) and five output words (WY).
Displays number of the current base.
Slot Address X Y WX WY Function I/O Number of Bit and Word I/O Special
1 2 3 4 5 6
0001 0000
00
00
No
00
00
Install the HSC into any avail- able I/O slot on the Series 505 base.
e The HSC is not an SF Module. The default for this definition is NO.
Figure 2-6 Sample I/O Definition Chart
2-10 Installation Series 505 High Speed Counter and Encoder Module User’s Manual
0000 0000 · No No

2.5.3 Viewing the I/O Use SHOW to view the I/O Configuration Chart. If the HSC is Configuration installed in slot 1, for channel 1, base 00, the I/O chart will appear Chart as displayed in Figure 2-7.
00000 WX001 WX002 WX003 WY004 WY005 WY006 WY007 WY008
Slot 2 Slot 3 Slot 4 Slot 5 Slot 6
00000
00000
00000
00000
00000
00000
00000
00000
Figure 2-7 I/O Configuration Chart
Installation 2-11 Series 505 High Speed Counter and Encoder Module User’s Manual
Slot 1 ·

3.1 Controller Input Words 3-2
3.1.1 WX1 (Status Word) 3-2 3.1.2 WX2 and WX3 (Channel Count) 3-3 3.1.3 WY4 (Setup Word) 3-3 3.1.4 WY5 – WY8 (Preset Words) 3-4 3.1.5 I/O Update Consideration 3-4
Programming 3-1 Series 505 High Speed Counter and Encoder Module User’s Manual

The HSC module is configured as three word inputs (WX) and five word outputs (WY). It occupies eight words of the controller’s word image register.
3.1.1 WX1 (Status Word) Word 1 (WX) is the module’s status word. Eight bits provide the status of each of the two channels. Figure 3-1 shows the format of the status word.
MSB
CH 1 — RESET ST ATUS
(1 = Counter reset)
CH 1 — INHIBIT STATUS (1 = Count inhibited)
CH 1 — OUTPUT 2 ST ATUS
CH 2 — RESET STATUS (1 = Counter reset)
(1 = Counts inhibited)
CH 2 — OUTPUT 1 STATUS (1 = On)
CH 2 — OUTPUT 2 STATUS (1 = On)
Reserved and will be returned as zeros
Figure 3-1 Status Word Format
Each channel has a Reset Status bit in the status word. If the channel’s RESET field input is active, this bit will be 1; otherwise this bit will be 0.
The Reset Command bit (see Setup Word, Section 3.1.3) does not affect the reset status bit.
Programming 3-2 Series 505 High Speed Counter and Encoder Module User’s Manual
(1 = On) · (1 = On)

Each channel has an Inhibit Status bit in the status word. If the channel’s field input is active or if its Inhibit Command bit is 1 (see Setup Word, Section 3.1.3), this bit will be 1 and the counter will not count. Otherwise, this bit will be 0.
Each channel has an Output 1 Status and an Output 2 Status bit in the status word. If the corresponding field output is on, the bit will be 1. Otherwise, the bit will be 0.
3.1.2 WX2 and WX3 Word 2 (WX2) contains the current value of the Channel 1 count (Channel Count) register, and Word 3 (WX3) contains the current value of the Channel 2 count register. These values are unsigned integers between 0 and 65,535 (inclusive). 3.1.3 WY4 (Setup Word) Word 4 (WY4) is the module setup word. The controller uses eight bits to control the HSC module’s operation. See Figure 3-2.
MSB
CH 1 — RESET (1 = Reset counter; default: 0)
CH 1 — INHIBIT (1 = Inhibits counts; default: 0)
CH 1 — OUTPUT 1 0: Count P = On (default) 1: Count < P = On CH 1 — OUTPUT 2
CH 2 — RESET (1 = Reset counter; default: 0)
CH 2 — INHIBIT (1 = Inhibits counts; default: 0)
Reserved and should be set to 0 (off)
Figure 3-2 Setup Word Format
Programming 3-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Both channels have a Reset Command bit. A transition from 0 (off) to 1 (on) of the Reset Command acts as a one-shot (providing a momentary reset of the channel), setting the count to 0. Even though the bit remains 1, counting resumes.
Both channels have an Inhibit Command bit. When this bit is set to 1, the channel stops counting.
When in the pulse counter mode, if the A or B input is in a different state at the beginning and end of an inhibit signal, the count will change according to the normal counting logic. If both A and B inputs are in different states, the change may be as much as two counts.
The output level bit specifies when the outputs for each channel turn on.
Setting the output level bit to 0 turns the output on when the current count is greater than or equal to the preset. If the current count is less than the preset, the output is off.
Setting the output level bit to 1 turns the output on when the current count is less than the preset. If the current count is greater than or equal to the preset, the output is off.
3.1.4 WY5 – WY8 Words WY5 through WY8 specifies preset values for each channel. (Preset Words) You can specify any value between 0 and 65,535.
specifies the value for Preset 1, Channel 1.
specifies the value for Preset 2, Channel 1.
specifies the value for Preset 1, Channel 2.
specifies the value for Preset 2, Channel 2.
3.1.5 I/O Update In each scan, the controller reads the module WX words before updating Consideration the WY words. For example, during a scan when the controller resets the module, the WX word(s) contain counter values existing prior to the reset.
Programming 3-4 Series 505 High Speed Counter and Encoder Module User’s Manual

