Titlep.1Contentsp.31 Overviewp.71.1 Featuresp.81.2 Inputsp.101.3 Outputsp.111.4 LED Indicatorsp.121.5 Counting Modesp.131.5.1 Pulse Counter Modep.131.5.2 Quadrature Modep.141.5.3 1X Quadraturep.141.5.4 2X Quadraturep.151.5.5 4X Quadraturep.162 Installationp.172.1 Before Installing the Modulep.182.1.1 Visual Inspectionp.182.1.2 Additional Referencesp.182.1.3 Handling the Modulep.182.1.4 General Wiring Considerationsp.192.1.5 Hierarchy of Installationp.202.2 Selecting Counter Operationp.212.2.1 Selecting Counter Modep.212.2.2 Selecting the Reset Filterp.222.3 Inserting the Module in the I/O Basep.232.4 Wiring the Modulep.242.4.1 Wiring the Terminal Blockp.242.4.2 Powering Up the Modulep.242.5 Logging the Module into the Controllerp.262.5.1 Updating the I/ O Configuration Definitionp.262.5.2 Selecting the I/O Configurationp.262.5.3 Viewing the I/ O Configuration Chartp.273 Programmingp.283.1 Controller Input Wordsp.293.1.1 WX1 (Status Word)p.293.1.2 WX2 and WX3 (Channel Count)p.303.1.3 WY4 (Setup Word)p.303.1.4 WY5 - WY8 (Preset Words)p.313.1.5 I/O Update Considerationp.314 Troubleshootingp.324.1 Checking the Operation of the Modulep.335 Applicationsp.345.1 Sprayer Examplep.355.1.1 Descriptionp.355.1.2 Solutionp.365.2 Flow Rate Examplep.385.2.1 Descriptionp.385.2.2 Solutionp.385.3 Tank Filling Examplep.395.3.1 Descriptionp.395.3.2 Solutionp.39A Terminal Block Worksheetp.42B Specificationsp.43B.1 Environmental Specificationsp.44B.2 Electrical Specificationsp.45B.3 Additional Compliancesp.48Customer Registrationp.49Indexp.51
Page 1 of the Siemens SIMATIC 505 user manual — User Manual
Seite 1 · Zum Vergrößern klicken
Seite 1

SIMA TIC 505

High Speed Counter and Encoder Module

User Manual

Order Number: PPX:505–81 13–2 Manual Assembly Number: 2586546–0019 Second Edition

Page 2 of the Siemens SIMATIC 505 user manual — Title
Seite 2 · Zum Vergrößern klicken
Seite 2

Copyright 1992 by Siemens Industrial Automation, Inc.

All Rights Reserved — Printed in USA

Reproduction, transmission or use of this document or contents is not permitted without express consent of Siemens Industrial Automation, Inc. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.

Technical data is subject to change.

We check the contents of every manual for accuracy at the time it is approved for printing; however, there may be undetected errors. Any errors found will be corrected in subsequent editions. Any suggestions for improvement are welcomed.

Since Siemens Industrial Automation, Inc. does not possess full access to data concerning all of the uses and applications of customer’s products, we do not assume responsibility either for customer product design or for any infringements of patents or rights of others which may result from our assistance.

01/21/92

Page 3 of the Siemens SIMATIC 505 user manual — Inhaltsverzeichnis
Seite 3 · Inhalt
Inhalt

Inhalt

Titlep.1Contentsp.31 Overviewp.71.1 Featuresp.81.2 Inputsp.101.3 Outputsp.111.4 LED Indicatorsp.121.5 Counting Modesp.131.5.1 Pulse Counter Modep.131.5.2 Quadrature Modep.141.5.3 1X Quadraturep.141.5.4 2X Quadraturep.151.5.5 4X Quadraturep.162 Installationp.172.1 Before Installing the Modulep.182.1.1 Visual Inspectionp.182.1.2 Additional Referencesp.182.1.3 Handling the Modulep.182.1.4 General Wiring Considerationsp.192.1.5 Hierarchy of Installationp.202.2 Selecting Counter Operationp.212.2.1 Selecting Counter Modep.212.2.2 Selecting the Reset Filterp.222.3 Inserting the Module in the I/O Basep.232.4 Wiring the Modulep.242.4.1 Wiring the Terminal Blockp.242.4.2 Powering Up the Modulep.242.5 Logging the Module into the Controllerp.262.5.1 Updating the I/ O Configuration Definitionp.262.5.2 Selecting the I/O Configurationp.262.5.3 Viewing the I/ O Configuration Chartp.273 Programmingp.283.1 Controller Input Wordsp.293.1.1 WX1 (Status Word)p.293.1.2 WX2 and WX3 (Channel Count)p.303.1.3 WY4 (Setup Word)p.303.1.4 WY5 - WY8 (Preset Words)p.313.1.5 I/O Update Considerationp.314 Troubleshootingp.324.1 Checking the Operation of the Modulep.335 Applicationsp.345.1 Sprayer Examplep.355.1.1 Descriptionp.355.1.2 Solutionp.365.2 Flow Rate Examplep.385.2.1 Descriptionp.385.2.2 Solutionp.385.3 Tank Filling Examplep.395.3.1 Descriptionp.395.3.2 Solutionp.39A Terminal Block Worksheetp.42B Specificationsp.43B.1 Environmental Specificationsp.44B.2 Electrical Specificationsp.45B.3 Additional Compliancesp.48Customer Registrationp.49Indexp.51
Page 7 of the Siemens SIMATIC 505 user manual — Chapter 1 Overview
Seite 7 · Zum Vergrößern klicken
Seite 7

Chapter 1 Overview

1.1 Features 1-2

1.2 Inputs 1-4

1.3 Outputs 1-5

1.4 LED Indicators 1-6

1.5 Counting Modes 1-7 1.5.1 Pulse-Counter Mode 1-7 1.5.2 Quadrature Mode Overview 1-8 1.5.3 1X Quadrature 1-8 1.5.4 2X Quadrature 1-9 1.5.5 4X Quadrature 1-10

Overview 1-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 8 of the Siemens SIMATIC 505 user manual — 1.1 Features
Seite 8 · Zum Vergrößern klicken
Seite 8

1.1 Features

The Series 505 High Speed Counter (HSC) module (PPX:505-7002) provides two independent high-speed counter channels.

Each channel has the following features.

Four counter modes:

Quadrature counter modes1X, 2X, 4X

A 10 kHz count rate with a minimum pulse width of 25 s.