Symptom Probable Cause Corrective Action
Input LED is not on and Output LED is not on
No power to board
Check for bent pins on board connector
Check your base power supply Check wiring Check encoder or field inputs
Problems with input signals, or output being reset or inhibited
Check Reset and Inhibit bits in Setup word (WY4)
Counts in wrong direction
Reverse wiring for inputs A and B
Input wires substantially different lengths
Check that wires are as short as possible, and make wires the same length (if possible)
Incorrect count Connections wrong
Trace wiring connections
Input wires substantially different lengths
Check that wires are as short as possible, and make wires the same length (if possible)
Broken wire Check continuity
Counts erratically Wrong quadrature mode or 2 jumpers on same chan- nel
Check jumper position and condition of jumper (metal insert intact)
See wiring considerations ( Section 2.1.4)
Broken wire Check continuity
Does not count Count being reset or in- hibited
Check Reset and Inhibit signals from field
Check Reset and Inhibit bits in Setup word (WY4)
Broken wire Check continuity
Counts too fast or too slow
Pulse too narrow, or frequency too high
Use slower gear ratio and higher resolution count
Check signal wire noise
Controller does not communicate with module
Module not configured in controller I/O configuration table
Nonfatal error as a result of the module
Module configured incorrectly in controller
Module has failed self-diagnostics
Return module for repair
Troubleshooting 4-1 Series 505 High Speed Counter and Encoder Module User’s Manual

To check the operation of the module, follow these steps.
Module outputs will turn on during this procedure.
Using the default configuration, the outputs should turn on.
The outputs should turn off.
Before resuming normal operation, clear any words that you have forced. Otherwise, these words remain forced during operation and could yield unexpected results.
If you used the setup word to configure the module, then the output follows your configuration.
To check the output operation look at the counter status word (WX1), the outputs correspond to the following bits.
Channel 1, Output 1 bit 3
Channel 1, Output 2 bit 4
0 = Output off 1 = Output on
Channel 2, Output 1 bit 7
Channel 2, Output 2 bit 8
4-2 Troubleshooting Series 505 High Speed Counter and Encoder Module User’s Manual

5.1 Sprayer Example 5-2
5.1.1 Description 5-2 5.1.2 Solution 5-3
5.2 Flow Rate Example 5-5
5.2.1 Description 5-5 5.2.2 Solution 5-5
5.3 Tank Filling Example 5-6
5.3.1 Description 5-6 5.3.2 Solution 5-6
Applications 5-1 Series 505 High Speed Counter and Encoder Module User’s Manual

5.1.1 Description A reversible DC motor drives a paint sprayer up and down a vertical assembly. A quadrature encoder on the drive shaft senses the direction and relative position of the sprayer. Channel 1 of the HSC will be used to enable the sprayer during a pre-defined section of travel. (See Figure 5-1.) The encoder resolution is 500 cycles per revolution. One shaft revolution equals 1 inch of sprayer travel. When encoder signal A leads, the direction of travel is up.
ÉÉÉÉÉÉÉÉÉÉ
LS2 – Reverse Motor
LS1 – (Home) Reverses Motor
Figure 5-1 Sprayer Application
Applications 5-2 Series 505 High Speed Counter and Encoder Module User’s Manual
“Stop Spray” · “Start Spray”