Four inputs:

two count inputs

Two field outputs, each controlled by a separate programmable preset.

LED indicators display the status of the A and B count inputs, and of Y1 and Y2 outputs.

All inputs may be sinking or sourcing (with external 24 VDC power supply).

The HSC module operates asynchronously from the controller scan. You can program the controller to monitor the HSC and/or to provide high-level control of the HSC’s operation. To support these functions, the HSC provides reset, inhibit, output and counter status to the controller and accepts reset and inhibit commands, and preset values from the controller.

! The HSC module controls its four outputs. If the controller switches from the Run mode to the Program mode, the HSC continues to function as programmed, and outputs may be activated by the HSC. This means that if you switch the controller to Program mode, any devices controlled by the four outputs of the HSC will continue to operate as programmed.

1-2 Series 505 High Speed Counter and Encoder Module User’s Manual

Pulse counter · reset · inhibit

Page 9 of the Siemens SIMATIC 505 user manual — 1.1 Features
Seite 9 · Zum Vergrößern klicken
Seite 9

Figure 1-1 High Speed Counter Module

Overview 1-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 9 more labels / short text on this page
Base Plane Connector · Bezel Screw · LEDs · Printed Circuit Board · Terminal · Block · Front Bezel · Bezel Screw ·
Page 10 of the Siemens SIMATIC 505 user manual — 1.2 Inputs
Seite 10 · Zum Vergrößern klicken
Seite 10

1.2 Inputs

The HSC module has two independent channels. Each channel has four inputs.

Two counter inputs

Each input may be used as either sinking or sourcing (with external 5–24 VDC power supply). The input signals are connected to the field wiring terminal block on the front bezel.

Each channel has two counter inputs — Input A and Input B.

Current flow through the reset input sets the channel’s counter to zero. The counter will be held at zero until the reset input becomes inactive.

Current flow through the inhibit input inhibits the channel from counting. The counter holds at the last value and does not change until the inhibit input becomes inactive.

When in the pulse counter mode, if the A or B input is in a different state at the beginning and end of an inhibit signal, the count will change according to the normal counting logic. If both A and B inputs are in different states, the change may be as much as two counts.

There are also software reset and inhibit functions. See Section 3.

1-4 Series 505 High Speed Counter and Encoder Module User’s Manual

Reset · Inhibit

Page 11 of the Siemens SIMATIC 505 user manual — 1.3 Outputs
Seite 11 · Zum Vergrößern klicken
Seite 11

1.3 Outputs

Each channel has two open collector outputs capable of driving TTL level signals or sinking up to 0.4 Amps of current (at 40C) from an external 24 VDC source and load.

The output transistor (Y or Y) turns on when the count is greater than or equal to the corresponding preset. Figure 1-2 shows the field output operation. You can invert this operation by setting the appropriate bits in the setup word, WY4. See Section 4.1.

Overview 1-5 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 8 more labels / short text on this page
Y Output · Output Return · Output Circuit · · · Counter Value · Figure 1-2 Output ·
Page 12 of the Siemens SIMATIC 505 user manual — 1.4 LED Indicators
Seite 12 · Zum Vergrößern klicken
Seite 12

1.4 LED Indicators

Each channel contains four LED indicators which provide a visual indication of the channel’s status as shown in Figure 1-3.

Figure 1-3 High Speed Counter LEDs

Turns on when there is current flow through the A input.

Turns on when there is current flow through the B input.

Turns on when Output 1 is on.

Turns on when Output 2 is on.

If Reset or Inhibit is turned on, the HSC does not count, and the A and B LEDs are frozen.

1-6 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 13 of the Siemens SIMATIC 505 user manual — 1.5 Counting Modes
Seite 13 · Zum Vergrößern klicken
Seite 13

1.5 Counting Modes

1.5.1 Pulse Counter Each channel has two inputs, A and B. In the pulse counter mode, counting Mode occurs on the rising or falling edge of the incoming pulses. The relationship of the states of these two inputs determines the direction of the count. See Table 1-1. Typical devices for counting are high-speed static switches or incremental encoders.

Table 1-1 Determining Count in Pulse Counter Mode

Counter Direction Edge A Input B Input

In the pulse counter mode, the channel senses the edges of the A or the B input to count up or down. See Figure 1-4. To reliably record this transition from low to high, the pulse width must be at least 8 s.

2 3 2 1 8 s min

11 s min

Count Up Count Down

Figure 1-4 Pulse Counter Mode 0

Overview 1-7 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 17 more labels / short text on this page
up up · ” · high · # · low · down · ” · high · down · # · low · Pulse Counter Mode · Count Value · Count Input · Input A · Input B ·
Page 14 of the Siemens SIMATIC 505 user manual — B
Seite 14 · Zum Vergrößern klicken
Seite 14

Counting Modes (continued)

1.5.2 Quadrature Mode For quadrature mode, each channel counts according to rising and/or falling edges. Typical devices for quadrature inputs are optical encoders. Different quadrature modes are selected based on the resolution required by the application and the encoder used.

1.5.3 1X Quadrature The module counts on the edges of the A input pulses.

When input A leads input B, the HSC counts up on each rising edge of input A.

When input B leads input A, the HSC counts down on the falling edge of input A.

Figure 1-5 illustrates the relationship between inputs A and B and the count value in 1X Quadrature mode.

1 2 1 0

A

26.7 s min

25 s min

B

Count Up (A Leading)

Figure 1-5 1X Quadrature Mode

1-8 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 4 more labels / short text on this page
1X Quadrature · Count Value · Count Down · (B Leading)
Page 15 of the Siemens SIMATIC 505 user manual — B
Seite 15 · Zum Vergrößern klicken
Seite 15

1.5.4 2X Quadrature If input A leads input B, the module counts up on both the rising and falling edges of input A. If input B leads input A, the module counts down on the rising and falling edges of input A.

Figure 1-6 illustrates the relationship between inputs A and B and the count value in the 2X quadrature mode.

1 2 3 4 3 2 1 0

A

26.7 s min

25 s min

B

Counts Up (A Leading)

Figure 1-6 2X Quadrature Mode

Overview 1-9 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 5 more labels / short text on this page
2X Quadrature · Count Value · Counts Down · (B Leading) ·
Page 16 of the Siemens SIMATIC 505 user manual — B
Seite 16 · Zum Vergrößern klicken
Seite 16

Counting Modes (continued)

1.5.5 4X Quadrature If input A leads input B, the module counts up on rising and falling edges of both input A and input B. If input B leads input A, the module counts down on the rising and falling edges of input A and input B.

Figure 1-7 shows the relationship between inputs A and B and the count value in the 4X quadrature mode.

1 2 3 4 5 6 7 8 7 6 5 4 3 2 1 0

A

26.7 s min

25 s min

B

Counts Up (A Leading)

Figure 1-7 4X Quadrature Mode

1-10 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 4 more labels / short text on this page
4X Quadrature · Count Value · Counts Down · (B Leading)
Page 17 of the Siemens SIMATIC 505 user manual — Chapter 2 Installation
Seite 17 · Zum Vergrößern klicken
Seite 17

Chapter 2 Installation

2.1 Before Installing the Module 2–2 2.1.1 Visual Inspection 2-2 2.1.2 Additional References 2-2 2.1.3 Handling the Module 2-2 2.1.4 General Wiring Considerations 2-3 2.1.5 Hierarchy of Installation 2-4

2.2 Selecting Counter Operation 2-5 2.2.1 Selecting Counter Mode 2-5 2.2.2 Selecting the Reset Filter 2-6

2.3 Inserting the Module in the I/O Base 2-7

2.4 Wiring the Module 2-8 2.4.1 Wiring the Terminal Block 2-8 2.4.2 Powering Up the Module 2-8

2.5 Logging the Module into the Controller 2-10 2.5.1 Updating the I/O Configuration Definition 2-10 2.5.2 Selecting the I/O Configuration 2-10 2.5.3 Viewing I/O Configuration Chart 2-11

Installation 2-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 18 of the Siemens SIMATIC 505 user manual — 2.1 Before Installing the Module
Seite 18 · Zum Vergrößern klicken
Seite 18

2.1 Before Installing the Module

2.1.1 Visual Inspection If there is any visible damage to the module, contact your Siemens Industrial Automation, Inc. distributor for replacement.

2.1.2 Additional Refer to the manuals listed below for instructions on installing, References programming, and troubleshooting your Series 505E controller.

SIMATIC TI545 System Manual (PPX:545–8101)

SIMATIC TI525/TI535 Hardware and Installation Manual (PPX:505–8103)

SIMATIC TI505 Programming Reference Manual (PPX:505–8104)

2.1.3 Handling the Many integrated circuit (IC) devices are susceptible to damage by the Module discharge of static electricity. Follow the suggestions listed below to reduce the probability of damage to these devices when you are handling a controller, a base controller, or any of the I/O modules.

Both the module and the person handling the module should be at the same ground potential. To accomplish this, ensure the following.

The module is transported in an anti-static container or antistatic material.

The work area has a conductive pad with a lead connecting it to a common ground.

You are grounded by making contact with the conductive pad and/or by wearing a grounded wrist strap.

2-2 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

Page 19 of the Siemens SIMATIC 505 user manual — 2.1.4 General Wiring Considerations
Seite 19 · Zum Vergrößern klicken
Seite 19

2.1.4 General Wiring The count, inhibit, and unfiltered reset inputs are high-speed inputs which Considerations may respond to noise present on the lines. To avoid problems, follow these guidelines when installing the HSC module.

Use the shortest possible wires.

Avoid placing signal wires parallel to high-energy wires. If the two must meet, cross them at right angles.

Avoid bending the wire into sharp angles.

Use wireways for wire routing.

When using shielded wires, ground them only at the source end for better noise immunity.

Place wires so that they don’t interfere with existing wiring.

Label the wires.

In some installations when both the HSC and TI505-49XX series of relay modules are used, false counts may be induced when switching high voltage in the relay module, (voltage > 40 Vrms). This is the result of internal arcing of the relay contacts.

If you encounter this problem, place a snubber consisting of a 47 ohm 1/4 watt resistor and a 0.022 Fd capacitor across the relay contact terminals on the terminal block. Snubbers were not included in the relay modules in order to meet the need for lower current leakage in many applications.

: Snubber components must be UL component recognized and/or CSA Certified for use across the rated voltage being switched by the relay module.

Installation 2-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 20 of the Siemens SIMATIC 505 user manual — Before Installing the Module (continued)
Seite 20 · Zum Vergrößern klicken
Seite 20

Before Installing the Module (continued)

2.1.5 Hierarchy of Figure 2-1 provides a simple flowchart of the installation process. Installation

Set Jumper Configuration on Module

Figure 2-1 Hierarchy of Installation

2-4 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

Show 4 more labels / short text on this page
Insert the Module · Connect Wires · Power Up · Log into Controller
Page 21 of the Siemens SIMATIC 505 user manual — 2.2 Selecting Counter Operation
Seite 21 · Zum Vergrößern klicken
Seite 21

2.2 Selecting Counter Operation

2.2.1 Selecting The HSC module has two channels. You can configure each channel Counter Mode to operate in any of four counter modes.

Prior to installing the module into the I/O backplane, configure the module by setting the jumper for each channel. Figure 2-2 shows the location of the jumpers on the printed circuit board. The top set of four pins set the counter mode for Channel 1. The bottom set of four pins set the counter mode for Channel 2. The default setting for the jumpers is 1X Quadrature mode for both channels.

CH 1 Jumper in SLW (filtered) position

CH 2 Jumper in FST (unfiltered) posi- tion

Figure 2-2 Jumper Settings

Each channel must have one (and only one) jumper installed.

Installation 2-5 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 22 of the Siemens SIMATIC 505 user manual — Selecting Counter Operation (continued)
Seite 22 · Zum Vergrößern klicken
Seite 22

Selecting Counter Operation (continued)

2.2.2 Selecting the Some applications require faster response on the reset input line than Reset Filter the standard 3.75-ms filter allows. For faster response, select the optional 0.95-ms filter. (The 0.9-ms filter is more sensitive to noisy signals, as noted in the Environmental Specifications in Appendix B.)

The reset filter may be selected independently for each input channel by placing the jumper in the (fast) or (slow) position as shown in Figure 2-2.

2-6 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

Page 23 of the Siemens SIMATIC 505 user manual — 2.3 Inserting the Module in the I/O Base
Seite 23 · Zum Vergrößern klicken
Seite 23

2.3 Inserting the Module in the I/O Base

The HSC is a single-wide module. Insert it into any available slot on any Series 505 I/O base. Do not touch the printed circuit board while inserting the module. This could cause electrostatic damage to the components on the board. Insert the module as shown in Figure 2-3.