5.1.2 Solution Connect encoder signals A and B to inputs A and B of the HSC. See Figure 5–2. Limit switch 1 (sprayer home) drives channel 1 Reset. Channel 1 outputs 1 and 2 are wire ORed and drive the sprayer enable. Select 1X Quadrature mode for channel 1, setup channel 1 output 1 to turn off when count preset, output 2 to turn on when count preset. Presets 1 and 2 are loaded with the Start Sprayer and Stop Sprayer counts, respectively. The Start Sprayer count = 500 X Distance (inches) from LS1 to Start Sprayer position. The Stop Sprayer count = 500 X Distance (inches) from LS1 to Stop Sprayer position.
Figure 5-2 HSC Connections
As the sprayer moves up and down, the channel 1 outputs and the sprayer enable signal levels produce the waveform shown in Figure 5-3.
Travels Up Travels Down
OUTPUT 1 OUTPUT 2
OFF ON OFF ON OFF
Figure 5-3 Waveform Pattern
Applications 5-3 Series 505 High Speed Counter and Encoder Module User’s Manual

SETUP CHANNEL 1 OUTPUT 2 TO GO LOW AT PRESET
CLEAR CHANNEL 1 SETUP WORD
LDC1
BITS1
BITS2
A:
WY4
A:
WY4
A:
WY4
N=
N=
N=
LOADS CHANNEL 1 PRESETS 1 & 2 FROM V200 & V201
INHIBIT CHANNEL 1 BIT IS CLEARED COUNTING IS ENABLED
MOVW1
BITC23
A:
A:
WY4
B: WY5
N=
N=
Figure 5-4 Ladder Logic for Sprayer Example
Applications 5-4 Series 505 High Speed Counter and Encoder Module User’s Manual

5.2.1 Description A flow meter outputs 200 pulses per gallon. The program requires calculation of flow rate in gallons per minute (GPM). 5.2.2 Solution Configure the HSC as WX9–WX11, WY12–WY16. Attach channel 1 to the flow meter. The HSC accumulates flow meter pulses for the duration of a 1-second fast timer. In the controller, accumulated pulses are scaled to GPM by the following calculation (using the controller memory locations).
Following each calculation, reset the HSC, restart the Timer, and perform a new calculation 1 second later.
: ONE SECOND TIMER HAS EXPIRED, COMPUTE FLOW RESTART TIMER ON NEXT SCAN
TMRF2
P= 01.000
: SCALE COUNTER VALUE IN GALS/MINUTE PUT RESULTS IN LOCATIONS V23–V24, RESET HSC CHANNEL 1
MULT1
DIV1
BITS1
A: WX10
A: V21
A:
WY12
B: C:
V20 V21
B: C:
V19 V23
N=
: TURN OFF CHANNEL 1 RESET TO HSC
BITC1
A:
WY12
N=
Figure 5-5 Ladder Logic for Flow Rate Example
Applications 5-5 Series 505 High Speed Counter and Encoder Module User’s Manual

5.3.1 Description The HSC module measures the volume of liquid and control the filling valve. (See Figure 5-6.) A flow meter, generating 200 pulses per gallon, is connected to the HSC channel 2, input A. Output 2 controls the filling valve. In this example, the HSC operates in the pulse counter mode.
Solution A count of 100,000 pulses is required to fill the tank to 500 gallons. As this would overflow the HSC, the following RLL is used to count 10 sets of 10,000 pulses before closing the filling valve. In this program, output 1 is used to indicate 10,000 pulses. Since the HSC runs asynchronous to the PLC, the program accumulates overcounts for each loop and adjusts the final loop to reach the exact count. The program utilizes the fact that the HSC WX’s are read before the WY’s are written in an I/O cycle.
Several V memory locations are used in the program, their initial values are:
V200 = 10,000 = channel 2, preset 1
V201 = 30,000 = channel 2, preset 2 initial value
V100 = 0 (overcounts will be accumulated here)
Figure 5-6 Tank Filling Application
Applications 5-6 Series 505 High Speed Counter and Encoder Module User’s Manual
· HSC Channel 2

C140 IS USED TO INITIATE/TERMINATE FILLING
C140 C256
: RESET HSC, LOAD INIT AL PRESETS
C140 C1
Y20
LDC4
BITS1
MOVW1
A: WY4
A: WY4
A: V200
B: WY7
N = 0
N = 5
N = 2
C141 : CLEAR RESET BIT
BITC1
A: WY4
N = 5
Y20
: ENABLE LIQUID FLOW
C1 Y20
Y20 C140
Figure 5-7 Ladder Logic for Tank Filling Example
Applications 5-7 Series 505 High Speed Counter and Encoder Module User’s Manual