! To minimize potential shock, turn off power to the I/O base and any modules installed in the base before inserting or removing a module. Failure to do so may result in potential injury to personnel or damage to equipment.

Figure 2-3 Inserting the Module into the I/O Base

Installation 2-7 Series 505 High Speed Counter and Encoder Module User’s Manual

Base Plane Connectors ·

Page 24 of the Siemens SIMATIC 505 user manual — 2.4 Wiring the Module
Seite 24 · Zum Vergrößern klicken
Seite 24

2.4 Wiring the Module

2.4.1 Wiring the Wiring the module consists of wiring the the input and output signals. Terminal Block See Figure 2-4 and Figure 2-5 for general guidelines. All connections are made at the module terminal block. See Figure 2-5. Output returns for Channel 1 and 2 are internally connected.

Use the Terminal Block Worksheet in Appendix B for planning your wiring.

! Turn off power to the I/O base and any modules installed in the base before inserting or removing a module. Failure to do so may cause potential injury to personnel or can damage equipment.

2.4.2 Powering Up After wiring the terminal block for the HSC, restore power to the the Module base.

1 cm Wire Gauge: 22–16

Max. W idth5.54 mm ( . 218 in.)
Stud Size#4 (2.5mm) Amp Part#: 321462
Max. W idth4.62 mm ( . 182 in.)
Stud Size#4 (2.5mm) Amp Part#: 327891 (Specify 2pt. connector)

Figure 2-4 Wiring Guidelines

2-8 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

Page 25 of the Siemens SIMATIC 505 user manual — 5–24 VDC
Seite 25 · Zum Vergrößern klicken
Seite 25

5–24 VDC

5–24 VDC

5–24 VDC

Figure 2-5 Sample Terminal Block Wiring Diagram

Installation 2-9 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 28 more labels / short text on this page
Sinking · Driver · Ch1 A+ · Ch1 A– · Ch1 B+ · Ch1 B– · Ch1 RST+ · Encoder · Ch1 RST– · Ch1 INH+ · Ch1 INH– · + – · Ch1 Y1 · Ch1 Y2 · 5–24 VDC Sourcing · Driver · Ch2 A+ · Ch2 A– · Ch2 B+ · Ch2 B– · Ch2 RST+ · Ch2 RST– · Ch2 INH+ · Ch2 INH– · + – · Ch2 Y1 · Ch2 Y2 ·
Page 26 of the Siemens SIMATIC 505 user manual — 2.5 Logging the Module into the Controller
Seite 26 · Zum Vergrößern klicken
Seite 26

2.5 Logging the Module into the Controller

2.5.1 Updating the I/O After inserting the module into the base, update the I/O configuration Configuration in the controller. The module does not automatically onfigure itself. Definition A VPU or other programming device must be connected to the controller to register and verify controller module communication.

2.5.2 Selecting the I/O With your VPU or other programming device, select the I/O Configuration Configuration option. For example, if you have the module inserted into the first slot of the first I/O base, configure it as displayed in Figure 2-6. Refer to the manual that came with the programming device for instructions.

The HSC module is logged in as three input words (WX) and five output words (WY).

Displays number of the current base.

I/O MODULE DEFINITION FORCHANNEL 1 BASE 00

Slot Address X Y WX WY Function I/O Number of Bit and Word I/O Special

1 2 3 4 5 6

0001 0000

00

00

No

00

00

Install the HSC into any avail- able I/O slot on the Series 505 base.

e The HSC is not an SF Module. The default for this definition is NO.

Figure 2-6 Sample I/O Definition Chart

2-10 Installation Series 505 High Speed Counter and Encoder Module User’s Manual

0000 0000 · No No

Page 27 of the Siemens SIMATIC 505 user manual — I/O POINTS
Seite 27 · Zum Vergrößern klicken
Seite 27

2.5.3 Viewing the I/O Use SHOW to view the I/O Configuration Chart. If the HSC is Configuration installed in slot 1, for channel 1, base 00, the I/O chart will appear Chart as displayed in Figure 2-7.

I/O CONFIGURA TION CHART FORCHANNEL 1, BASE 00

I/O POINTS

00000 WX001 WX002 WX003 WY004 WY005 WY006 WY007 WY008

Slot 2 Slot 3 Slot 4 Slot 5 Slot 6

00000

00000

00000

00000

00000

00000

00000

00000

Figure 2-7 I/O Configuration Chart

Installation 2-11 Series 505 High Speed Counter and Encoder Module User’s Manual

Slot 1 ·

Page 28 of the Siemens SIMATIC 505 user manual — Chapter 3 Programming
Seite 28 · Zum Vergrößern klicken
Seite 28

Chapter 3 Programming

3.1 Controller Input Words 3-2

3.1.1 WX1 (Status Word) 3-2 3.1.2 WX2 and WX3 (Channel Count) 3-3 3.1.3 WY4 (Setup Word) 3-3 3.1.4 WY5 – WY8 (Preset Words) 3-4 3.1.5 I/O Update Consideration 3-4

Programming 3-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 29 of the Siemens SIMATIC 505 user manual — LSB
Seite 29 · Zum Vergrößern klicken
Seite 29

3.1 Controller Input Words

The HSC module is configured as three word inputs (WX) and five word outputs (WY). It occupies eight words of the controller’s word image register.

3.1.1 WX1 (Status Word) Word 1 (WX) is the module’s status word. Eight bits provide the status of each of the two channels. Figure 3-1 shows the format of the status word.

BIT

MSB

CH 1 — RESET ST ATUS

(1 = Counter reset)

CH 1 — INHIBIT STATUS (1 = Count inhibited)

CH 1 — OUTPUT 1 ST ATUS

CH 1 — OUTPUT 2 ST ATUS

CH 2 — RESET STATUS (1 = Counter reset)

CH 2 — INHIBIT ST ATUS

(1 = Counts inhibited)

CH 2 — OUTPUT 1 STATUS (1 = On)

CH 2 — OUTPUT 2 STATUS (1 = On)

Reserved and will be returned as zeros

LSB

Figure 3-1 Status Word Format

Each channel has a Reset Status bit in the status word. If the channel’s RESET field input is active, this bit will be 1; otherwise this bit will be 0.

The Reset Command bit (see Setup Word, Section 3.1.3) does not affect the reset status bit.

Programming 3-2 Series 505 High Speed Counter and Encoder Module User’s Manual

(1 = On) · (1 = On)

Page 30 of the Siemens SIMATIC 505 user manual — LSB
Seite 30 · Zum Vergrößern klicken
Seite 30

Each channel has an Inhibit Status bit in the status word. If the channel’s field input is active or if its Inhibit Command bit is 1 (see Setup Word, Section 3.1.3), this bit will be 1 and the counter will not count. Otherwise, this bit will be 0.

Each channel has an Output 1 Status and an Output 2 Status bit in the status word. If the corresponding field output is on, the bit will be 1. Otherwise, the bit will be 0.

3.1.2 WX2 and WX3 Word 2 (WX2) contains the current value of the Channel 1 count (Channel Count) register, and Word 3 (WX3) contains the current value of the Channel 2 count register. These values are unsigned integers between 0 and 65,535 (inclusive). 3.1.3 WY4 (Setup Word) Word 4 (WY4) is the module setup word. The controller uses eight bits to control the HSC module’s operation. See Figure 3-2.

BIT

MSB

CH 1 — RESET (1 = Reset counter; default: 0)

CH 1 — INHIBIT (1 = Inhibits counts; default: 0)

CH 1 — OUTPUT 1 0: Count P = On (default) 1: Count < P = On CH 1 — OUTPUT 2

CH 2 — RESET (1 = Reset counter; default: 0)

CH 2 — INHIBIT (1 = Inhibits counts; default: 0)

CH 2 — OUTPUT 1

0. Count P = On (default) 1: Count < P = On

CH 2 — OUTPUT 2

Reserved and should be set to 0 (off)

LSB

Figure 3-2 Setup Word Format

Programming 3-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 31 of the Siemens SIMATIC 505 user manual — Controller Input Words (continued)
Seite 31 · Zum Vergrößern klicken
Seite 31

Controller Input Words (continued)

Both channels have a Reset Command bit. A transition from 0 (off) to 1 (on) of the Reset Command acts as a one-shot (providing a momentary reset of the channel), setting the count to 0. Even though the bit remains 1, counting resumes.

Both channels have an Inhibit Command bit. When this bit is set to 1, the channel stops counting.

When in the pulse counter mode, if the A or B input is in a different state at the beginning and end of an inhibit signal, the count will change according to the normal counting logic. If both A and B inputs are in different states, the change may be as much as two counts.

The output level bit specifies when the outputs for each channel turn on.

Setting the output level bit to 0 turns the output on when the current count is greater than or equal to the preset. If the current count is less than the preset, the output is off.

Setting the output level bit to 1 turns the output on when the current count is less than the preset. If the current count is greater than or equal to the preset, the output is off.

3.1.4 WY5 – WY8 Words WY5 through WY8 specifies preset values for each channel. (Preset Words) You can specify any value between 0 and 65,535.

specifies the value for Preset 1, Channel 1.

specifies the value for Preset 2, Channel 1.

specifies the value for Preset 1, Channel 2.

specifies the value for Preset 2, Channel 2.

3.1.5 I/O Update In each scan, the controller reads the module WX words before updating Consideration the WY words. For example, during a scan when the controller resets the module, the WX word(s) contain counter values existing prior to the reset.

Programming 3-4 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 32 of the Siemens SIMATIC 505 user manual — Chapter 4 Troubleshooting
Seite 32 · Zum Vergrößern klicken
Seite 32

Chapter 4 Troubleshooting

Symptom Probable Cause Corrective Action

Input LED is not on and Output LED is not on

No power to board

Check for bent pins on board connector

Check your base power supply Check wiring Check encoder or field inputs

Problems with input signals, or output being reset or inhibited

Check Reset and Inhibit bits in Setup word (WY4)

Counts in wrong direction

Reverse wiring for inputs A and B

Input wires substantially different lengths

Check that wires are as short as possible, and make wires the same length (if possible)

Incorrect count Connections wrong

Trace wiring connections

Input wires substantially different lengths

Check that wires are as short as possible, and make wires the same length (if possible)

Broken wire Check continuity

Counts erratically Wrong quadrature mode or 2 jumpers on same chan- nel

Check jumper position and condition of jumper (metal insert intact)

See wiring considerations ( Section 2.1.4)

Broken wire Check continuity

Does not count Count being reset or in- hibited

Check Reset and Inhibit signals from field

Check Reset and Inhibit bits in Setup word (WY4)

Broken wire Check continuity

Counts too fast or too slow

Pulse too narrow, or frequency too high

Use slower gear ratio and higher resolution count

Check signal wire noise

Controller does not communicate with module

Module not configured in controller I/O configuration table

Nonfatal error as a result of the module

Module configured incorrectly in controller

Module has failed self-diagnostics

Return module for repair

Troubleshooting 4-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 8 more labels / short text on this page
Re-seat board · Connections wrong · Signal wire noise · Check quadrature mode · Marginal input signal · Configure module · Reconfigure the module ·
Page 33 of the Siemens SIMATIC 505 user manual — 4.1 Checking the Operation of the Module
Seite 33 · Zum Vergrößern klicken
Seite 33

4.1 Checking the Operation of the Module

To check the operation of the module, follow these steps.

Module outputs will turn on during this procedure.

1. Using a programming device, force all presets to 0.
2. Reset both counters through the reset signals from your application.

Using the default configuration, the outputs should turn on.

3. Using your programming device, force the presets to any number greater than 0.

The outputs should turn off.

Before resuming normal operation, clear any words that you have forced. Otherwise, these words remain forced during operation and could yield unexpected results.

If you used the setup word to configure the module, then the output follows your configuration.

To check the output operation look at the counter status word (WX1), the outputs correspond to the following bits.

Channel 1, Output 1 bit 3

Channel 1, Output 2 bit 4

0 = Output off 1 = Output on

Channel 2, Output 1 bit 7

Channel 2, Output 2 bit 8

4-2 Troubleshooting Series 505 High Speed Counter and Encoder Module User’s Manual

Page 34 of the Siemens SIMATIC 505 user manual — Chapter 5 Applications
Seite 34 · Zum Vergrößern klicken
Seite 34

Chapter 5 Applications

5.1 Sprayer Example 5-2

5.1.1 Description 5-2 5.1.2 Solution 5-3

5.2 Flow Rate Example 5-5

5.2.1 Description 5-5 5.2.2 Solution 5-5

5.3 Tank Filling Example 5-6

5.3.1 Description 5-6 5.3.2 Solution 5-6

Applications 5-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 35 of the Siemens SIMATIC 505 user manual — ÉÉÉÉÉÉÉÉÉÉ
Seite 35 · Zum Vergrößern klicken
Seite 35

5.1 Sprayer Example

5.1.1 Description A reversible DC motor drives a paint sprayer up and down a vertical assembly. A quadrature encoder on the drive shaft senses the direction and relative position of the sprayer. Channel 1 of the HSC will be used to enable the sprayer during a pre-defined section of travel. (See Figure 5-1.) The encoder resolution is 500 cycles per revolution. One shaft revolution equals 1 inch of sprayer travel. When encoder signal A leads, the direction of travel is up.

ÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉ

LS2 – Reverse Motor

LS1 – (Home) Reverses Motor

ÉÉÉÉÉÉÉÉÉÉ

Figure 5-1 Sprayer Application

Applications 5-2 Series 505 High Speed Counter and Encoder Module User’s Manual

“Stop Spray” · “Start Spray”

Page 36 of the Siemens SIMATIC 505 user manual — LS1 P1 P2 LS2 P2 P1 LS1
Seite 36 · Zum Vergrößern klicken
Seite 36

5.1.2 Solution Connect encoder signals A and B to inputs A and B of the HSC. See Figure 5–2. Limit switch 1 (sprayer home) drives channel 1 Reset. Channel 1 outputs 1 and 2 are wire ORed and drive the sprayer enable. Select 1X Quadrature mode for channel 1, setup channel 1 output 1 to turn off when count preset, output 2 to turn on when count preset. Presets 1 and 2 are loaded with the Start Sprayer and Stop Sprayer counts, respectively. The Start Sprayer count = 500 X Distance (inches) from LS1 to Start Sprayer position. The Stop Sprayer count = 500 X Distance (inches) from LS1 to Stop Sprayer position.

LS1

Figure 5-2 HSC Connections

As the sprayer moves up and down, the channel 1 outputs and the sprayer enable signal levels produce the waveform shown in Figure 5-3.

Travels Up Travels Down

LS1 P1 P2 LS2 P2 P1 LS1

OUTPUT 1 OUTPUT 2

OFF ON OFF ON OFF

Figure 5-3 Waveform Pattern

Applications 5-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 10 more labels / short text on this page
Encoder A · Input A · Encoder B · Input B · Reset · Output 1 · Output 2 · Sprayer Travel · Sprayer Enable ·
Page 37 of the Siemens SIMATIC 505 user manual — C15 C14
Seite 37 · Zum Vergrößern klicken
Seite 37

Sprayer Example (continued)

SETUP CHANNEL 1 OUTPUT 2 TO GO LOW AT PRESET

SELECT COUNT INHIBIT ON CHANNEL 1

CLEAR CHANNEL 1 SETUP WORD

LDC1

BITS1

BITS2

A:

WY4

A:

WY4

A:

WY4

N=

N=

N=

LOADS CHANNEL 1 PRESETS 1 & 2 FROM V200 & V201

INHIBIT CHANNEL 1 BIT IS CLEARED COUNTING IS ENABLED

C15 C14

MOVW1

BITC23

A:

A:

WY4

B: WY5

N=

N=

Figure 5-4 Ladder Logic for Sprayer Example

Applications 5-4 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 38 of the Siemens SIMATIC 505 user manual — C25 C23
Seite 38 · Zum Vergrößern klicken
Seite 38

5.2 Flow Rate Example

5.2.1 Description A flow meter outputs 200 pulses per gallon. The program requires calculation of flow rate in gallons per minute (GPM). 5.2.2 Solution Configure the HSC as WX9–WX11, WY12–WY16. Attach channel 1 to the flow meter. The HSC accumulates flow meter pulses for the duration of a 1-second fast timer. In the controller, accumulated pulses are scaled to GPM by the following calculation (using the controller memory locations).

Following each calculation, reset the HSC, restart the Timer, and perform a new calculation 1 second later.

: ONE SECOND TIMER HAS EXPIRED, COMPUTE FLOW RESTART TIMER ON NEXT SCAN

C23 C20

TMRF2

P= 01.000

: SCALE COUNTER VALUE IN GALS/MINUTE PUT RESULTS IN LOCATIONS V23–V24, RESET HSC CHANNEL 1

C24 C23

MULT1

DIV1

BITS1

A: WX10

A: V21

A:

WY12

B: C:

V20 V21

B: C:

V19 V23

N=

: TURN OFF CHANNEL 1 RESET TO HSC

C25 C23

BITC1

A:

WY12

N=

Figure 5-5 Ladder Logic for Flow Rate Example

Applications 5-5 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 39 of the Siemens SIMATIC 505 user manual — Y20
Seite 39 · Zum Vergrößern klicken
Seite 39

5.3 Tank Filling Example

5.3.1 Description The HSC module measures the volume of liquid and control the filling valve. (See Figure 5-6.) A flow meter, generating 200 pulses per gallon, is connected to the HSC channel 2, input A. Output 2 controls the filling valve. In this example, the HSC operates in the pulse counter mode.

Solution A count of 100,000 pulses is required to fill the tank to 500 gallons. As this would overflow the HSC, the following RLL is used to count 10 sets of 10,000 pulses before closing the filling valve. In this program, output 1 is used to indicate 10,000 pulses. Since the HSC runs asynchronous to the PLC, the program accumulates overcounts for each loop and adjusts the final loop to reach the exact count. The program utilizes the fact that the HSC WX’s are read before the WY’s are written in an I/O cycle.

Several V memory locations are used in the program, their initial values are:

V200 = 10,000 = channel 2, preset 1

V201 = 30,000 = channel 2, preset 2 initial value

V100 = 0 (overcounts will be accumulated here)

Y20

Figure 5-6 Tank Filling Application

Applications 5-6 Series 505 High Speed Counter and Encoder Module User’s Manual

· HSC Channel 2

Page 40 of the Siemens SIMATIC 505 user manual — X128 C140
Seite 40 · Zum Vergrößern klicken
Seite 40

C140 IS USED TO INITIATE/TERMINATE FILLING

X128 C140

C140 C256

: RESET HSC, LOAD INIT AL PRESETS

C140 C1

Y20

LDC4

BITS1

MOVW1

A: WY4

A: WY4

A: V200

B: WY7

N = 0

N = 5

N = 2

C141 : CLEAR RESET BIT

BITC1

A: WY4

N = 5

Y20

: ENABLE LIQUID FLOW

C1 Y20

Y20 C140

Figure 5-7 Ladder Logic for Tank Filling Example

Applications 5-7 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 41 of the Siemens SIMATIC 505 user manual — C51 C8 Y20
Seite 41 · Zum Vergrößern klicken
Seite 41

Tank Filling Example (continued)

: ACCUMULA TE THE OVERCOUNTS

SUB1

ADD1

A: WX3

A: V101

B: V200

B: V100

C: V101

C: V100

: AFTER 90,000 PULSES, SUBTRACT THE OVERCOUNTS FROM 10,000

AND LOAD THE REMAINING COUNT INTO PRESET 2.