: ACCUMULA TE THE OVERCOUNTS
SUB1
ADD1
A: WX3
A: V101
B: V200
B: V100
C: V101
C: V100
: AFTER 90,000 PULSES, SUBTRACT THE OVERCOUNTS FROM 10,000
AND LOAD THE REMAINING COUNT INTO PRESET 2.
SUB2
MOVW2
P = 9
A: V200
A: V201
B: V100
B: WY7
WY8 C140
C:
N = 1
: TEST FOR COMPLETION OF 100,000 COUNTS, INHIBIT FURTHER
COUNTS, AND CLEAR OVERCOUNT ACCUMULATOR. C256 WILL THEN TURN OFF C140 AND DISABLE THE VALVE.
BITP2
BITS2
LDC3
A: WX1
A: WY4
A: V100
N = 6 N = 8
N = 0
OR GREATER, RESET COUNTER AND START NEW COUNT.
BITP5
BITS5
A: WX1
A: WY4
N = 7
N = 5
Figure 5-7 Ladder Logic for Tank Filling Example (continued)
Applications 5-8 Series 505 High Speed Counter and Encoder Module User’s Manual

Terminal Block Worksheet A-1 Series 505 High Speed Counter and Encoder Module User’s Manual

B.1 Environmental Specifications B-2
B.2 Electrical Specifications B-3
B.3 Additional Compliances B-6
Specifications B-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Table B-1 Environmental Specifications
Operating Temperature 0 to 60C (32 to 140F)
Storage Temperature –40 to 70C (–40 to 158F)
Relative Humidity 5% to 95% noncondensing
Pollution Degree 2, IEC 664, 664A
Sinusoidal IEC 68–2–6, Test Fc; 0.15 mm, peak-to-peak, 10-57 Hz; 1.0 g 57-150 Hz Random NAVMAT P–9492 or IEC 68–2–34, Test Fdc with 0.04 g/Hz, 80–350 Hz, and 3 dB/octave rolloff, 80–20 Hz and 350–2000 Hz at 10 min/axis
Impact Shock IEC 68–2–27, Test Ea; Half Sine, 15 g, 11 ms
Electrostatic Discharge2 IEC 801, Part 2, Level 4 (15 kV)1
Electrical Noise Immunity IEC 801, Part 4, Level 3 Conducted2 MIL STD 461B, Part 4; CS01, CS02, CS061 IEC 255–4, Appendix E1 EEC 4517/79 Com(78) 766 Final, Part 4 IEEE 472, 2.5 kV
Radiated IEC 801, Part 3, Level 3 MIL STD 461B, Part 4; RS01, RS02
Corrosion Protection All parts are of corrosion resistant material or are plated or painted as corrosion protection.
Agency Approvals UL Listed, CSA Certified
1The unfilltered reset input may be susceptible to these types of EMI. 2The module responds to noise signals at its count or inhibit inputs that are within its passband.
Specifications B-2 Series 505 High Speed Counter and Encoder Module User’s Manual
Vibration

Table B-2 Electrical Specifications
Duty Count Mode Quadrature Mode
10% 10 Khz 4 Khz 20% 25 Khz 8 Khz 25% 30 Khz 10 Khz 30% 35 Khz 12 Khz 40% 50 Khz 15 Khz 50% 45 Khz 15 Khz 60% 35 Khz 15 Khz
On voltage: 4 to 28 VDC, Class 2 supply Current on: 8 to 16 mA Off voltage: –1.5 to 1.5 VDC Current off: 0 to 1 mA
Volt–Ampere Curve for Count Inputs
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉ
4 6 8 10 12 14 16
ÉÉ Off Region Transition Region On Region
Specifications B-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Count inputs are constant current type inputs.
Reset and Inhibit Inputs:
On voltage: to 28 VDC, Class 2 supply Current on: 2 to 40 mA Off voltage: –1.5 to 1.5 VDC Current off: 0 to 0.75 mA Reset delay time: unfiltered 950 s on 950 s off filtered 3.75 ms on 5.00 ms off Inhibit delay time: 200 s on 200 s off
Volt–Ampere Curve for Reset and Inhibit Inputs
ÉÉÉ
10 20 30 40
Off Region Transition Region On Region
Specifications B-4 Series 505 High Speed Counter and Encoder Module User’s Manual
Min Max · Vin (Volts) · Iin (mA)

User voltage: 28 VDC max Voltage drop: 1.8 VDC max. @ 400 mA
1.0 VDC max. @ 25 mA Leakage current: 500 A max Peak current: 500 mA for 1 ms Output current:
1 Point per channel
2 Points per channel
20 40 60 80 100
Isolation:
User-side to P/C-side 1500 V rms
Channel 1 to 2 (inputs) 1500 V rms
Channel 1 to 2 (outputs) 0 V rms
Inputs to outputs 1500 V rms
Power Required from Base: 2.5 W
Response Time 1.1 ms (Input pulse to output action)
Specifications B-5 Series 505 High Speed Counter and Encoder Module User’s Manual