CTR2

SUB2

MOVW2

P = 9

A: V200

A: V201

B: V100

B: WY7

WY8 C140

C:

N = 1

: TEST FOR COMPLETION OF 100,000 COUNTS, INHIBIT FURTHER

COUNTS, AND CLEAR OVERCOUNT ACCUMULATOR. C256 WILL THEN TURN OFF C140 AND DISABLE THE VALVE.

C8 C256

BITP2

BITS2

LDC3

A: WX1

A: WY4

A: V100

N = 6 N = 8

N = 0

C51WHEN HSC CH2 OUTPUT 1 TURNS ON, PULSE COUNT IS 10,000

OR GREATER, RESET COUNTER AND START NEW COUNT.

C51 C8 Y20

BITP5

BITS5

A: WX1

A: WY4

N = 7

N = 5

Figure 5-7 Ladder Logic for Tank Filling Example (continued)

Applications 5-8 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 42 of the Siemens SIMATIC 505 user manual — Appendix A Terminal Block W orksheet
Seite 42 · Zum Vergrößern klicken
Seite 42

Appendix A Terminal Block W orksheet

Terminal Block Worksheet A-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 43 of the Siemens SIMATIC 505 user manual — Appendix B Specifications
Seite 43 · Zum Vergrößern klicken
Seite 43

Appendix B Specifications

B.1 Environmental Specifications B-2

B.2 Electrical Specifications B-3

B.3 Additional Compliances B-6

Specifications B-1 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 44 of the Siemens SIMATIC 505 user manual — B.1 Environmental Specifications
Seite 44 · Zum Vergrößern klicken
Seite 44

B.1 Environmental Specifications

Table B-1 Environmental Specifications

Operating Temperature 0 to 60C (32 to 140F)

Storage Temperature –40 to 70C (–40 to 158F)

Relative Humidity 5% to 95% noncondensing

Pollution Degree 2, IEC 664, 664A

Sinusoidal IEC 68–2–6, Test Fc; 0.15 mm, peak-to-peak, 10-57 Hz; 1.0 g 57-150 Hz Random NAVMAT P–9492 or IEC 68–2–34, Test Fdc with 0.04 g/Hz, 80–350 Hz, and 3 dB/octave rolloff, 80–20 Hz and 350–2000 Hz at 10 min/axis

Impact Shock IEC 68–2–27, Test Ea; Half Sine, 15 g, 11 ms

Electrostatic Discharge2 IEC 801, Part 2, Level 4 (15 kV)1

Electrical Noise Immunity IEC 801, Part 4, Level 3 Conducted2 MIL STD 461B, Part 4; CS01, CS02, CS061 IEC 255–4, Appendix E1 EEC 4517/79 Com(78) 766 Final, Part 4 IEEE 472, 2.5 kV

Radiated IEC 801, Part 3, Level 3 MIL STD 461B, Part 4; RS01, RS02

Corrosion Protection All parts are of corrosion resistant material or are plated or painted as corrosion protection.

Agency Approvals UL Listed, CSA Certified

1The unfilltered reset input may be susceptible to these types of EMI. 2The module responds to noise signals at its count or inhibit inputs that are within its passband.

Specifications B-2 Series 505 High Speed Counter and Encoder Module User’s Manual

Vibration

Page 45 of the Siemens SIMATIC 505 user manual — ÉÉÉÉÉÉÉÉÉÉÉÉ
Seite 45 · Zum Vergrößern klicken
Seite 45

B.2 Electrical Specifications

Table B-2 Electrical Specifications

Duty Count Mode Quadrature Mode

10% 10 Khz 4 Khz 20% 25 Khz 8 Khz 25% 30 Khz 10 Khz 30% 35 Khz 12 Khz 40% 50 Khz 15 Khz 50% 45 Khz 15 Khz 60% 35 Khz 15 Khz

On voltage: 4 to 28 VDC, Class 2 supply Current on: 8 to 16 mA Off voltage: –1.5 to 1.5 VDC Current off: 0 to 1 mA

Volt–Ampere Curve for Count Inputs

ÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉ

ÉÉÉÉÉÉÉÉÉÉÉÉ

4 6 8 10 12 14 16

ÉÉ Off Region Transition Region On Region

Specifications B-3 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 6 more labels / short text on this page
Count Inputs · Frequency (maximum) · Min Max · Vin (Volts) · Iin (mA) ·
Page 46 of the Siemens SIMATIC 505 user manual — É
Seite 46 · Zum Vergrößern klicken
Seite 46

Electrical Specifications (continued)

Count inputs are constant current type inputs.

Reset and Inhibit Inputs:

On voltage: to 28 VDC, Class 2 supply Current on: 2 to 40 mA Off voltage: –1.5 to 1.5 VDC Current off: 0 to 0.75 mA Reset delay time: unfiltered 950 s on 950 s off filtered 3.75 ms on 5.00 ms off Inhibit delay time: 200 s on 200 s off

Volt–Ampere Curve for Reset and Inhibit Inputs

ÉÉÉ

ÉÉÉ

10 20 30 40

É

Off Region Transition Region On Region

É

Specifications B-4 Series 505 High Speed Counter and Encoder Module User’s Manual

Min Max · Vin (Volts) · Iin (mA)

Page 47 of the Siemens SIMATIC 505 user manual — T (  C)
Seite 47 · Zum Vergrößern klicken
Seite 47

User voltage: 28 VDC max Voltage drop: 1.8 VDC max. @ 400 mA

1.0 VDC max. @ 25 mA Leakage current: 500 A max Peak current: 500 mA for 1 ms Output current:

1 Point per channel

2 Points per channel

20 40 60 80 100

T ( C)

Isolation:

User-side to P/C-side 1500 V rms

Channel 1 to 2 (inputs) 1500 V rms

Channel 1 to 2 (outputs) 0 V rms

Inputs to outputs 1500 V rms

Power Required from Base: 2.5 W

Response Time 1.1 ms (Input pulse to output action)

Specifications B-5 Series 505 High Speed Counter and Encoder Module User’s Manual

Show 5 more labels / short text on this page
Outputs · I(mA) · 275 mA · 175 mA ·
Page 48 of the Siemens SIMATIC 505 user manual — B.3 Additional Compliances
Seite 48 · Zum Vergrößern klicken
Seite 48

B.3 Additional Compliances

In addition, the system complies with applicable requirements of Verband Deutscher Elektrotechniker (VDE) 0160: Electrical Equipment

Series 505 products have been developed with consideration of the draft standard for programmable controllers as described in the proposed standard of the International Electrotechnical Commission Committee (IEC–65A/WG6, Part 2).