In addition, the system complies with applicable requirements of Verband Deutscher Elektrotechniker (VDE) 0160: Electrical Equipment
Series 505 products have been developed with consideration of the draft standard for programmable controllers as described in the proposed standard of the International Electrotechnical Commission Committee (IEC–65A/WG6, Part 2).
Information concerning product reliability and compliance to the IEC or other standards can be provided upon request. Contact your Siemens Industrial Automation, Inc. distributor for additional information.
Specifications B-6 Series 505 High Speed Counter and Encoder Module User’s Manual

We would like to know what you think about our user manuals so that we can serve you better. How would you rate the quality of our manuals?
Excellent Good Fair Poor
Accuracy Organization Clarity Completeness Overall design Size Index
Would you be interested in giving us more detailed comments about our manuals?
Yes! Please send me a questionnaire.
No. Thanks anyway.
Your Name:
Title:
Company Name:
Company Address:

NO POST AGE
NECESSARY
IF MAILED
IN THE UNITED ST ATES
BUSINESS REPL Y MAIL
FIRST CLASS PERMIT NO.3 JOHNSON CITY , TN
POST AGE WILL BE P AID BY ADDRESSEE
SIEMENS INDUSTRIAL AUTOMATION, INC. 3000 BILL GARLAND RD. P.O. BOX 1255 JOHNSON CITY TN 37605–1255

T
Quadrature Mode, quadruple count, 1-10
Terminal block, 2-8
wiring diagram, 2-9 worksheet, 2-8
double-count, 1-9 single-count, 1-8
Quadruple count, quadrature mode, 1-10
R
Using status words, 3-2
S
Wiring, 2-3, 2-8
Static electricity, 2-2

SIMATIC is a registered trademark of Siemens AG.
Series 505 and TISOFT are trademarks of Siemens Industrial Automation, Inc.
Texas Instruments and TI are registered trademarks of Texas Instruments Incorporated.
TI505, TI525, TI535, and TI545 are trademarks of Texas Instruments Incorporated.
UL is a registered trademark of Underwriters Laboratories.
Häufige Probleme, wahrscheinliche Ursachen und Lösungen.
| Problem | Mögliche Ursache | Abhilfe | |
|---|---|---|---|
| Input LED is not on and Output LED is not on | No power to board | Re-seat board | p.32 |
| Input LED is not on and Output LED is not on | Check for bent pins on board connector | p.32 | |
| Input LED is not on and Output LED is not on | Check your base power supply | p.32 | |
| Input LED is not on and Output LED is not on | Problems with input signals, or output being reset or inhibited | Check wiring | p.32 |
| Input LED is not on and Output LED is not on | Check encoder or field inputs | p.32 | |
| Input LED is not on and Output LED is not on | Check Reset and Inhibit bits in Setup word (WY4) | p.32 | |
| Counts in wrong direction | Connections wrong | Reverse wiring for inputs A and B | p.32 |
| Counts in wrong direction | Input wires substantially different lengths | Check that wires are as short as possible, and make wires the same length (if possible) | p.32 |
| Incorrect count | Connections wrong | Trace wiring connections | p.32 |
| Incorrect count | Input wires substantially different lengths | Check that wires are as short as possible, and make wires the same length (if possible) | p.32 |
| Incorrect count | Broken wire | Check continuity | p.32 |
| Counts erratically | Wrong quadrature mode or 2 jumpers on same chan- nel | Check jumper position and condition of jumper (metal insert intact) | p.32 |
| Counts erratically | Signal wire noise | See wiring considerations ( Section 2.1.4) | p.32 |
| Counts erratically | Broken wire | Check continuity | p.32 |
| Does not count | Count being reset or in- hibited | Check Reset and Inhibit signals from field | p.32 |
| Does not count | Check Reset and Inhibit bits in Setup word (WY4) | p.32 | |
| Does not count | Broken wire | Check continuity | p.32 |
| Counts too fast or too slow | Pulse too narrow, or frequency too high | Use slower gear ratio and higher resolution count | p.32 |
| Counts too fast or too slow | Check quadrature mode | p.32 | |
| Counts too fast or too slow | Check signal wire noise | p.32 | |
| Counts too fast or too slow | Marginal input signal | p.32 | |
| Controller does not communicate with module | Module not configured in controller I/O configuration table | Configure module | p.32 |
| Nonfatal error as a result of the module | Module configured incorrectly in controller | Reconfigure the module | p.32 |
| Nonfatal error as a result of the module | Module has failed self-diagnostics | Return module for repair | p.32 |