Information concerning product reliability and compliance to the IEC or other standards can be provided upon request. Contact your Siemens Industrial Automation, Inc. distributor for additional information.

Specifications B-6 Series 505 High Speed Counter and Encoder Module User’s Manual

Page 49 of the Siemens SIMATIC 505 user manual — Customer Registration
Seite 49 · Zum Vergrößern klicken
Seite 49

Customer Registration

We would like to know what you think about our user manuals so that we can serve you better. How would you rate the quality of our manuals?

Excellent Good Fair Poor

Accuracy Organization Clarity Completeness Overall design Size Index

Would you be interested in giving us more detailed comments about our manuals?

Yes! Please send me a questionnaire.

No. Thanks anyway.

Your Name:

Title:

Telephone Number( )

Company Name:

Company Address:

Manual NameHigh Speed Counter and Encoder Module User Manual Edition: Second
Manual Assembly Number2586546-0019 Date: 12/92
Order NumberPPX:505–8113–2
Page 50 of the Siemens SIMATIC 505 user manual — FOLD
Seite 50 · Zum Vergrößern klicken
Seite 50

FOLD

NO POST AGE

NECESSARY

IF MAILED

IN THE UNITED ST ATES

BUSINESS REPL Y MAIL

FIRST CLASS PERMIT NO.3 JOHNSON CITY , TN

POST AGE WILL BE P AID BY ADDRESSEE

SIEMENS INDUSTRIAL AUTOMATION, INC. 3000 BILL GARLAND RD. P.O. BOX 1255 JOHNSON CITY TN 37605–1255

ATTN: Technical Communications M/S 3519

FOLD

Page 52 of the Siemens SIMATIC 505 user manual — W
Seite 52 · Zum Vergrößern klicken
Seite 52

Q

T

Quadrature Mode, quadruple count, 1-10

Terminal block, 2-8

wiring diagram, 2-9 worksheet, 2-8

double-count, 1-9 single-count, 1-8

Quadruple count, quadrature mode, 1-10

U

R

Using status words, 3-2

W

S

Wiring, 2-3, 2-8

Static electricity, 2-2

Show 6 more labels / short text on this page
Quadrature mode · References, 2-2 · Reset, 1-2, 1-4 · Single-count quadrature, 1-8 · considerations, 2-3 · Index-2
Page 53 of the Siemens SIMATIC 505 user manual — Index
Seite 53 · Zum Vergrößern klicken
Seite 53

SIMATIC is a registered trademark of Siemens AG.

Series 505 and TISOFT are trademarks of Siemens Industrial Automation, Inc.

Texas Instruments and TI are registered trademarks of Texas Instruments Incorporated.

TI505, TI525, TI535, and TI545 are trademarks of Texas Instruments Incorporated.

UL is a registered trademark of Underwriters Laboratories.

Reparatur

Fehlerbehebung

Häufige Probleme, wahrscheinliche Ursachen und Lösungen.

ProblemMögliche UrsacheAbhilfe
Input LED is not on and Output LED is not onNo power to boardRe-seat board p.32
Input LED is not on and Output LED is not onCheck for bent pins on board connector p.32
Input LED is not on and Output LED is not onCheck your base power supply p.32
Input LED is not on and Output LED is not onProblems with input signals, or output being reset or inhibitedCheck wiring p.32
Input LED is not on and Output LED is not onCheck encoder or field inputs p.32
Input LED is not on and Output LED is not onCheck Reset and Inhibit bits in Setup word (WY4) p.32
Counts in wrong directionConnections wrongReverse wiring for inputs A and B p.32
Counts in wrong directionInput wires substantially different lengthsCheck that wires are as short as possible, and make wires the same length (if possible) p.32
Incorrect countConnections wrongTrace wiring connections p.32
Incorrect countInput wires substantially different lengthsCheck that wires are as short as possible, and make wires the same length (if possible) p.32
Incorrect countBroken wireCheck continuity p.32
Counts erraticallyWrong quadrature mode or 2 jumpers on same chan- nelCheck jumper position and condition of jumper (metal insert intact) p.32
Counts erraticallySignal wire noiseSee wiring considerations ( Section 2.1.4) p.32
Counts erraticallyBroken wireCheck continuity p.32
Does not countCount being reset or in- hibitedCheck Reset and Inhibit signals from field p.32
Does not countCheck Reset and Inhibit bits in Setup word (WY4) p.32
Does not countBroken wireCheck continuity p.32
Counts too fast or too slowPulse too narrow, or frequency too highUse slower gear ratio and higher resolution count p.32
Counts too fast or too slowCheck quadrature mode p.32
Counts too fast or too slowCheck signal wire noise p.32
Counts too fast or too slowMarginal input signal p.32
Controller does not communicate with moduleModule not configured in controller I/O configuration tableConfigure module p.32
Nonfatal error as a result of the moduleModule configured incorrectly in controllerReconfigure the module p.32
Nonfatal error as a result of the moduleModule has failed self-diagnosticsReturn module for repair p.32

Frage zu Siemens SIMATIC 505 stellen

Besitzer und unser Team antworten in der Regel innerhalb eines Tages – und Ihre Frage hilft auch anderen weiter.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Noch keine Fragen zu Siemens SIMATIC 505

Stellen Sie die erste Frage — andere Nutzer oder unser Team antworten Ihnen.

Originaldokument

Siemens SIMATIC 505 PDF-Anleitung

53 Seiten·297 KB·Haustierzaun·PDF
Klicken Sie oben auf eine Seite, um sie hier zu öffnen
Seite 1 / …
100%
Seiten werden geladen…